5 - use this part to connect the air inlet and flue gas outlet to the water heater
Fig. Example parallel venting system
Refer to the table for the correct pipe dimensions of the C13 or a C33 parallel venting
systems.
Description
Unit
LGC 160-210 CE to
LGC 200-350 CE
LGC 245-420 CE to
LGC 380-560 CE
Diameter flue discharge/
air inlet
mm/mm
80/80
80/80
Maximum length air inlet
m
50
75
Maximum length flue gas
outlet
m
50
75
L
equivalent
45°-bend
m
1,1
1,1
L
equivalent
90°-bend
m
3,9
3,9
Caution
Always make sure the installation is in compliance with the requirements stated in this
table.
Caution
Use a special adapter box to convert the concentric connection on the water heater to a
parallel connection. This adapter box converts the 80/125 mm to two times 80 mm. This
adapter (LV312209) can be ordered at your supplier or wholesaler. The use of a different
adapter box may cause the water heater to malfunction.
c
0312582_EcoSword_V4.0, 03-05-2021
45
Содержание EcoSword LGC 160-210 G P CE
Страница 11: ...User part 0312582_EcoSword_V4 0 03 05 2021 11 ...
Страница 12: ...12 ...
Страница 14: ...14 User part ...
Страница 16: ...16 User part ...
Страница 22: ...22 User part ...
Страница 25: ...Installation Maintenance and Service part 0312582_EcoSword_V4 0 03 05 2021 25 ...
Страница 26: ...26 User part ...
Страница 34: ...34 Installation Maintenance and Service part ...
Страница 56: ...56 Installation Maintenance and Service part ...
Страница 68: ...68 Installation Maintenance and Service part ...
Страница 85: ...13 4 Electrical wiring diagram 0312582_EcoSword_V4 0 03 05 2021 85 ...
Страница 90: ...90 Installation Maintenance and Service part ...
Страница 93: ......