Installation & Operation Manual

7  

Maintenance

*  Make sure that the rest of the boiler and domestic 
 

water piping is free of leaks.

*  If there is an oil lubricated circulator in the system, 
 

make sure it is lubricated as called for by the 

 circulator 

manufacturer.

Make sure that the boiler is maintained in accordance 

 

with the boiler manufacturer’s instructions.

*  If a water treatment system is required to keep the 
 

water chemistry within the parameters shown in 

 

Table 2A (see Section 2 - Pre-Installation), make sure 

 

that this system is properly maintained.

The Lochinvar SIT DW series indirect water heater is an 
extremely simple device and as such requires very little 
maintenance.  There are, however, several items which 
should be checked out on an annual or as needed basis to 
ensure a reliable supply of hot water:

Maintenance Schedule

Annual service by a qualified service technician 
should include the following:

  Any procedure required by local codes.

  Verify system pressure.  Air venting procedure may 

 

require adding water to bring boiler system up to 

 

pressure, typically 12 psig.

  Manually operate T&P relief valve at least once a year.  

 

This will release some hot water.

 WARNING

Before operating a T&P relief valve, make 
sure no one is in front of or around the 
T&P relief valve discharge piping.  Hot 
discharge water can cause severe personal 
injury or substantial property damage.

  Move operating lever to open position for a few 

 

seconds and then move it back, allowing it to snap 

 

closed. After the T&P relief valve is operated, if it 

 

continues to release water, close the cold water inlet to 

 

the water heater immediately. Follow the draining 

 

instructions, and replace the T&P relief valve.  If the 

 

T&P relief valve weeps periodically, it may be due to 

 

thermal expansion.  Do not plug the T&P relief valve or 

 discharge 

piping.

Homeowner monthly maintenance to include:

  Visually check valves, pipes, and fittings for leaks.  Call a 

 

qualified service technician to repair leaks.

To Fill the Water Heater

1.  Close the water heater drain valve by turning the knob 
 clockwise.

2.  Open the cold water supply shutoff valve.

3.  Open several hot water faucets to allow air to escape from 
 the 

system.

4.  When a steady stream of water flows from the faucets, the 
 

water heater is filled.  Close the faucets and check for water 

 

leaks at the water heater drain valve, combination 

 

temperature and pressure relief valve and the hot and cold 

 water 

connections.

 DANGER

Plugging the T&P relief valve or discharge 
piping can cause excessive pressure in the 
water heater, resulting in severe personal 
injury, death, or substantial property 
damage.

 WARNING

Water from opened drain valves, unions and 
other connections may be extremely hot. 

 

To avoid severe personal injury, death, or 
substantial property damage:

Tighten all drain hose connections.

-  Direct hot water away from all 
 persons.

To Drain the Water Heater

Should it become necessary to completely drain the water 
heater, be sure to follow the steps below:

1.  Disconnect the power supply to the heat source. Consult 
 

the plumbing professional or electric company in your area 

 for 

service.

2.  Close the cold water supply shutoff valve.

3.  Open the drain valve on the water heater.  

4.  Open a hot water faucet to allow air to enter the system.

 

•  If boiler water does not contain sufficient 

 

 

antifreeze, the boiler water and the domestic water 

  must 

be 

drained.

If antifreeze is used in the boiler water, check concentration.  
Boiler water (including additives) must be practically non-toxic, 
having a toxicity rating or class of 1, as listed in the “Clinical 
Toxicology of Commercial Products”. A maximum 50/50 
mixture of inhibited propylene glycol is recommended.  Follow 
the antifreeze manufacturer’s instructions.

 WARNING

Do not use automotive, ethylene glycol 
or petroleum-based antifreeze. Do not use 
any undiluted antifreeze. This can cause 
severe personal injury, death, or substantial 
property damage.

Drain the water heater if it will be shut off and exposed to 
freezing temperatures.  Freezing water will expand and damage 
the water heater.

 

•  If boiler water contains sufficient antifreeze, then 

 

 

only the domestic water needs to be drained.

  Follow instructions on circulator to oil, if required.

  Check mixing valve, valves, pipes, and fittings for leaks.

  Check function of the field-installed controls and valves.  

 

See component manufacturer’s instructions.

  Review homeowner’s maintenance responsibilities and 

 

their frequencies, including any not listed in the 

 following 

section.

17

Содержание Squire SIT040DW

Страница 1: ...ed heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property...

Страница 2: ...EFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Double Wall Heat Exchanger 4 2 PRE INSTALLATION Locating the Tank 5 Recommended Clearances 5 3 BOILER SIDE PIPING Zone with Circulator...

Страница 3: ...AS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instruc...

Страница 4: ...B C D 22 5 45 F 1 MPT SEE NOTE 2 1 MPT 1 MPT AQUASTAT SENSOR WELL NOTES 1 1 FPT ON MODELS SIT040DW 050DW 1 RELIEF VALVE CONNECTION 2 HOT WATER OUTLET 3 BOILER WATER IN 4 BOILER WATER OUT 5 DRAIN COLD...

