Page 5
SE-330 Series (New Revision) Modbus/TCP Interface
Rev. 0-E-121117
APPENDIX A
MODBUS REGISTER TABLE
A
TTRIBUTE
N
UMBER
A
TTRIBUTE
N
AME
S
ERVICES
D
ATA
T
YPE
N
OTES
0
Model Code
Read Only
T1
Always Reads 330
1
Software Version
Read Only
T1
Where 100 = 1.00
2
Serial Number
Read Only
T2 (Low)
3
Read Only
T2 (High)
4
Model Type
Read Only
T3
5
Communication Code
Read Only
T4
6
Command Register
Write Only
T5
7
8
9
10
Date
Read Only
T6 (Low)
11
Read Only
T6 (High)
12
Time
Read Only
T7 (Low)
13
Read Only
T7 (High)
14
EF/GF Trip Time (s)
Read Only
T15
15
EF/GF Trip Level (%)
Read Only
T16
16
EF/GF MEM Trip Level (%)
R/W
T1
17
Pulse Period (s)
Read Only
T19
Not used on SE-330AU or SE-330HV.
18
Vn Trip Level (V)
Read Only
T1
19
NGR Calibration Value
Read Only
T20
Signed 16-Bit Value
20
K1 Configuration
Read Only
T8
21
K1 Mode
Read Only
T9
Not used on SE-330AU or SE-330HV.
22
EF/GF-Trip Latch
Read Only
T10
Not used on SE-330AU or SE-330HV.
23
RF-Trip Latch
Read Only
T10
24
Sensing Resistor Selection
Read Only
T11
25
Frequency
Read Only
T12
26
Spare
Read Only
T1
27
Upgrade Enable
Read Only
T13
28
Pulse Enable State
Read Only
T14
Not used on SE-330AU or SE-330HV
29
SD Card Status
Read Only
T17
30
Remote Reset State
Read Only
T14
31
Calibration State
Read Only
T14
32
K2 Mode
R/W
T18
33
K3 Mode
R/W
T18
34
CT Primary
R/W
T1
See “Effective CT Primary” Setting in SE-MON330.
35
NGR Current (%FS)
Read Only
T1
36
NGR Voltage (% Setting)
Read Only
T1
37
Resistance Change (Ohms)
Read Only
T20
38
CT Detection
Read Only
T1
SE-330AU Only
39
Geo-Magnetic Filter
R/W
T31
40
Resistor-Fault Trip Time (s)
R/W
T1
41
Resistor-Fault Trip Level
(ohms)
R/W
T1
42
Diagnostic LED behavior
R/W
T34
43
44
45
46
K1 Trip Relay
Read Only
T21
47
K2 GF Relay
Read Only
T21
48
K3 RF Relay
Read Only
T21
49
Drive Polarity Output
Read Only
T1
1 = Negative 0 = Positive
50