UltraLink
®
Monitor
FTMU
lindab | technical information
* = the value depends on the dimension of the product.
Addr
ess
UltraLink
®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
Sensor
3x2001
X
X
Sensor Global Set Point
Factor
Multiplication factor for flow set point
16bit
100
100
RO
3x2002
X
X
Sensor Global Factored
Set Point
Holding register FLOW_SET_POINT (314)
multiplied with SENSOR_GLOBAL_SET_
POINT_FACTOR
16bit
l/s
0
RO
3x2007
X
X
Sensor Global State for
Control
Current state of control:
0 = Off
1 = Unoccupird
2 = Normal
3 = Forced
4 = Delayed presence
5 = Temperature increase
6 = Temperature decrease
7 = CO2 decrease
8 = Humidity increase
9 = Humidity decrease
10 = VOC decrease
11 = Particles decrease
50 = Flow slave
100 = Clearing error
101 = Error C1
102 = Error C2
103 = Error C3
104 = Error C4
105 = Error C5
106 = Error C6
3x2012
X
X
Sensor Com Current Pre-
sence Sum
Current Presence based on sum from all
sensors
16bit
0
RO
3x2014
X
X
Sensor Com Presence
State
0 = Disabled
1 = Unoccupied
2 = Normal
3 = Forced
4 = Delayed presence
5 = Error
16bit
RO
3x2021
X
X
Sensor Com Min. Temp
Minimum Temperature
16bit
degC
10
RO
3x2022
X
X
Sensor Com Max. Temp
Maximum Temperature
16bit
degC
10
RO
3x2023
X
X
Sensor Com Average Temp Average Temperature
16bit
degC
10
RO
3x2025
X
X
Sensor Com Temp State
0 = Disabled,
1 = Within deadband,
2 = Outside deadband,
3 = Error
16bit
RO
3x2034
X
X
Sensor Com Summed
Flow
Summed Flow
16bit
l/s
10
RO
3x2036
X
X
Sensor Com Flow State
0 = Disabled,
1 = Within deadband,
2 = Outside deadband,
3 = Error
16bit
RO
3x2041
X
X
Sensor Com Min. Humidity
Minimum Humidity
16bit
% RH
10
RO
3x2042
X
X
Sensor Com Max. Hu-
midity
Maximum Humidity
16bit
% RH
10
RO
3x2043
X
X
Sensor Com Average
Humidity
Average Humidity
16bit
% RH
10
RO
3x2045
X
X
Sensor Com Humidity
State
0 = Disabled,
1 = Within deadband,
2 = Otside deadband,
3 = Error
16bit
RO
3x2051
X
X
Sensor Com Minimum CO
2
Minimum CO
2
16bit
ppm
0
RO
3x2052
X
X
Sensor Com Maximum
CO
2
Maximum CO
2
16bit
ppm
0
RO
3x2053
X
X
Sensor Com Average CO
2
Average CO
2
16bit
ppm
0
RO