Страница 5: ...appliance and must also be kept vertical on a level surface 2 Keep distance between boiler and water heater to a minimum to a reduce piping heat loss b provide minimal friction loss 3 Figure 1 1 on pa...

Страница 6: ...8 GPM 12 GPM 16 GPM 20 GPM 25 GPM 30 GPM SIT040 1 1 1 36 5 12 05 0 87 1 99 4 05 6 00 9 89 14 62 20 11 SIT050 1 1 1 36 5 12 05 0 87 1 99 4 05 6 00 9 89 14 62 20 11 SIT065 1 5 1 5 1 44 15 03 0 94 2 14...

Страница 7: ...EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY HOT WATER OUT ANTI SCALD MIXING VALVE RECIRCULATION PUMP CHECK VALVE DRAIN ZONE 1 ZONE 2 ZONE...

Страница 8: ...D SYSTEM CIRCULATOR SYSTEM SUPPLY SENSOR WHEN USED NOT TO EXCEED 4 PIPE DIA OR A MAXIMUM OF 12 APART TANK SENSOR AQUASTAT RELIEF VALVE Y STRAINER DRAIN FIELD SUPPLY RECIRCULATION PUMP CHECK VALVE DRAI...

Страница 9: ...IN POINT TYPICAL MAKE UP WATER FROM SYSTEM BOILER CIRCULATOR SYSTEM CIRCULATOR TO SYSTEM SYSTEM SUPPLY SENSOR DRAIN DRAIN FIELD SUPPLY RECIRCULATION PUMP TANK SENSOR AQUASTAT Y STRAINER RECOMMENDED HO...

Страница 10: ...R RECOMMENDED BOILER CIRCULATOR DOMESTIC HOT WATER CIRCULATOR UNION TYPICAL TEMPERATURE PRESSURE GAUGE DRAIN PRESSURE RELIEF VALVE KNIGHT BOILER SQUIRE SQUIRE HOT WATER OUT ANTI SCALD MIXING VALVE REL...

Страница 11: ...reverse return piping layout see FIG 3 4 Each tank must have its own T P valve It is recommended that each tank be equipped with its own isolation valves unions and drains so that one tank may be rem...

Страница 12: ...tion VIII Interpretation VIII 1 86 136 Check with local codes for applicability Do not place a valve between the combination T P relief valve and the tank Determine T P relief valve size by the follow...

Страница 13: ...ter system Refer to the expansion tank manufacturer s installation instructions for proper sizing 4 Domestic side tank piping continued WARNING Failure to install and maintain a new listed 3 4 X 3 4 T...

Страница 14: ...sensor has a built in high temperature limit set at 194 F NOTICE The sensor supplied contains an Auto Reset High Limit 194 F 3 The Knight boiler will automatically read the sensor and default the tank...

Страница 15: ...t control 100208546 can be ordered from your local Lochinvar distributor 2 Connect Aquastat to the zone controller for the Indirect Water Heater Zone 3 Adjust Aquastat to the desired temperature INDIR...

Страница 16: ...xtended period of time after installation Flush the indirect water heater by drawing at least three times its volume from the tank 3 Make sure that all electrical connections are made correctly and th...

Страница 17: ...to allow air to escape from the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve com...

Страница 18: ...er AHRI Rating Indirect Water Heater Model Number Potable Water Volume Gal Heat Source Water Volume Gal Standby Heat Loss F hr First Hour Rating Gal hr Continuous Draw Rating Gal hr Minimum Heat Outpu...

Страница 19: ...han 165 gallons Fixture Count Guide To quickly estimate the minimum gallons of hot water required based on a family size number of baths and hot water appliances the First Hour Rating of the Squire mu...

Страница 20: ...459 Boiler Output Capacity Table 8B First Hour Rating 180 F Boiler Loop Water Knight Boiler 8 Performance data First Hour Rating 180 F Boiler Loop Water Knight Boiler Models SIT080DW SIT119DW Model S...

Страница 21: ...34 339 258 365 278 115 000 371 281 379 287 421 317 428 322 140 000 454 340 MAX BTU INPUT 47 144 57 327 62 606 67 133 73 108 81 841 89 761 47 144 57 327 62 606 67 133 73 108 81 841 89 761 70 904 77 315...

Страница 22: ...PUT 81 087 98 603 107 683 115 469 125 746 140 766 154 389 81 087 98 603 107 683 115 469 125 746 140 766 154 389 121 955 132 982 151 146 168 661 173 202 195 905 214 070 Table 8D First Hour Rating 200 F...

Страница 23: ...Notes Installation Operation Manual 23...

Страница 24: ...ision A Process 3000001798_Change 500002025 initial release Revision B PCP 3000006451 CN 500006731 reflects the addition of the CSA 1 91 logo to the front cover MM 100273038_DIR 2000529317 Rev B 02 17...

Отзывы: