LPG COMMISSIONING AND TESTING
The commissioning procedure on LPG is similar to that when the water heater is firing on Natural Gas. As such, the same procedure
should be followed taking in to account the following information:
18.3.1
LPG
PRESSURE
ADJUSTMENT
AND
COMBUSTION
CHECKS
The Lochinvar EcoKnight™ series are supplied with a pre-set gas/air ratio inlet assembly. This must
not be tampered with. Any attempt to adjust the gas valve or venturi will invalidate the warranty.
Combustion figures should be as follows:
Model No.
CO
2
CO
EKW46CE
10.5%
0.5%
<100 ppm
EKW61CE
10.5%
0.5%
<100 ppm
EKW86CE
10.5%
0.5%
<100 ppm
18.3.2
LPG
COMBUSTION
FIGURES
If the combustion figures are not within the range specified, contact Lochinvar Technical Support for further guidance.