8  OPERATING CODES/TROUBLESHOOTING

60

8  OPERATING CODES/TROUBLESHOOTING

8�1  OVERVIEW AND OPERATING CODES/TROUBLESHOOTING

Table 8�1 – TABLE OF OPERATING CODES generated by the S61 electronic board (firmware version 3.026)

CODES

DESCRIPTION

TRIP CONDITIONS

RESET METHOD

E 400

FAULT ON RESET CIRCUIT OF FLAME 

CONTROL UNIT

Fault on reset circuit of flame control unit.

Contact authorised Technical Assistance.

u 401

GENERATOR LIMIT TEMPERATURE 

THERMOSTAT

High temperature detected by limit thermostat 

on body of generator

Acknowledge the thermostat manually: reset will be automatic as 

soon as fault condition is over.

E 401

GENERATOR LIMIT TEMPERATURE 

THERMOSTAT

u_01 code active for 1 hour, or u_01 code gener-

ated 3 times in 2 hours of operation.

Contact authorised Technical Assistance.

u 402

FUMES THERMOSTAT

High temperature detected by exhaust fumes 

thermostat

Acknowledge the thermostat manually: reset will be automatic as 

soon as fault condition is over.

E 402

FUMES THERMOSTAT

u_02 code active for 1 hour, or u_02 code gener-

ated 3 times in 2 hours of operation.

Contact authorised Technical Assistance.

E 405

HIGH AMBIENT TEMPERATURE

HIGH temperature detected by ambient tempera-

ture sensor.

Reset occurs automatically when the condition that generated the 

code ceases.

u 406

LOW AMBIENT TEMPERATURE

LOW temperature detected by ambient tempera-

ture sensor.

Reset occurs automatically when the cause ceases or when the unit 

is switched off.

u 407

GENERATOR TEMPERATURE HIGH

Temperature detected by generator’s probe HIGH. Reset occurs automatically when the condition that generated the 

code ceases.

E 407

GENERATOR TEMPERATURE HIGH

Permanence of u_07 for 1 hour, or intervention of 

u_07 for 12 times in 2 hours of operation.

Carry out appropriate checks. Reset may be performed from the 

controller (or from the S61 board via menu 2, parameter 21). If the 

code persists, contact authorised Technical Assistance.

E 408

FLAME CONTROL UNIT ERROR

E_12 on unit and condenser inlet temperature 

increasing by over 10 °C within 1 hour.

Carry out appropriate checks. Reset may be performed from the 

controller (or from the S61 board via menu 2, parameter 21). If the 

code persists, contact authorised Technical Assistance.

u 410

INSUFFICIENT HOT WATER FLOW

Insufficient water flow (the circulator is on and 

the flowmeter measure a low water flow).

Reset occurs automatically when correct water flow is restored.

E 410

INSUFFICIENT HOT WATER FLOW

u_10 code is repeated, or code u_10 is active for 

1 hour.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

u 411

INSUFFICIENT ROTATION OF OIL 

PRESSURE PUMP

Insufficient rotation of oil pressure pump.

Reset occurs automatically 20 minutes after the Code is generated.

E 411

INSUFFICIENT ROTATION OF OIL 

PRESSURE PUMP

u_11 code generated twice in 2 hours of 

operation.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

u 412

FLAME CONTROL UNIT ARREST

Failure to ignite burner.

Reset occurs automatically when the solenoid valve opens again 

(new ignition attempt), or if the code persists for 5 minutes.

E 412

FLAME CONTROL UNIT ARREST

Flame arrest signal.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 20). If the code persists, contact authorised 

Technical Assistance.

E 416

HOT OUTLET WATER TEMPERATURE 

SENSOR DEFECTIVE

Fault (interruption or short circuit) on outlet hot 

water temperature sensor.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 417

COLD INLET WATER TEMPERATURE 

SENSOR DEFECTIVE

Fault (interruption or short circuit) on inlet water 

temperature sensor.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 420

CONDENSER INLET TEMPERATURE 

SENSOR DEFECTIVE

Fault (interruption or short circuit) on condenser 

inlet temperature sensor.

