Installation & Operation Manual

6

DHW prioritization

This piping system is designed to provide direct hot water 
priority over the other zones in the heating system.  When 
there is a Domestic Hot Water (DHW) call for heat, the 
Knight control will shut off the boiler circulator and activate 
the domestic hot water circulator.  Once the DHW demand 
is satisfied, the boiler circulator will be readjusted as demand 
requires.  The circulator must be large enough to move the 
boiler water through the coils.  The recommended piping for a 
DHW priority system is depicted in FIG. 3-3 on page 9.

Multiple tank connections (boiler side)

Multiple tank installations must be done in the “reverse-return” 
manner.  The reason for this is to create the same pressure drop 
(and therefore, the same flow) through the coil of each tank.  
The boiler manifold piping must be sized so that each coil has 
the flow rate called for in Table 3B.  

Because the pressure drop through tank coils varies from size 
to size, it is hard to predict the flow rate that will be developed 
through each coil when two tanks of different sizes are placed 
in the same manifold.  For this reason it is best not to mix tanks 
of different sizes in the same zone if their recovery is critical.

Table 3B

Pressure Drop Values

MODEL

WATER

INLET

(NPT) 

WATER

OUTLET

(NPT) 

COIL 

CONNECTION

(NPT)  

COIL 

LENGTH

(FT)  

SQ FT 

SURFACE

AREA 

PRESSURE DROP

(FT/HD)

GPM

8

 GPM

12 

GPM

16

GPM

20 

GPM

25

GPM

30 

GPM

SIT040

1

1

1

36.5

12.05

0.87

1.99

4.05

6.00

9.89

14.62

20.11

SIT050

1

1

1

36.5

12.05

0.87

1.99

4.05

6.00

9.89

14.62

20.11

SIT065

1.5

1.5

1

44

15.03

0.94

2.14

4.35

7.20

10.64

15.72

21.63

SIT080

1.5

1.5

1

44

15.03

0.94

2.14

4.35

7.20

10.64

15.72

21.63

SIT119

1.5

1.5

1

44

15.03

0.94

2.14

4.35

7.20

10.64

15.72

21.63

3  

Boiler side piping 

Figures 3-1 thru 3-4 show typical boiler side piping for 
several common situations.  Regardless of which system is 
used it is imperative that the flow rates called for in Table 
3B are developed through the coil.  This requires properly 
sized piping and a properly sized pump.  

The system shown in FIG’s 3-1 thru 3-4 are described 
below:

Zone with circulator to Aquastat

This system is like the circulator zone system on a straight 
heat job except that one of the zones goes to the tank 
instead of radiation.  As on any circulator zone system 
check valves should be installed in each zone to prevent 
unwanted circulation through zones which are not calling 
for heat.  Figure 3-1 on page 7 illustrates typical circulator 
zone piping.

Zone with valve to Aquastat

As with the circulator zone system, this system is just like a 
standard heating zone system except that one of the zones 
is connected to the tank coil as shown in FIG. 3-2.  The 
system circulator must be large enough to move boiler 
water through the coil regardless of the flow rate required 
through the heating zones.

Table 3A

Pressure Drop Coil Chart

0

5

10

15

20

25

0

5

10

15

20

25

30

35

Foot Of Head

Flow 

Pressure Drop Coil

36.5
44

44'

36.5'

Содержание Squire SIT040DW

Страница 1: ...ed heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property...

Страница 2: ...EFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Double Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING Zone with Circulator...

Страница 3: ...AS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc...

Страница 4: ...B C D 22 5 45 F 1 MPT SEE NOTE 2 1 MPT 1 MPT AQUASTAT SENSOR WELL NOTES 1 1 FPT ON MODELS SIT040DW 050DW 1 RELIEF VALVE CONNECTION 2 HOT WATER OUTLET 3 BOILER WATER IN 4 BOILER WATER OUT 5 DRAIN COLD...

Страница 5: ...appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on pa...

Страница 6: ...8 GPM 12 GPM 16 GPM 20 GPM 25 GPM 30 GPM SIT040 1 1 1 36 5 12 05 0 87 1 99 4 05 6 00 9 89 14 62 20 11 SIT050 1 1 1 36 5 12 05 0 87 1 99 4 05 6 00 9 89 14 62 20 11 SIT065 1 5 1 5 1 44 15 03 0 94 2 14...

Страница 7: ...EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE DRAIN ZONE 1 ZONE 2 ZONE...

Страница 8: ...D SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE DRAI...

Страница 9: ...IN POINT TYPICAL MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HO...

Страница 10: ...R RECOMMENDED BOILER CIRCULATOR DOMESTIC HOT WATER CIRCULATOR UNION TYPICAL TEMPERATURE PRESSURE GAUGE DRAIN PRESSURE RELIEF VALVE KNIGHT BOILER SQUIRE SQUIRE HOT WATER OUT ANTI SCALD MIXING VALVE REL...

Страница 11: ...reverse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be rem...

Страница 12: ...tion VIII Interpretation VIII 1 86 136 Check with local codes for applicability Do not place a valve between the combination T P relief valve and the tank Determine T P relief valve size by the follow...

Страница 13: ...ter system Refer to the expansion tank manufacturer s installation instructions for proper sizing 4 Domestic side tank piping continued WARNING Failure to install and maintain a new listed 3 4 X 3 4 T...

Страница 14: ...sensor has a built in high temperature limit set at 194 F NOTICE The sensor supplied contains an Auto Reset High Limit 194 F 3 The Knight boiler will automatically read the sensor and default the tank...

Страница 15: ...t control 100208546 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIR...

Страница 16: ...xtended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and th...

Страница 17: ...to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve com...

Страница 18: ...er AHRI Rating Indirect Water Heater Model Number Potable Water Volume Gal Heat Source Water Volume Gal Standby Heat Loss F hr First Hour Rating Gal hr Continuous Draw Rating Gal hr Minimum Heat Outpu...

Страница 19: ...han 165 gallons Fixture Count Guide To quickly estimate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour Rating of the Squire mu...

Страница 20: ...459 Boiler Output Capacity Table 8B First Hour Rating 180 F Boiler Loop Water Knight Boiler 8 Performance data First Hour Rating 180 F Boiler Loop Water Knight Boiler Models SIT080DW SIT119DW Model S...

Страница 21: ...34 339 258 365 278 115 000 371 281 379 287 421 317 428 322 140 000 454 340 MAX BTU INPUT 47 144 57 327 62 606 67 133 73 108 81 841 89 761 47 144 57 327 62 606 67 133 73 108 81 841 89 761 70 904 77 315...

Страница 22: ...PUT 81 087 98 603 107 683 115 469 125 746 140 766 154 389 81 087 98 603 107 683 115 469 125 746 140 766 154 389 121 955 132 982 151 146 168 661 173 202 195 905 214 070 Table 8D First Hour Rating 200 F...

Страница 23: ...Notes Installation Operation Manual 23...

Страница 24: ...ision A Process 3000001798_Change 500002025 initial release Revision B PCP 3000006451 CN 500006731 reflects the addition of the CSA 1 91 logo to the front cover MM 100273038_DIR 2000529317 Rev B 02 17...

Отзывы: