Protective Functions
CURRENT IN MULTIPLES OF PICKUP SETTING (I
M
)
TIME IN SECONDS (t)
IEEE MODERATE INVERSE
1
2
3
4
5
6
7
8
9 10
20
0.1
0.2
0.3
0.4
0.5
0.7
1
2
3
4
5
7
10
20
30
40
50
70
100
1.0
0.7
0.5
0.3
0.2
0.1
0.05
I
M
> 1.1: t = T
M
x 3 x (0.0515/(I
M
0.02
- 1) + 0.114)
I
M
> 20: t = t
I
M
=20
I
M
< 0.9: t
reset
= T
M
x 3 x 4.85/(1 - I
M
2
)
Time
Multiplier
(T
M
)
FIGURE 5.7 IEEE Moderate Inverse Curves.