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 422

WATER FLOWMETER FAULT

Water flowmeter fault

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 423

AIR/GAS MIXTURE SENSOR FAULT

Air gas mixture sensor fault

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

u 424

FUMES TEMPERATURE SENSOR 

FAULT

Fumes temperature sensor fault

Reset occurs automatically when the condition that generated the 

code ceases.

E 424

FUMES TEMPERATURE SENSOR 

FAULT

Presence of E_24 for 5 seconds

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 425

CONDENSATE DISCHARGE 

CLOGGED

Condensate discharge clogged 

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

u 426

GENERATOR FIN TEMPERATURE 

SENSOR MALFUNCTION

Generator fin temperature sensor malfunction

Reset occurs automatically when the condition that generated the 

code ceases.

E 426

GENERATOR FIN TEMPERATURE 

SENSOR MALFUNCTION

Presence of u_26 for 5 seconds

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

E 428

GAS SOLENOID VALVE EXCITED 

DURING FLAME CONTROLLER 

ARREST

The flame controller is arrested (E_12) but the gas 

solenoid valve is excited. In this case the flame 

controller is de-excited (E_12 resets).

Reset may be performed from the controller (or from the S61 board 

via menu 2, parameter 21). If the code persists, contact authorised 

Technical Assistance.

u 429

GAS SOLENOID VALVE WITHOUT 

ELECTRICAL POWER

Gas solenoid valve is off for 5 seconds (with 

central flame control unit on).

Reset occurs automatically if the gas solenoid valve switches on 

again within 10 minutes (with central flame control unit on).

Содержание LCGHP

Страница 1: ...Installation user and maintenance manual LCGHP LSGHP powered by gas and renewable energies Air Water gas absorption heat pump...

Страница 2: ...f this manual other than for personal consultation must be previously authorised by Lochinvar The rights of those who have legitimately filed the registered trademarks contained within this publicatio...

Страница 3: ...0 5 1 GENERAL INSTALLATION PRINCIPLES 20 5 2 POSITION OF THE APPLIANCE 20 5 3 HYDRAULIC CONNECTIONS 22 5 4 GAS SUPPLY 24 5 5 CONDENSATE DISCHARGE 24 5 6 FILLING OF HYDRAULIC CIRCUIT 25 5 7 EXHAUST FLU...

Страница 4: ...nformation for a particular country References If the appliance is connected to a Comfort Control Panel see detail CCP in Figure 6 3 p 31 it is switched on and controlled by the Comfort Control Panel...

Страница 5: ...id or near the appliance problems with the electrical gas grid or hydraulic circuit parts of the appliance submerged in water or otherwise damaged controls or safety components bypassed or defective I...

Страница 6: ...only be done by a contractor legally author ised to work on gas appliances and equipment Use only original spare parts 2 1 WARRANTY TERMS Warranty can be invalidated by each one of the following cond...

Страница 7: ...and complete Installation of the appliance may only be carried out by professionally qualified personnel by i e firms qualified according to the cur rent legislation of the country of installation Pr...

Страница 8: ...sistance Proper ordinary maintenance ensures the efficiency and good operation of the appliance over time Carry out maintenance operations according to the instructions supplied by the manufacturer Fo...

Страница 9: ...C with manual reset Sealed circuit safety relief valve Safety by pass valve between high and low pressure parts of the sealed circuit Antifreeze functions for hydraulic circuit Ionization flame contr...

Страница 10: ...r operating conditions other than nominal refer to the Design Manual 2 For flow rates different from the nominal refer to the Design Manual 3 PCI 34 02 MJ m3 1013 mbar 15 C 4 PCI 46 34 MJ kg 1013 mbar...

Страница 11: ...n bar 4 Maximum flow flue condensate l h 4 Water content inside the apparatus l 4 Water fitting TYPE F thread G 1 1 4 Gas fitting TYPE F thread G 3 4 Fume outlet Diameter mm 80 Residual head Pa 80 Siz...

Страница 12: ...1 5 Evaporator l 3 7 Cooling volume transformer l 4 5 Cooling absorber solution l 6 3 Solution pump l 3 3 TEST PRESSURE IN AIR bar g 55 MAXIMUM PRESSURE OFTHE COOLING CIRCUIT bar g 32 FILLING RATIO kg...

Страница 13: ...intenance manual LCGHP LSGHP 13 Figure 3 2 Dimensions LCGHP low consumption ventilation Front and side views dimensions in mm Figure 3 3 Service plate A B Hydraulic gas unions detail LEGEND G Gas fitt...

Страница 14: ...ol of the appliance will occur exclusively by operating the DDC In this case refer to the manual supplied with it The appliance must never normally be switched on and off by shutting off the power sup...

Страница 15: ...interval the appliance automatically launches the start up procedure again If code u_12 is signalled 4 times on successive activation attempts the code persists the appliance locks out the flame contr...

Страница 16: ...ximately three seconds and then the name of the board S61 ap pears After around 15 seconds after the appliance powers up the appliance starts running if the required consent is available During correc...

Страница 17: ...24 Timed forcing to maximum power 2 24 25 Stop power forcing 2 25 E EXIT MENU 2 E The general operating codes of the controller can be reset with functions 20 and 21 Actions 23 24 and 25 are used to...

Страница 18: ...fitted to the appliance before proceeding you must acquire this informa tion Paragraph 4 2 p 15 At the moment of installation the appliance is set up by the installation technician for best operation...

Страница 19: ...he above recommendation is necessary in order to avoid to fill continuously with water that may imply the additional intro duction of oxygen and the consequent dilution of the used inhibitor for ex gl...

Страница 20: ...ctions the right and left sides must have a minimum clearance of 45 cm the minimum rear clearance from walls is 60 cm see Figure 5 2 p 22 No obstruction or overhanging structure roofs eaves balconies...

Страница 21: ...any damage arising from failure to observe this warning Installation at ground level If a horizontal support base is unavailable see also SUPPORTS and LEVELLING below it is necessary to create a flat...

Страница 22: ...lence is required such as bedrooms meeting rooms etc Evaluate the noise impact of the appliance with respect to the installation site avoid placing the appliance in locations such as cor ners of build...

Страница 23: ...for health for the environment and for appliances Several products for water treatment are available on the market Lochinvar does not perform detailed market surveys therefore suggests to contact Comp...

Страница 24: ...from 1 5 bar to 0 037 bar 37mbar LPG may cause corrosion piping and fitting materials must be resistant to this corrosion Vertical gas pipes must be equipped with a siphon and provided with a drain f...

Страница 25: ...ndensate pump must be installed near to the discharge realized in such a way as to prevent icing of the condensate mixed for example with domestic effluents washing machine dishwasher etc usually alka...

Страница 26: ...caused by the use or disposal of glycol antifreeze It is equally important to recall that the use of monoethylene glycol modifies the thermophysical characteristics of the water in the plant and in p...

Страница 27: ...SPLAY SHOWS Hot water thermostat control selection 3 160 Hot water setpoint 3 161 Hot water temperature differential 3 162 EXIT MENU 3 E Description of parameters Hot water thermostat control paramete...

Страница 28: ...hs Display and knob and How to access the menus and following To set the parameters of menu 3 You will need the appliance on and access to the electrical panel see Display and knob Access menu 3 The d...

Страница 29: ...ed by installation that is incorrect or that does not comply with current legislation Figure 6 1 p 29 and Table 6 1 p 29 provide details of input and ouput of the S61 electronic board The auxiliary el...

Страница 30: ...Input probe of evaporator output TA2 Not used TCN Combustive air temperature probe input TF Exhausted gas thermostat input TG Generator temperature probe input THMF Hot water delivery temperature pro...

Страница 31: ...nts componing the CCP AVS37 Comfort Control Siemens RVS61 System controller and set point CCI Comfort Control Interface PLC Programmable Logic Control AVS75 Expansion Optional components to predict QA...

Страница 32: ...6 ELECTRICAL INSTALLATION 32 Figure 6 4 CCI DDC...

