Page E-3
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix E, Register Formats
T
YPE
C
T
YPE
D
ESCRIPTION
(1)
T43
Short Alarm
Action
0:
Disabled
1:
Alarm1
2:
Alarm2
3:
Alarm3
4: Alarm1 & Alarm2
5: Alarm1 & Alarm3
6: Alarm1 & Alarm2 & Alarm3
7: Alarm2 & Alarm3
T45
Short
Trip/Alarm Message Code Bits
(3)
15..0
T46
Short
Trip/Alarm Message Code Bits
(3)
31..16
T47
Short
Trip/Alarm Message Code Bits
(3)
47..32
T48
Short
Trip/Alarm Message Code Bits
(3)
63..48
T49
Short
Trip/Alarm Message Code Bits
(3)
79..64
T50
Short
Trip/Alarm Message Code Bits
(3)
95..80
T51
Short
Trip/Alarm Message Code Bits
(3)
111..96
T52
Short
Trip/Alarm Message Code Bits
(3)
127..112
T65
Short
Network Communication Type
0:
None
1:
A-B
DF1
2:
DeviceNet
3:
Reserved
4: Modbus RTU
5: Modbus TCP
6:
Reserved
T66
Short
Local Communication Baud Rates
0:
9,600
bit/s
1: 19,200 bit/s
2: 38,400 bit/s
T67
Short
Trip and Alarm Summary
Bit0:
0
Bit1:
0
Bit2:
0
Bit3:
0
Bit4:
Trip1
Bit5:
Trip2
Bit6:
Trip3
Bit7:
Alarm1
Bit8:
Alarm2
Bit9:
Alarm3
Содержание FPU-32
Страница 2: ...Factory default password is 1111 New Password See Section 4 5 Feeder Identification...
Страница 8: ...Page 1 4 FPU 32 Feeder Protection Unit Rev 2 A 103014 Introduction This page intentionally left blank...
Страница 16: ...Page 2 8 FPU 32 Feeder Protection Unit Rev 2 A 103014 Installation This page intentionally left blank...
Страница 44: ...Page 6 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Theory of Operation This page intentionally left blank...
Страница 46: ...Page 7 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Communications This page intentionally left blank...