NTI AG / LinMot
User Manual PROFINET PROFIdrive Interface
Page 35/38
5
PROFIdrive Parameters
5.1 Parameters
The PROFIdrive Interface has an additional parameter tree branch (Parameters
→
Profinet), which can be configured with the distributed LinMot-Talk software.
With these parameters, the PROFIdrive interface can be enabled or disabled.
The LinMot-Talk software can be downloaded from
http://www.linmot.com
under the section
download, software & manuals.
5.1.1. PROFdrive/Dis-/Enable
With the Dis-/Enable parameter the LinMot Servo Drive can be run without the Ethernet
PROFIdrive Interface going online. So in a first step the system can be configured and run
without any bus connection.
PROFIdrive/Dis-/Enable
Disable
Servo Drive runs without PROFINET.
Enable
Servo Drive runs with PROFINET connection.
IMPORTANT
: If the PROFIdrive Interface is disabled, the integrated TPS1-ASIC rests in
reset state! No messages will be sent to other devices connected to the
PROFINET-Network via the servo drive.
5.1.2. PROFdrive/Byte Order
With the Byte Order parameter the used Byte order of the transmitted data could be defined.
PROFIdrive/Byte Order
reversed
Byte order is reversed. For S7 PLC_s select reversed.
not reversed
Byte order is not reversed.
5.1.3. PROFdrive/Word Order
With the Word Order parameter the used Word order of the transmitted data could be
defined.
PROFIdrive/Word Order
Reversed
Word order is reversed.
not reversed
Word order is not reversed.