2

Definitions:

 

Normally closed contacts (NC)
Normally open contacts (NO)

FACP -   Fire Alarm Control Panel
ACC -   Access Control Contacts
FS - 

Fail safe (needs power to lock) 

See Section 10 for an explanation 

of the Warnings and Cautions 

used in this booklet. 

FSE -  Fail secure (needs power to unlock) 

 

Installation Overview

Wiring methods shall be applied in accordance with the National Electric Code/NFPA 70/NFPA 72/ANSI, and with all local codes and 

authorities having jurisdiction. 

 WARNING

To avoid risk of electric shock, turn off AC power before 

installing or servicing LP150/LP250 power supply. 

1.  Mount unit in a protected area

 

per Section 2. 

 

 

2.  Select voltage (12 or 24 VDC) per Section 3.

 

3. 

Connect AC power

 

per Section 3.

• 

Connect the earth ground to the green/yellow cabinet wire and line (L) and neutral (N) to the appropriate terminals on the AC 

terminal block. 

 

̢

Measure output voltage before connecting devices to prevent damage.

4.  Disconnect AC power and finish all wiring per Sections 4 and 6.

5.  Install battery backup (if required)

 

per Sections 2 and 3.

 

̢

If AC input goes off and battery backup is not being used, all devices connected to the power supply will be unpowered. 

6.  AC status may be required for Battery Backup systems

 

(Section 3).

 

7.  Secure cover with screws or keylock when complete per Section 7. 

8.  For maintenance and troubleshooting, see Sections 8 and 9. 

Содержание LP150

Страница 1: ...B4 12 VDC 13 2V nominal or 24 VDC 26 4V nominal 2 5A Class 2 rated Output Protection DC OUT and CONTROL OUT are protected from overload or shorts via self resetting electronic protection circuit Batte...

Страница 2: ...er supply 1 Mount unit in a protected area per Section 2 2 Select voltage 12 or 24 VDC per Section 3 3 Connect AC power per Section 3 Connect the earth ground to the green yellow cabinet wire and line...

Страница 3: ...er 10 11 Enclosure Dimensions Mounting Hole Dimensions Battery Backup Time 12 13 3 Cover not shown for clarity Enclosure mounting screws not provided Calculated battery backup time based on charging t...

Страница 4: ...ut NC to DC DC out NO to DC 0V CONTROL 24VDC BATTERY CONFIGURATION 12V BATTERY 12V BATTERY Yellow Black Red 12V BATTERY Red Black 12VDC BATTERY CONFIGURATION OR 24V 12V BAT BAT 120VAC NOT present on i...

Страница 5: ...inals 2 Opening of the FACP contacts will unpower the CONTROL OUT NC contacts and power the NO contacts 3 DC OUT is always powered regardless of the state of the FACP contacts FSE device using open in...

Страница 6: ...nimum The gauge can be increased if desired Distance total one way wiring distance between power supply and powered device includes both power wires For UL installations the minimum permissible wire s...

Страница 7: ...No Keylock Enclosure will be secured with 2 screws as shown done as last step If Keylock Remove knockout and insert key cylinder and secure with nut as shown exterior of door interior of door a b c 6...

Страница 8: ...fer to Section 3 for LED status of the AC input DC output and Battery to determine the cause for any abnormal condition Each LED has the definition of its ON or OFF state 10 Warnings and Cautions WARN...

Страница 9: ...2 V 13 2V nominal ou 24 V 26 4V nominal 2 5A classe 2 Protection de sortie Les ports DC OUT et CONTROL OUT sont prot g s contre les surcharges et les courts circuits gr ce un circuit de protection lec...

Страница 10: ...zone prot g e conform ment la section 2 2 S lectionnez la tension 12 ou 24 V selon la section 3 3 Branchez l alimentation CA conform ment la Section 3 Connectez la mise la terre au fil vert jaune de l...

Страница 11: ...Dimensions du trou d installation Temps de sauvegarde de la batterie 12 5 8 po 13 po 3 1 4 po Couverture non illustr e pour plus de clart Vis d installation du bo tier non fournies L installation de l...

Страница 12: ...issant une batterie de secours 120 V NON pr sent l entr e 120 V pr sent l entr e d sactiv activ 120 V ligne verte Sortie CC d sactiv e ou en court circuit surcharge Sortie DC activ e 12 ou 24V LED rou...

Страница 13: ...des contacts de l ACC alimentera la frappe FSE pour la d verrouiller ENTR E DES CONTR LES SORTIE DES CONTR LES SORTIE CC NC NO DC IN C DC DC LP150 250 FACP ACC SORTIE CC CONTINUE FS MAGLOCK Op ration...

Страница 14: ...peut tre augment e si vous le souhaitez Distance distance totale de c blage unidirectionnel entre l alimentation et le p riph rique aliment inclut les deux c bles d alimentation Pour les installation...

Страница 15: ...o tier sera fix avec 2 vis comme indiqu la derni re tape Si une serrure est pr sente Retirez la d coupe ins rez le barillet et fixez le avec l crou comme indiqu ext rieur de la porte int rieur de la p...

Страница 16: ...le Chaque voyant a la d finition de son tat ON ou OFF 10 Avertissements et mises en garde Les avis indiquent une condition pouvant uniquement causer des dommages mat riels Les avertissements ressemble...

Отзывы: