![Lindab UltraLink FTMU Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/lindab/ultralink-ftmu/ultralink-ftmu_technical-information_1919367021.webp)
21
Lindab reserves the right to make changes without prior notice
2021-11-02
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink
®
Monitor
FTMU
lindab | technical information
Addr
ess
UltraLink
®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
4x432
X
X
Analog Output 2 Temp.
Min.
Min temperature shown = Min output voltage
(Only relevat when 4x431 is set to 1 )
16bit
ºC
0
-40
50
RW
4x433
X
X
Analog Output 2 Temp.
Max.
Max temperature shown = Max output volta-
ge (Only relevant when 4x431 is set to 1 )
16bit
ºC
50
-40
50
RW
4x434
X
X
Analog Output 2 Flow Min.
Min flow shown = Min output voltage (Only
relevant when 4x431 is set to 0 )
16bit
l/s
0
-4700
4700
RW
4x436
X
X
Analog Output 2 Flow Max. Max flow shown = Max output voltage (Only
relevant when 4x431 is set to 0 )
16bit
l/s
*
-4700
4700
RW
Sensor
4x2100
X
X
Sensor Presence Enable
Control
0 = Disable
1 = Enable
16bit
0
0
1
RW
4x2101
X
X
Sensor Presence Trigger
Time
Temporary trigger time for presence
16bit
min
1
0
60
RW
4x2102
X
X
Sensor Presence Trigger
Factor
Factor related to toggle 0 -> 1
16bit
%
100
150
49
501
RW
4x2103
X
X
Sensor Unoccupied Mul-
tiplication Factor
Multiplication factor for Unoccupied
16bit
%
100
50
-1
101
RW
4x2110
X
X
Sensor Temperature Ena-
ble Control
0 = Disable
1 = max
2 = min
3 = avg
16bit
0
0
3
RW
4x2111
X
X
Sensor Temperature
Baseline
Baseline for temperature
16bit
C
22
-50
50
RW
4x2112
X
X
Sensor Temperature
Deviation
Allowed deviation before full factor effect
16bit
C
2
0
50
RW
4x2113
X
X
Sensor Temperature Dead
Band
Dead band for sensor type Temperature
16bit
%
100
50
-1
101
RW
4x2114
X
X
Sensor Temperature Mul-
tiplication Factor
Multiplication factor for Temperature
16bit
%
100
150
49
501
RW
4x2120
X
X
Sensor Flow Enable
Control
0 = Disable
1 = Sum
16bit
0
0
1
RW
4x2121
X
X
Sensor Flow Dead Band
Dead band for sensor type Flow
16bit
%
100
2
0
100
RW
4x2122
X
X
Sensor Flow Multiplication
Factor
Multiplication factor for Flow
16bit
%
100
100
0
500
RW
4x2130
X
X
Sensor Humidity Enable
Control
0 = Disable
1 = max
2 = min
3 =avg
16bit
0
0
3
RW
4x2131
X
X
Sensor Humidity Baseline
Baseline for humidity
16bit
%
50
0
100
RW
4x2132
X
X
Sensor Humidity Deviation
Allowed deviation before full factor effect
16bit
%
20
0
100
RW
4x2133
X
X
Sensor Humidity Dead
Band
Dead band for sensor type Humidity
16bit
%
100
50
-1
101
RW
4x2134
X
X
Sensor Humidity Multipli-
cation Factor
Multiplication factor for Humidity
16bit
%
100
150
49
501
RW
4x2135
X
X
Sensor Humidity Supplied
Estimated value of supply air humidity
16bit
%
50
0
100
RW
4x2140
X
X
Sensor CO
2
Enable Control
0 = Disable
1 = max
2 = min
3 =avg
16bit
0
0
3
RW
4x2141
X
X
Sensor CO
2
Baseline
Baseline for CO
2
16bit
ppm
600
400
2000
RW
4x2142
X
X
Sensor CO
2
Deviation
Allowed deviation before full factor effect
16bit
ppm
400
0
1000
RW
4x2143
X
X
Sensor CO
2
Dead Band
Dead band for sensor type CO
2
16bit
%
100
50
-1
101
RW
4x2144
X
X
Sensor CO
2
Multiplication
Factor
Multiplication factor for CO
2
16bit
%
100
150
49
501
RW
4x2145
X
X
Sensor CO
2
Supplied
Estimated value of supply air CO
2
16bit
ppm
400
300
2000
RW
* = the value depends on the dimension of the product.