54
11
Operating information
Armor X2 control module
Figure 11-1 Status Screen
The Status Screen displays water heater status, Cascade addresses, outlet water temperature, inlet water temperature, and tank
temperature.
The water heater can be forced off by pressing the ON/OFF button. The Details Screen and Main Menu Screen can be accessed
by pressing the appropriate button.
When the ON/OFF switch is turned to the ON position,
the first screen visible on the LCD display will be the
Status Screen. This screen displays the current status of the
Armor X2 water heater. The following items can be viewed or
interacted with on the Status Screen:
On/Off
button - Pressing this button allows the water heater/
Cascade to be placed in either Manual Shutdown Mode or
Standby Mode.
Status
- This line shows the current operating status of the
Armor X2 water heater. Displayed items are as follows:
• Manual Shutdown - The water heater will not respond to
either a system call or a hot water generation call.
• Standby - The water heater has not received a hot water
generation
call.
• HW Call for Heat - The water heater has received a hot water
generation
call.
• HW Pump Delay - The water heater has satisfied a hot
water generation call and the hot water generator pumps
are running for a fixed time to remove any residual heat.
• HW BMS - The water heater has received a call for heat from
a 0-10 VDC BMS control.
• Service Set Point Met - While in Service Mode, the
water temperature at either the outlet sensor or the system
sensor has exceeded 185°F.
• HW Set Point Met - The tank water plus (+) offset
temperature has exceeded the Tank Set Point.
• Anti-Cycle Delay - The water heater has satisfied a call
for heat, but has received another call for heat before
the anti-cycling time parameter has elapsed.
• Cascade ComError - A communication error has occurred
between the Control Module 1 and Control Module 2 or
between the Leader and Member water heaters.
Installation & Operation Manual
Содержание Armor X2 AWL1500