5
4
Typical Wiring
FS & FSE device connected to
PS board with FACP override
NC
NO
DC-
IN
C
DC+
DC-
CONTROL
IN
CONTROL
OUT
DC
OUT
LP150/250
FACP
ACC
ACC
FSE
E-STRIKE
CONTINUOUS
DC OUTPUT
+
+
FS
MAGLOCK
+
Operation:
1. CONTROL IN controls the operation of devices connected to the NO
or NC terminals.
2. Opening of the FACP contacts will unpower the CONTROL OUT NC
contacts and power the NO contacts.
3. DC OUT is always powered regardless of the state of the FACP
contacts.
FSE device using open input
control contacts
NC
NO
DC-
IN
C
DC+
DC-
CONTROL
IN
CONTROL
OUT
DC
OUT
LP150/250
FSE
E-STRIKE
CONTINUOUS
DC OUTPUT
+
+
Operation:
1. CONTROL IN controls the operation of the strike connected to the
NC terminal.
2. Closing the ACC contacts will apply power to the FSE strike to unlock it.