![Littelfuse SE-330 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/littelfuse/se-330/se-330_manual_1928632014.webp)
Page 10
SE-330 Series (New Revision) Modbus/TCP Interface
Rev. 0-E-121117
Data Types (continued)
T
YPE
C T
YPE
D
ESCRIPTION
N
OTES
T24
Short
1 = Healthy
0 = Not Healthy
T25
Short
0 = NONE
1 = Factory Default 0
2 = Factory Default 1
3 = Upgrade 0
4 = Upgrade 1
T26
Short
Bit 1, K3
1 = RF Indication Relay Energized
0 = Not Energized
Bit 2, K2
1 = EF/GF Indication Relay Energized
0 = Not Energized
Bit 3, K1
1 = Trip/Pulse Relay Energized
0 = Not Energized
T27
Short
Bit 0, S4
1 = RF Latched
0 = RF Not Latched
Bit 1, S3
1 = EF/GF Latched
0 = EF/GF Not Latched
Bit 2, S5
1 = 20 k Sensor (200 k for SE-330HV)
0 = 100 k Sensor
Bit 3, S6
1 = 50 Hz
0 = 60 Hz
Bit 4, S2
1 = Fail Safe Trip-Relay Operation
0 = Non Fail Safe Operation
S2 not applicable to SE-330AU.
Bit 5, S1
1 = Trip Configuration (K1)
0 = Pulsing Configuration (K1)
S1 not applicable to SE-330AU, SE-330HV.
Bit 6, Not Used = 0
Bit 7, Not Used = 0
T28
Long
IP Address (a.b.c.d)
(High) Bits 31..24 = a
(High) Bits 23..16 = b
(Low) Bits 15..8 = c
(Low) Bits 7..0 = d
T29
Long
Long
MAC Address (a:b:c:d:e:f)
(Word2) Bits 47..40 = a
(Word2) Bits 39..32 = b
(Word1) Bits 31..24 = c
(Word1) Bits 23..16 = d
(Word0) Bits 15..8 = e
(Word0) Bits 7..0 = f
T30
Short
0 = None
1 = Calibration Error
2 = Remote Trip
3 = CT Latch Error
4 = ADC Error
5 = SD Card Error
6 = Watchdog Trip
7 = Hardware Error
8 = NVRAM Error
9 = Flash Upgrade Error
10 = USB Error
T31
Short
0 = Disabled
1 = Enabled