Страница 33: ...S Gas valve ON indicator lamp GV Gas solenoid valve TC Manual fumes thermostat TL Generator limit thermostat FM Flowmeter CWS Condensation water sensor VD Defrosting valve FAN Fan C Fan condenser not...

Страница 34: ...or outlet temperature sensor TK Condensate discharge heating element thermostat MA Terminal block REED Hydraulic pump rotation sensor 6 2 HOW TO CONNECT THE APPLIANCE ELECTRICALLY Before making electr...

Страница 35: ...CP refer to the specific manuals supplied with it The appliance and the CCP communicate with each other via a CAN bus network The CAN bus network is characterized by a series of elements appliances or...

Страница 36: ...EN 3086A H BLACK L WHITE GND BROWN 450 m TURCK type 530 DeviceNet Mid Cable TURCK type 5711 H BLUE L WHITE GND BLACK 450 m Honeywell SDS 2022 TURCK type 531 H BLACK L WHITE GND BROWN 200 m For total d...

Страница 37: ...36 on the figure and on the electronic board below the connector 6 If the appliance is an intermediate node repeat the operations from step 2 to step 5 for the other cables required in this way you w...

Страница 38: ...e long enough to allow installing it without kinking 4 Remove the sheath for a length of approximately 70 80 mm taking care not to cut the shielding metallic shield and or alu minium sheet and if pres...

Страница 39: ...of cable CAN BUS Figure 6 12 Connection of CCI to CAN BUS network LEGEND CCI Comfort Control Interface P8 Orange connector J21 Jumpers CAN BUS on CCI board A detail of terminal node case 3 wires J21 j...

Страница 40: ...6 ELECTRICAL INSTALLATION 40 Figure 6 13 Connection of CCI to 1 appliance LEGEND SCH S61 controller CCI Comfort Control Interface Connection of CCI to 1 appliance...

Страница 41: ...CAL INSTALLATION Installation user and maintenance manual LCGHP LSGHP 41 Figure 6 14 Connection of CCI to 3 appliances LEGEND SCH S61 controller CCI Comfort Control Interface Connection of CCI to 3 ap...

Страница 42: ...truction for connecting the WILO STRATOS PARA pumps are given below Each WILO pump includes its power cord and signal cable 0 10V both 1 5 m long for connection to the appliance s electrical panel For...

Страница 43: ...ng diagram for connection of Wilo variable rate pumps LEGEND IP Bipolar pump power switch F Fuse PM Hot water circulation pump primary circuit Pump signal 0 10V wire colours brown connect to ve white...

Страница 44: ...nt only Intermediate nodes are appliances or DDCs that are connected to two other elements The diagram in Figure 6 8 p 36 gives an example of a CAN BUS network 3 appliances are connected to each other...

Страница 45: ...tor on the board set the jumpers as shown in detail B of Figure 6 10 p 38 8 After finished with all the above operations close the electrical panel and refit the front panel of the appliance How to co...

Страница 46: ...oceed as follows You will need the appliance disconnected from the electricity supply 1 Remove the DDC s back panel by undoing the 4 bolts securing it 2 Cut a suitable length of power cord minimum 2x0...

Страница 47: ...ormer The following wiring diagrams show the connection of the DDC to 1 appliance Figure 6 19 p 48 and 2 appliances Figure 6 20 p 49 respectively LEGEND DDC CCI DDC AL supply 4 poles connector 1 clamp...

Страница 48: ...one unit LEGEND DDC direct digital control SCH electronic board S61 J1 Jumper CAN BUS in board S61 J21 Jumper CAN BUS in board DDC A terminal nodes connection 3 wires J1 e J21 closed H L GND data sig...

Страница 49: ...ure 6 21 p 50 and check that the jumper J10 located at the bottom left of the electronic board above the NO Contact contacts is CLOSED as shown in detail A If the power of the pump is equal to or high...

Страница 50: ...ance through a relay If several appliances are connected on the same hydraulic circuit it is always necessary to provide a safety transformer SELV secondary with relevant relay make connections accord...

