5

RPV-I&S

NOTE: 

For installations requiring both horizontal and vertical runs,

the following rule must be followed: Total number of feet of straight

pipe (both horizontally and vertically) must not exceed the allowable

length listed in the “Through The Wall” section of the table for total

number of elbows used.  Also: Total number of vertical feet of straight

pipe must not exceed the allowable length listed in the “Through

The Roof” section of the table for total number of elbows used. For

angular rises in venting, any angle that is greater than or equal to

45° from the horizontal should be considered a vertical rise.

THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE:

When venting cannot exit through the wall at a height greater than or equal to

12" 

(30.5 cm)

 above the ground, or anticipated snow level, the installation

must be modified as shown below (see Figure 5). Refer to Table 4 for maximum
venting lengths using 3" 

(7.6 cm)

 PVC or Table 5 for maximum lengths using 4"

(10.1 cm)

 PVC.

HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER

3,000 FEET 

(914.5 m)

 ABOVE SEA LEVEL

The capacity of the induced draft blower declines with increasing altitude due to

a reduction in the air density.  In order to assure safe and reliable performance

of the water heater, the following guidelines must be followed. Refer to the

venting tables below for maximum distances for the altitudes in your location.

Part II - Venting Specifications for:

40 Gallon, 40,000 BTU input (151.4 L, 11.7 kW/Hr)

48 Gallon, 40,000 BTU input (189.3 L, 11.7 kW/Hr)

This water heater is a power vented appliance and is designed to vent its
products of combustion through 2" 

(5.1 cm)

 or 3" 

(7.6 cm)

 diameter Schedule

40 (solid or cellular core) PVC pipe to the outdoors. The water heater may be

either vented through the wall or vertically through the roof.  Use a 3" 

(7.6 cm)

to 2" 

(5.1 cm)

 reducer to connect to the vent outlet when using 3" 

(7.6 cm)

PVC.  Apply PVC cement at PVC locations. Table 7 lists the maximum vent

lengths for this water heater using 2" 

(5.1 cm)

 PVC. If possible, locate the

water heater so that the venting length and number of elbows are kept to the

minimum distance necessary to reach the outside.  If the installation requires

venting lengths that exceed the lengths listed for 2" 

(5.1 cm)

 PVC in Table 7

then use 3" 

(7.6 cm)

 PVC for the vent connector. Table 8 lists the venting

distances allowed with 3" 

(7.6 cm)

 diameter PVC pipe. When venting with 3"

(7.6 cm)

 PVC, use a 3" 

(7.6 cm)

 to 2" 

(5.1 cm)

 reducer to exit through the

building wall with 2" (5.1 cm) PVC. Use the 2" 

(5.1 cm)

 vent terminal supplied

with the water heater to terminate on the outside of the building. If the length
of the 2" 

(5.1 cm)

needed to go through the wall is greater than 14" (35.6 cm),

use 3" (7.6 cm) PVC to go through the wall and reduce to 2" (5.1 cm) PVC
immediately after exiting the outside wall. Refer to the venting illustrations on
the following pages. Make sure the vent pipe terminal is at least 1" (2.5 cm)
away from the edge of the wall. To vent horizontally with zero (0) elbows,
remove 3 screws from blower housing and rotate the blower housing 90°
clockwise (see Figure 7). Replace the three (3) screws once blower housing
rotation is complete.

TABLE - 4

3" 

(7.6 cm)

 PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL

FOR LOW GROUND CLEARANCE INSTALLATIONS

             Terminating                # of         Maximum        Minimum

                          Elbows         Length            Length

(2) 90° Elbows with (1) 90° Elbow

1

30 ft 

(9.1 m)

5 ft 

(1.5 m)

(2) 90° Elbows with (1) 90° Elbow

2

25 ft 

(7.6 m)

   6 ft 

(2 m)

(2) 90° Elbows with (1) 90° Elbow

3

20 ft 

(6.1 m)

8 ft 

(2.5 m)

(2) 90° Elbows with (1) 90° Elbow

4

15 ft 

(4.6 m)

10 ft 

(3 m)

TABLE - 5

4" 

(10.1 cm)

 VENT CONNECTOR LENGTHS FROM INSIDE WALL

FOR LOW GROUND CLEARANCE INSTALLATIONS

Terminating (Reduce 4" to 3")  # of         Maximum       Minimum

 (Reduce 10.1 cm to 7.6 cm)

Elbows     Length            Length

(2) 90° Elbows with (1) 90° Elbow

1

60 ft 

(18.3 m)

 10 ft 

(3 m)

(2) 90° Elbows with (1) 90° Elbow

2

55 ft 

(16.8 m)      

12 ft 

(3.7 m)

(2) 90° Elbows with (1) 90° Elbow

3

50 ft 

(15.2 m)      

15 ft 

(4.6 m)

(2) 90° Elbows with (1) 90° Elbow

4

45 ft 

(13.7 m)      

18 ft 

(5.5 m)

(2) 90° Elbows with (1) 90° Elbow

5

40 ft 

(12.2 m)      

22 ft 

(6.7 m)

TABLE - 7

VENT CONNECTOR LENGTHS FOR 2" 

(5.1cm)

 DIAMETER PVC

   Terminating      # of 90° Elbows        Maximum            Minimum

       (excluding vent             Length                 Length

                                terminal)

Through the Wall

0

45 ft 

(13.7m)                

  2 ft 

(.6 m)

Through the Wall

1

40 ft 

(12.2m)                

  2 ft 

(.6 m)

Through the Wall

2

35 ft 

(10.7m)                

  2 ft 

(.6 m)

Through the Wall

3

3 0 ft 

(9.2 m)                 

  2 ft 

(.6 m)

Through the Wall

4

 25 ft 

(7.6 m)                 

  3 ft 

(.9 m)

Through the Roof

0

 31 ft 

(9.5 m)                 

  3 ft 

(.9 m)

Through the Roof

1

 28 ft 

(8.5 m)                 

  3 ft 

(.9 m)

Through the Roof

2

 25 ft 

(7.6 m)                  

 3 ft 

(.9 m)

Through the Roof

3

 22 ft 

(6.7 m)                  

 3 ft 

(.9 m)

Through the Roof

4

 19 ft 

(5.8 m)                

4 ft 

(1.2 m)

 

Figure 5

TABLE - 6

HIGH  ALTITUDE  LENGTHS

Altitude

Max. venting       Max. venting        Modifications to

above

length reduction   length reduction    water heater

sea level

from tables          from tables

2 & 4                 3 & 5

Requires high altitude
Kit. Call the supplier or
the manufacturer

No reduction
in vent length
required

No reduction
in vent length
required

over 3,000-
10,000 ft

(914.5-3048m)

0-3,000 ft

(0-914.5m)

No reduction
in vent length
required

No reduction
in vent length
required

None

Содержание RPV-I&S

Страница 1: ...ged in water You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water Make sure that you check the rating plate and combination gas control on the water heater to be certain that the type of gas being supplied corresponds with the marking on the rating plate and c...

Страница 2: ... is recommended that a minimum clearance of four 4 inches 10 2 cm be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve MINIMUM CLEARANCES This installation must allow access to the front of the water heater and adequate clearance must be provided for servicing and operating this water heater The water heater may be insta...

Страница 3: ...ainst on installations where condensation can form in the venting system Formation of condensation in the venting system of Power Vented water heaters is dependent upon installation conditions including but not limited to 1 Ambient temperature and humidity of installation location 2 Ambient temperature and humidity of venting space vent distance and slope 3 And product usage In order to effectivel...

Страница 4: ... support brackets for every 3 feet 91 m of horizontal vent THROUGH THE ROOF VENTING VERTICAL VENTING Cut the necessary holes through the roof and ceiling and install the vent connector as shown in Figure 4 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code Figure 2 TABLE 3 VENT CONNECTOR LENGTHS FOR 4...

Страница 5: ...ing with 3 7 6 cm PVC use a 3 7 6 cm to 2 5 1 cm reducer to exit through the building wall with 2 5 1 cm PVC Use the 2 5 1 cm vent terminal supplied with the water heater to terminate on the outside of the building If the length of the 2 5 1 cm needed to go through the wall is greater than 14 35 6 cm use 3 7 6 cm PVC to go through the wall and reduce to 2 5 1 cm PVC immediately after exiting the o...

Страница 6: ... and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm from the ground or from the anticipated snow level then the installation must be modified as shown below see Figure 10 Refer to Table 9 for maximum venting lengths...

Страница 7: ...zation equipment in the confined space but not less than 100 square inches 645 cm2 One opening must be within 12 inches 31 cm of the top and one within 12 inches 31 cm of the bottom of the enclosure All Air From Outdoors The confined space must be provided with two permanent openings one commencing within 12 inches 31 cm of the top and one commencing within 12 inches 31 cm from the bottom of the e...

Страница 8: ...ble from the local plumbing supplier Please consult with a plumbing professional CAUTION If sweat fittings are to be usedDO NOT apply heat to the nipples on top of the water heater Sweat the tubing to the adapter before fitting the adapter to the waterconnections Itisimperativethatheatisnotappliedtothenipplescontaining a plastic liner WARNING FAILURE TO INSTALL AND MAINTAIN A NEW LISTED 3 4 X 3 4 ...

Страница 9: ...supply to the corresponding locations that were connected to the flexible line cord The wiring diagram for the 48 gal 65 000 BTU 181 7 L 19 1 Kw Hr 65 gal 65 000 BTU 246 1 L 19 1 Kw Hr and 75 gal 76 000 BTU input 283 9 L 22 3 Kw Hr models is located in Figure 11 on page 10 The wiring diagram for the 40 gal 40 000 BTU 151 4 L 11 7 Kw Hr and 48 gal 40 000 BTU 181 7 L 11 7 Kw Hr models are located in...

Страница 10: ...10 RPV I S Figure 11 ...

Страница 11: ...11 RPV I S Figure 12 ...

Страница 12: ...anual gas control valve to the appliance and call a qualified service technician Note Whenever the water heater is filled with cold water condensate will form on the cool tank surface and drops of water will fall on the hot burner and combustion chamber surfaces producing a sizzling noise Condensation is normal and does not indicate a leak It will disappear when the tank becomes heated FOR YOUR SA...

Страница 13: ...pplier or local plumbing inspector on how to correct this situation Do not plug the combination temperature and pressure relief valve outlet 10 A combination sacrificial anode rod hot water outlet nipple has been installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will influence th...

Страница 14: ...icals such as those used for boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non potable water heating appliance 4 When the system requires water for space heating at temperatures higher than required for other means a tempering valve must be installed to ...

Страница 15: ...l c Applicator Tools i A pure bristle paintbrush or roller may be used to apply cement Prompt application of the cement is important due its fast drying properties 3 Inspection Cleaning Priming and Cementing a Inspect the pipe inside and out for dirt dust moisture or grease etc Check pipe and fittings for splits or cracks and replace if necessary b Clean pipe and fittings are imperative for proper...

Страница 16: ...16 RPV I S Printed in USA ...

Отзывы: