Page D-2
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix D, Communications Database Table
FPU-32
R
EGISTER
(D
ECIMAL
)
M
ODBUS
R
EGISTER
(D
ECIMAL
)
D
EVICE
N
ET
(Hex)
(N
OTE
4)
A-B F
ILE
(D
ECIMAL
)
(N
OTE
2)
D
ESCRIPTION
A
CCESS
R
ANGE
T
YPE
(N
OTE
1)
Overload Reset
44
40045
2C-00-64
3:44
Overload Reset Type
R/W
0 – 2
T38
45
40046
2C-00-65
3:45
Overload Reset Level
R/W
0.1 – 0.9
T1 (Low)
46 40047 3:46
T1
(High)
Phase Inverse Group 1
50
40051
69-01-01
3:50
Trip Action
R/W
0 – 7
T42
51
40052
69-01-02
3:51
Curve Type
R/W
0 – 7
T73
52
40053
69-01-03
3:52
Time Multiplier
R/W
0.05 – 1.0
T1 (Low)
53 40054 3:53
T1
(High)
54
40055
69-01-04
3:54
Pickup in pu of CT Rating
R/W
0.1 – 10 x I
p
T1
(Low)
55 40056 3:55
T1
(High)
Phase Inverse Group 2
60
40061
69-02-01
3:60
Trip Action
R/W
0 – 7
T42
61
40062
69-02-02
3:61
Curve Type
R/W
0 – 7
T73
62
40063
69-02-03
3:62
Time Multiplier
R/W
0.05 – 1.0
T1 (Low)
63 40064 3:63
T1
(High)
64
40065
69-02-04
3:64
Pickup in pu of CT Rating
R/W
0.1 – 10 x I
p
T1 (Low)
65 40066 3:65
T1
(High)
Phase Definite Time Group 1
70
40071
64-01-01
3:70
Trip Action
R/W
0 – 7
T42
71
40072
64-01-02
3:71
Alarm Action
R/W
0 – 7
T43
72
40073
64-01-03
3:72
Trip Level
R/W
0.1 – 15 x I
p
T1 (Low)
73 40074 3:73
T1
(High)
74
40075
64-01-04
3:74
Trip Delay
R/W
0 – 10 s
T1 (Low)
75 40076 3:75
T1
(High)
76
40077
64-01-05
3:76
Alarm Level
R/W
0.1 – 15 x I
p
T1 (Low)
77 40078 3:77
T1
(High)
78
40079
64-01-06
3:78
Alarm Delay
R/W
0 – 10 s
T1 (Low)
79 40080 3:79
T1
(High)
Phase Definite Time Group 2
84
40085
64-02-01
3:84
Trip Action
R/W
0 – 7
T42
85
40086
64-02-02
3:85
Alarm Action
R/W
0 – 7
T43
86
40087
64-02-03
3:86
Trip Level
R/W
0.1 – 15 x I
p
T1 (Low)
87 40088 3:87
T1
(High)
88
40089
64-02-04
3:88
Trip Delay
R/W
0 – 10 s
T1 (Low)
89 40090 3:89
T1
(High)
90
40091
64-02-05
3:90
Alarm Level
R/W
0.1 – 15 x I
p
T1 (Low)
91 40092 3:91
T1
(High)
92
40093
64-02-06
3:92
Alarm Delay
R/W
0 – 10 s
T1 (Low)
93 40094 3:93
T1
(High)
Содержание FPU-32
Страница 2: ...Factory default password is 1111 New Password See Section 4 5 Feeder Identification...
Страница 8: ...Page 1 4 FPU 32 Feeder Protection Unit Rev 2 A 103014 Introduction This page intentionally left blank...
Страница 16: ...Page 2 8 FPU 32 Feeder Protection Unit Rev 2 A 103014 Installation This page intentionally left blank...
Страница 44: ...Page 6 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Theory of Operation This page intentionally left blank...
Страница 46: ...Page 7 2 FPU 32 Feeder Protection Unit Rev 2 A 103014 Communications This page intentionally left blank...