![Littelfuse Startco FPU-32 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/littelfuse-startco/fpu-32/fpu-32_manual_1928675080.webp)
Page E-2
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix E, Register Formats
T
YPE
C
T
YPE
D
ESCRIPTION
(1)
T23
Long Date
Bits 31..16: Year in Binary
Bits 15..8: 1-12 Months in Binary
Bits 7..0: 1-31 Days in Binary
T24
Long Time
Bits 31..24: 0-23 Hours in Binary
Bits 23..16: 0-60 Minutes in Binary
Bits 15..8: 0-60 Seconds in Binary
Bits 7..0: 0-99 Hundredths of a Second in Binary
T31
Char
RTC ASCII-Character Setting String:
YY/MM/DD
HH:mm:SS
YY: 2-digit Year (Year 2000 – 2099)
MM: Month 1-12
DD: Day 1-31
HH: Hour 0-23
mm: Minute 0-59
SS: Seconds 0-59
RTC is updated when “Set RTC” command is issued.
T32
Short Free
Record
Pointer
Subtract one to obtain last record.
Range is 0 to 99.
T38
Short
Overload Reset Type
0:
Normal
1:
Autoreset
2:
Rapid
T42
Short Trip
Action
0:
Disabled
1:
Trip1
2:
Trip2
3:
Trip3
4: Trip1 & Trip2
5: Trip1 & Trip3
6: Trip1 & Trip2 & Trip3
7: Trip2 & Trip3
Содержание FPU-32
Страница 2: ...Factory default password is 1111 New Password See Section 4 5 Feeder Identification...
Страница 8: ...Page 1 4 FPU 32 Feeder Protection Unit Rev 2 A 103014 Introduction This page intentionally left blank...
Страница 16: ...Page 2 8 FPU 32 Feeder Protection Unit Rev 2 A 103014 Installation This page intentionally left blank...
Страница 44: ...Page 6 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Theory of Operation This page intentionally left blank...
Страница 46: ...Page 7 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Communications This page intentionally left blank...