LXC9220/LXC9210
Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC9220/LXC9210 Product User Manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
�
:
T:+86-769-23836636
�
:
F:+86-769-23166296
�
:
www.lixise.com
Page
14
of
58
5.4.
5.4.
5.4.
5.4. Basic
Basic
Basic
Basic configuration
configuration
configuration
configuration
The basic configuration parameters interface has the following options,press
to select up and
down the items you need to change
,
press
to enter the selected item to modify the state
,
press
can modify the value
,
Can shift
,
Change after press
to save the changes.
�
Tips
Tips
Tips
Tips
:
This series of controllers using a large-screen display, just a basic configuration menu to query
and modify all items.
1
Language Selection:
2
Mains detection option:
3
Mains rated voltage(30-30000V):
4
Mains rated frequency (10-65Hz):
5
Fast load:
6
Starting conditions for success:
7
Engine Teeth(10-300):
8
Engine rated speed(0-6000RPM):
9
Gen rated voltage(30-30000V):
10
Gen rated frequency(10-65Hz):
11 CT ratio(6000/5A):
12 Rated current(5-6000A):
13 Rated power(KW):
14 Battery Voltage (0-600V):
15 Module date:
16 Module time:
17 Start delay(0-3600s):
18 Stop delay(0-3600s):
19 Return delay(0-3600s):
20 Preheat timer(0-3600s):
21 Cranking timer(3-60s):
22 Crank Rest Timer (3-60s):
23 Safety on time(0-3600s):
24 Start idle timer(0-3600s):
25 Warming up timer(0-3600s):
26 Cooling timer (0-3600s):
27 Stop idle timer(0-3600s):
28 ETS(Energize to Stop) hold delay(0-3600s):
29 Wait stop delay(0-3600s):
30 After stop delay (0-3600s):
31 Controller information:
5.5.
5.5.
5.5.
5.5. A
A
A
Advanced
dvanced
dvanced
dvanced configuration
configuration
configuration
configuration
Press the
key, enter the correct password to enter the advanced parameters
configuration menu, press
to return to the previous menu.
1
Application configuration
2
Timer
3
Engine
4
Generator
5
Load
6
Analog Sensor
7
Digital Inputs
8
Digital Outputs
9 ATS
10 Mains
11 Module
12 Scheduled
13 Maintenance
14 GSM(SMS)
15 Controller information
16 Calibration parameters