20
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink
®
Monitor
FTMU
lindab | technical information
Addr
ess
UltraLink
®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
Analog input (Settings below are only relevant when register 4x071 is set to 1)
4x500
X
Analog In Level Conf.
Analog input:
0 = 0-10 V,
1 = 10-0 V,
2 = 2-10 V,
3 = 10-2 V.
16bit
2
0
3
RW
4x501
X
Analog In Angle Minimum
Min angle = min voltage
16bit
%
0
0
100
RW
4x502
X
Analog In Angle Maximum
Max = max voltage
16bit
%
100
0
100
RW
4x503
X
Analog In Flow Minimum
Min flow = min voltage
(Must be equal or higher than register 4x315)
16bit
l/s
0
0
4700
RW
4x504
X
Analog In Flow Maximum
Max flow = max voltage
(Must be equal or lower than register 4x316)
16bit
l/s
*
0
4700
RW
4x510
X
Analog In Override Low
Trigger Min.
Lowest voltage level to activate 1st Override
level
(Only relevant when 4x500 is set to 2 or 3)
16bit
V
10
0
0
20
RW
4x511
X
Analog In Override Low
Trigger Max.
Highest voltage level to activate 1st Override
level (Only relevant when
4x500 is set to 2 or 3)
16bit
V
10
8
0
20
RW
* = the value depends on the dimension of the product.
Addr
ess
UltraLink
®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
4x005
X
X
RS485 Protocol Conf.
Protocol:
0 = Modbus;
1 = Not used;
2 = Pascal;
16bit
0
0
2
RW
4×006
X
X
Bluetooth Password
Password which must be provided to pair
Bluetooth devices. This password can always
be changed from wired connection. From wi-
reless it can only be changed when connec-
tion is established using current password.
16bit
1111
0000
9999
RW
4×007
X
X
Bluetooth Enable
Enable Bluetooth Communication
0 = Bluetooth turned off;
1 = Bluetooth turned on;
16bit
1
0
2
RW
4x008
X
X
PLA
ID used for Pascal
16bit
1
239
RW
4x009
X
X
ELA
ID used for Pascal
16bit
1
239
RW
4×010
X
X
Bluetooth TX Power Level
Configure TX Power Level dBm. Accepted
values:
-40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7,
8, 9
16bit
0
-40
9
RW
System configuration
4x072
X
X
Installation as Extract or
Supply
Specifies if device is in supply or extract:
0 = Undefined
1 = Supply
2 = Extract
16bit
0
0
2
RW
4x073
X
X
Installation Zone Number
Specifies in which zone the product is
installed in
16 bit
0
0
65535
RW
4x074
X
X
Installation Floor Number
Specifies on which floor the product is
installed in
16bit
0
0
65535
RW
4x082
X
X
Execute Factory Reset
Factory reset of all parameters. Unit will
restart
0 = Do nothing;
1 = Factory Reset
16bit
0
0
1
RW
4x083
X
X
Execute Reboot
Reboot the unit
0 = Do nothing;
1 = Reboot the unit;
16bit
0
0
1
RW
Analog output
4x400
X
X
Analog Output 1 Level
Conf.
Analog output config:
0 = 0-10 V,
1 = 10-0 V,
2 = 2-10 V,
3 = 10-2 V.
16bit
2
0
3
RW
4x401
X
X
Analog Output 1 Unit Conf.
Show:
0 = Flow;
1 = Temperature;
2 = Angle;
16bit
0
0
2
RW
4x402
X
X
Analog Output 1 Temp.
Min.
Min temperature shown = Min output voltage
(Only relevant when 4x401 is set to 1 )
16bit
ºC
0
-40
50
RW
4x403
X
X
Analog Output 1 Temp.
Max.
Max temperature shown = Max output volta-
ge (Only relevant when 4x401 is set to 1 )
16bit
ºC
50
-40
50
RW
4x404
X
X
Analog Output 1 Flow Min.
Min flow shown = Min output voltage (Only
relevant when 4x401 is set to 0 )
16bit
l/s
0
-4700
4700
RW
4x406
X
X
Analog Output 1 Flow Max. Max flow shown = Max output voltage (Only
relevant when 4x401 is set to 0 )
16bit
l/s
*
-4700
4700
RW
4x430
X
X
Analog Output 2 Level
Conf.
Analog output config:
0 = 0-10 V,
1 = 10-0 V,
2 = 2-10 V,
3 = 10-2 V.
16bit
2
0
3
RW
4x431
X
X
Analog Output 2 Unit Conf.
Show:
0 = Flow
1 = Temperature
2 = Angle
16bit
2
0
2
RW