49
10
Start-up
(continued)
Set clock
To program the clock, access the night setback parameter by
pressing the following buttons:
The SMART TOUCH control has a built-in clock that it uses
for its night setback feature and for logging events. This clock
must be set when the water heater is installed, and anytime
the water heater has been powered off for more than one
month. Use the following procedure to set the clock:
1. To set the clock, press the SELECT button in the upper
right-hand corner of the display. The date and time are
displayed as “Day dd/mm/yy hh:mm”. Day = day of the
week (1 = Monday, 2 = Tuesday, etc.), dd = date, mm =
month, yy = year, hh = hour, mm = minutes (24 hour
time; 2:30PM = 14:30).
2. Using the keypad, adjust the date and time by working
from left to right. If a digit has been entered incorrectly,
press the left arrow key on the keypad to back the digit
up. If no change is necessary, press the BACK button to
return to the Parameter List Screen. Once the correct
date and time have been entered press the OK button on
the display to program the date and time into memory
and return to the Parameter List Screen.
NOTICE
The internal clock does not adjust for
Daylight Savings Time and therefore, will
require a manual adjustment.
Configuration of the cascade
When installed in a Cascade system, the individual controls
must be programmed for cascade operation. To program the
cascade parameters, access the Cascade Menu found in the
Setup Menu by pressing the following buttons:
Note:
The CASCADE button on the Main Menu will only
display the current status of the cascade.
1. Once in the Cascade Setup Menu select the appropriate
parameter by pressing the SELECT button.
2. The first time the cascade setup parameters are accessed,
you will be required to enter the service password. Enter
the service password as described in the Armor X2 Service
Manual.
3. Once the password has been entered correctly, the
Parameter Change Screen will appear. The Parameter
Change Screen will display the parameter being changed,
the previous setting of the parameter, and adjustment
buttons.
4. To adjust the parameter, press the + or - buttons to change
the value being displayed.
5. Make the correct adjustments and then press the APPLY
button.
6. Once
all
the parameters have been adjusted press the BACK
button. This will return you to the Setup Menu.
7. Press the SAVE button to program all controls.
Note:
The SAVE button must be pressed to ensure proper
programming of the controls. Failure to press the SAVE button
will require all changes to be reprogrammed.
>>
>>
>>
>>
Installation & Operation Manual
Содержание Armor X2 AWL1500
Страница 66: ...Notes Installation Operation Manual 66...
Страница 67: ...Notes Installation Operation Manual 67...