Страница 51: ...iable flow pump WILO STRATOS PARA can also be used In this case for the electrical wiring of the pump please refer to Figure 6 15 p 43 and the relevant paragraph The primary circulation pump s must be...

Страница 52: ...onnect the plant water circulation pump For how to connect the system pumps see the section with this title in Paragraph 6 4 p 44 Variable flow pump WILO STRATOS PARA can also be used In this case for...

Страница 53: ...ntenance manual LCGHP LSGHP 53 Figure 6 25 Button connection for flame controller reset LEGEND 1 White 2 Grey 3 Orange 4 Green 5 Yellow Black 6 Black 7 Yellow Green Ground 8 Brown 9 Blue 10 Yellow 11...

Страница 54: ...per the Declaration of Conformity provided by the installer to the owner The Declaration of Conformity CERTIFIES that the installation is compliant with current regulations This Declaration is a manda...

Страница 55: ...the installation technician is authorised to perform such operations and in so doing may invalidate the guarantee of the appliance The appliance is delivered already regulated for the type of gas req...

Страница 56: ...analyser corresponds to the data given in the Table 7 3 p 58 at the Delta CO2 between MAX and MIN potentiality line with tolerance of 0 3 0 0 Example G20 gas if at point 4 a content of CO2 equal to 9...

Страница 57: ...letion of the shut down cycle When the appliance is off switch off power supply and gas supply ac cording to anti icing settings opening the electrical breaker and closing the gas isolation valve GUID...

Страница 58: ...e itself 6 Check that the o ring B is fitted 7 Reassemble the gas valve to the blower with the 4 bolts G taking care that the red silicon hose between the venturi tube and the gas valve see detail F o...

Страница 59: ...NCE Installation user and maintenance manual LCGHP LSGHP 59 Figure 7 2 Gas changeover Gas changeover LEGEND A Gas valve B O ring C O ring D Gas nozzle E Fixing screws F Red silicon pipe G Fixing screw...

Страница 60: ...ance u 412 FLAME CONTROL UNIT ARREST Failure to ignite burner Reset occurs automatically when the solenoid valve opens again new ignition attempt or if the code persists for 5 minutes E 412 FLAME CONT...

Страница 61: ...ng in conditioning mode and the flowmeter of the hot module is closed Reset is automatic and occurs when the condition that generated it ceases to apply u 478 OUTLET HOTWATERTEMPERATURE TOO HIGH Outle...

Страница 62: ...empera ture sensor Reset may be performed from the controller or from the S61 board via menu 2 parameter 1 If the code persists or occurs again contact authorisedTechnical Assistance E 491 CONTROLLER...

Страница 63: ...rmity with the following EC Directives 2006 42 EC Machinery Directive with subsequent amendments and integrations 2004 108 EC Electromagnetic Compatibility with subsequent amendments and integrations...

Страница 64: ...e GA ACF60 00 standard e versioni speciali 2 delle Pompe di Calore a gas ad Assorbimento prodotte da ROBUR S p A serie GAHP GS WS A AR standard e versioni speciali serie GAS HP G W A standard e versio...

Страница 65: ...1 des unit s Absorption gaz fabriqu es par la Soci t ROBUR S p A s rie GA ACF60 00 standard et versions sp ciales 2 des Pompes Chaleur Absorption gaz fabriqu es par la soci t ROBUR S p A s rie GAHP G...

Страница 66: ...i nieniem z kategorii III MODU H dla Total Quality Assurance numer CE 1370 PED H ROB001 13 ITA Wydane przez BUREAU VERITAS ITALIA S p A Via Miramare 15 20126 Milano Italy Uk ady wyposa one s w zaw r b...

Страница 67: ......

Страница 68: ...ficiency Water Heaters and Boilers 7 Lombard Way The MXL Centre Banbury Oxon OX16 4TJ T 44 0 1295 269981 F 44 0 1295 271640 sales lochinvar ltd uk www lochinvar ltd uk Revisione A Codice D LBR724 14 M...

Отзывы: