background image

7

RPV-I&S

NOTE: 

For installations requiring both horizontal and vertical runs,

the following rule must be followed: Total number of feet of straight

pipe (both horizontally and vertically) must not exceed the allowable

length listed in the “Through The Wall” section of the table for total

number of elbows used.  Also: Total number of vertical feet of straight

pipe must not exceed the allowable length listed in the “Through The

Roof” section of the table for total number of elbows used.  For

angular rises in venting, any angle that is greater than or equal to

45° from the horizontal should be considered a vertical rise.

HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER 2,000 FEET

(610 m)

 ABOVE SEA LEVEL

The capacity of the induced draft blower declines with increasing altitude due to

a reduction in the air density.  In order to assure safe and reliable performance

of the water heater, the following guidelines must be followed. Refer to the
venting tables below for maximum distances for the altitudes in your location.

COMBUSTION AIR SUPPLY

Provide adequate air for combustion and ventilation.  An insufficient supply of

air will cause recirculation of combustion products resulting in air contamination

that may be hazardous to life.  Such a condition often will result in a yellow,
luminous burner flame, causing carbon build up or sooting of the combustion

chamber, burners, and flue tubes with possible damage to the heater.

When an exhaust fan is installed in the same room with a heater, sufficient

openings for air must be provided in the walls.  Undersized openings will cause

air to be drawn into the room through the chimney, causing recirculation of
combustion products.

Unconfined Spaces

In unconfined spaces in buildings, infiltration may be adequate to provide air

for combustion, ventilation, and dilution of flue gases. However, in buildings of

tight construction (for example, weather stripping, heavily insulated, caulked,
vapor barrier, etc.), additional air may need to be provided using the methods

described under CONFINED SPACES:  All Air From Outdoors or Specially Engineered

Installations.

Confined Spaces

Confined spaces are spaces defined as having less than 50 ft.

3

/1000 BTU

(1.4 m

3

/0.29 kw-hr

).

All Air From Inside the Building:

  The confined space must be provided

with two permanent openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all spaces meets the

criteria for an unconfined space.  The total input of all gas utilization equipment
installed in the combined space must be considered in making this determination.

Each opening must have a minimum free area of 1 square inch per 1000 BTU

(6.5 cm

2

/0.29 kw)

 per hour of the total input rating of all gas  utilization

equipment in the confined space, but not less than 100 square inches (645

cm

2

).  One opening must be within 12 inches 

(31 cm)

 of the top and one within

12 inches 

(31 cm)

 of the bottom of the enclosure.

All Air From Outdoors

: The confined space must be provided with two

permanent openings, one commencing within 12 inches 

(31 cm)

 of the top and

one commencing within 12 inches 

(31 cm)

 from the bottom of the enclosure.

The openings must communicate directly, or by ducts, with the outdoors or

spaces (crawl or attic) that freely communicate with the outdoors.

TABLE - 9

2" (5.1 cm) PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL

FOR LOW GROUND CLEARANCE INSTALLATIONS

             Terminating

# of         Maximum       Minimum

Elbows     Length            Length

(2) 90° Elbows with Vent Terminal

0

35 ft 

(10.7 m)

   2 ft 

(.6 m)

(2) 90° Elbows with Vent Terminal

1

  30 ft 

(9.2 m)

   2 ft 

(.6 m)

(2) 90° Elbows with Vent Terminal

2

  25 ft 

(7.6 m)

   2 ft 

(.6 m)

(2) 90° Elbows with Vent Terminal

3

  20 ft 

(6.1 m)

   3 ft 

(.9 m)

(2) 90° Elbows with Vent Terminal

4

  15 ft 

(4.6 m)

4 ft 

(1.2 m)

TABLE - 10

3" (7.6 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL

FOR LOW GROUND CLEARANCE INSTALLATIONS

 Terminating (Reduce 3" to 2")   # of         Maximum       Minimum
  (Reduce 7.6 cm to 5.1 cm)

Elbows     Length            Length

 (2) 90° Elbows with (1) 90° Elbow

1

60 ft 

(18.3 m)

    10 ft 

(3 m)

 (2) 90° Elbows with Vent Terminal

0

90 ft 

(27.5 m)

10 ft 

(3.1 m)

 (2) 90° Elbows with Vent Terminal

1

85 ft (

25.9 m)

10 ft 

(3.1 m)

 (2) 90° Elbows with Vent Terminal

2

80 ft 

(24.4 m)

10 ft 

(3.1 m)

 (2) 90° Elbows with Vent Terminal

3

75 ft 

(22.9 m)

10 ft 

(3.1 m)

 (2) 90° Elbows with Vent Terminal

4

70 ft 

(21.4 m)

10 ft 

(3.1 m)

 (2) 90° Elbows with Vent Terminal

5

65 ft 

(19.8 m)

12 ft 

(3.7 m)

 WARNING

Liquefied petroleum gases/propane gas are heavier than air and will remain
at floor level if there is a leak. Basements, crawl spaces, closets and areas
below ground level will serve as pockets for accumulation of leaking gas.
Before lighting, smell all around the appliance area for gas. Be sure to smell
next to the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any telephone

in your building.

• Immediately call your gas supplier from a neighbor’s

telephone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

DO NOT OPERATE APPLIANCE UNTIL LEAKAGE IS CORRECTED!

IMPORTANT

The flow of combustion and ventilating air must not be obstructed.

TABLE - 11

HIGH ALTITUDE VENT CONNECTOR MODIFICATIONS

Altitude above

Maximum venting

Maximum venting

sea level

length reduction

length reduction

tables 7 & 9

tables 8 & 10

Reduce maximum vent
length by 20 ft 

(6.1 m)

No reduction in vent
length required

over 2,000 - 5,000ft

(over 610 - 1524 m)

0 - 2,000 ft

(0 - 610 m)

No reduction in vent
length required

over 5,000 - 8,000 ft

(over 1524 - 2439 m)

Use only 3" 

(7.6 cm)

PVC (Tables 8 & 10)

No reduction in vent
length required

over 8,000 - 10,000 ft

(over 2439  - 2540 m)

Use only 3" 

(7.6 cm)

PVC (Tables 8 & 10)

 

Reduce maximum vent

 length by 20 ft 

(6.1 m)

No reduction in vent
length required

Содержание RPV-I&S

Страница 1: ...ged in water You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water Make sure that you check the rating plate and combination gas control on the water heater to be certain that the type of gas being supplied corresponds with the marking on the rating plate and c...

Страница 2: ... is recommended that a minimum clearance of four 4 inches 10 2 cm be provided on the side of the water heater for servicing and maintenance of the combination temperature and pressure relief valve MINIMUM CLEARANCES This installation must allow access to the front of the water heater and adequate clearance must be provided for servicing and operating this water heater The water heater may be insta...

Страница 3: ...ainst on installations where condensation can form in the venting system Formation of condensation in the venting system of Power Vented water heaters is dependent upon installation conditions including but not limited to 1 Ambient temperature and humidity of installation location 2 Ambient temperature and humidity of venting space vent distance and slope 3 And product usage In order to effectivel...

Страница 4: ... support brackets for every 3 feet 91 m of horizontal vent THROUGH THE ROOF VENTING VERTICAL VENTING Cut the necessary holes through the roof and ceiling and install the vent connector as shown in Figure 4 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code Figure 2 TABLE 3 VENT CONNECTOR LENGTHS FOR 4...

Страница 5: ...ing with 3 7 6 cm PVC use a 3 7 6 cm to 2 5 1 cm reducer to exit through the building wall with 2 5 1 cm PVC Use the 2 5 1 cm vent terminal supplied with the water heater to terminate on the outside of the building If the length of the 2 5 1 cm needed to go through the wall is greater than 14 35 6 cm use 3 7 6 cm PVC to go through the wall and reduce to 2 5 1 cm PVC immediately after exiting the o...

Страница 6: ... and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE When venting cannot exit through the wall at a height greater than or equal to 12 30 5 cm from the ground or from the anticipated snow level then the installation must be modified as shown below see Figure 10 Refer to Table 9 for maximum venting lengths...

Страница 7: ...zation equipment in the confined space but not less than 100 square inches 645 cm2 One opening must be within 12 inches 31 cm of the top and one within 12 inches 31 cm of the bottom of the enclosure All Air From Outdoors The confined space must be provided with two permanent openings one commencing within 12 inches 31 cm of the top and one commencing within 12 inches 31 cm from the bottom of the e...

Страница 8: ...ble from the local plumbing supplier Please consult with a plumbing professional CAUTION If sweat fittings are to be usedDO NOT apply heat to the nipples on top of the water heater Sweat the tubing to the adapter before fitting the adapter to the waterconnections Itisimperativethatheatisnotappliedtothenipplescontaining a plastic liner WARNING FAILURE TO INSTALL AND MAINTAIN A NEW LISTED 3 4 X 3 4 ...

Страница 9: ...supply to the corresponding locations that were connected to the flexible line cord The wiring diagram for the 48 gal 65 000 BTU 181 7 L 19 1 Kw Hr 65 gal 65 000 BTU 246 1 L 19 1 Kw Hr and 75 gal 76 000 BTU input 283 9 L 22 3 Kw Hr models is located in Figure 11 on page 10 The wiring diagram for the 40 gal 40 000 BTU 151 4 L 11 7 Kw Hr and 48 gal 40 000 BTU 181 7 L 11 7 Kw Hr models are located in...

Страница 10: ...10 RPV I S Figure 11 ...

Страница 11: ...11 RPV I S Figure 12 ...

Страница 12: ...anual gas control valve to the appliance and call a qualified service technician Note Whenever the water heater is filled with cold water condensate will form on the cool tank surface and drops of water will fall on the hot burner and combustion chamber surfaces producing a sizzling noise Condensation is normal and does not indicate a leak It will disappear when the tank becomes heated FOR YOUR SA...

Страница 13: ...pplier or local plumbing inspector on how to correct this situation Do not plug the combination temperature and pressure relief valve outlet 10 A combination sacrificial anode rod hot water outlet nipple has been installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will influence th...

Страница 14: ...icals such as those used for boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non potable water heating appliance 4 When the system requires water for space heating at temperatures higher than required for other means a tempering valve must be installed to ...

Страница 15: ...l c Applicator Tools i A pure bristle paintbrush or roller may be used to apply cement Prompt application of the cement is important due its fast drying properties 3 Inspection Cleaning Priming and Cementing a Inspect the pipe inside and out for dirt dust moisture or grease etc Check pipe and fittings for splits or cracks and replace if necessary b Clean pipe and fittings are imperative for proper...

Страница 16: ...16 RPV I S Printed in USA ...

Отзывы: