1.   Short extension duct

2.   Flexible  connector

L  Air duct length

Lf  Flexible part length of flexible connector

The length (Lf ) of the flexible element must be equal or higher to 1% 

of air duct length.

The minimum length (Lf ) of the flexible element is equal to 250 mm 

for circular damper.

The minimum length (Lf ) of the flexible element is equal to 100 mm 

for rectangular damper.

1.   Positioning  brackets

2.   Sealing

3.   Short extension duct

4.   Flexible  connector

5.   Floor

 

†

Use of flexible connectors in the case of remote installation

1.   Duct

2.   Flexible  connector

3.   Short extension duct

4.   Fire  damper

 

†

Example of damper support in case of installation within floor 

with Fire Batt (Weichschott) sealing

1.   Fire  damper

2.   Short extension duct

3.   Flexible  connector

4.   C-shaped profile 36 x 36 x 2,5 

mm, e.g. Würth or Müpro or Hilti 

or equivalent

5.   Fixing bracket 38 x 30 x 2 mm, 

e.g. Würth or Müpro or Hilti or 

equivalent

6.   M10  screw

7.   Washer

8.   M10  nut

9.   Fixing bracket 90° 36 x 33 x 5 

mm, e.g. Würth or Müpro or Hilti 

or equivalent

10.   M10 threaded rod

 

„

Minimum distances

It is recommended to keep enough space for using the control 

mechanism or for maintenance.

Maintain a minimum distance of 200 mm between fire damper and 

any other element that crosses the wall (e.g: doors, electrical cables, 

hydraulic pipes etc.) and between different fire damper models.

In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-

mum distances indicated below.

Содержание RECTANGULAR Series

Страница 1: ...ts the aesthetic or dimensional features the technical data the equipment and acces sories indicated could be subject to variations Installation booklet Cert N 1812 CPR 1045 EN 15650 www mp3 italia it...

Страница 2: ...i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 90 S Installation within vertical light wall gypsum blocks wall Wall minimum thickness 70...

Страница 3: ...Rock wool 140 kg m and endothermic varnish sealing ve i o W B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 EI 120 S Installation within vertical...

Страница 4: ...00 EI 120 S Installation remote from the vertical light wall gypsum blocks wall with Fire Batt Weichschott sealing Wall minimum thickness 100 mm Wall minimum density 995 kg m Rock wool 140 kg m and en...

Страница 5: ...r 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade opening mode The damper must be opened when the ventilation system if switch...

Страница 6: ...nnec tions for further information To manually open the damper use the handle supplied and carefully rotate clockwise to the 90 indicator To hold the damper in open position operate on the lever indic...

Страница 7: ...microswitches included 1 Microswitch contacts for blade position 2 Magnet power supply contacts 24V DC or 48V DC Keep to the polarity for input magnet MAG Magnet power supply FCU Closed blade contact...

Страница 8: ...SB Belimo BFL24T Opening 2 5 W In stand by 0 8 W Motor 230 V AC WK25DSB Belimo BFL230T Opening 3 5 W In stand by 1 1 W Motor 24 V AC DC WK25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230 V...

Страница 9: ...a for blade exposition values Fire damper and short extension ducts have to be connected to each other and fixed at the bottom and near the damper and suspended from the ceiling 1 Fire damper 2 Sealin...

Страница 10: ...in case of installation within floor with Fire Batt Weichschott sealing 1 Fire damper 2 Short extension duct 3 Flexible connector 4 C shaped profile 36 x 36 x 2 5 mm e g W rth or M pro or Hilti or eq...

Страница 11: ...ng 200 75 No Floor EI 180 S Installation within floor Mortar sealing 200 75 No EI 120 S Installation within floor Mortar sealing 200 75 No EI 90 S Installation within floor Mortar sealing 200 75 No Th...

Страница 12: ...tained as well as the correlation between wall floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor...

Страница 13: ...al walls Shaft wall The following indications are given for the installation walls U shaped horizontal metal frame minimum width 50 mm and C shaped vertical frame minimum width 49 mm made from sheet m...

Страница 14: ...and in the drawing Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall minimum thickness S mm Sealing EI 120 S Installation within vertical rigid wall Wall mi...

Страница 15: ...opening must be provided in the wall as indicated in the table and in the drawing In case of paired installation refer to the section Fire dampers pairing for further information Damper positioning P...

Страница 16: ...B 90 x H 90 185 100 Mortar sealing EI 120 S Installation within floor Floor minimum density 650 kg m EI 120 S 500 Pa From B 70 x H 70 to B 90 x H 90 170 150 Mortar sealing EI 180 S Installation withi...

Страница 17: ...le height see table above E Damper protrusion from the wall see table above 1 Rock wool panel 50 mm thick with 140 kg m density 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PASTE...

Страница 18: ...aded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the wall and the damper using mortar suit able f...

Страница 19: ...shaped steel profiles 10x41x41x41x10 mm 2 M10 threaded rods 4 M10 nuts Position the threaded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of th...

Страница 20: ...d rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the damper and the wall using Fire Batt Weichschott...

Страница 21: ...loor as indicated in the drawing The hanging structure is composed by 4 Angle connectors 105x105x90 mm Screws M8 x 40 mm Washers 15 x 9 mm Flush anchors M8 x 40 mm Filling Fill the space between the f...

Страница 22: ...rts characteristics for further information Comply with the minimum distances indicated on section Minimum distances Wall opening A opening must be provided in the wall as indicated in the table and i...

Страница 23: ...lasterboard infill panel thickness 20 mm 3 Mortar M 10 EN998 2 or plaster putty 4 Metal frame 5 Self drilling screw 3 5 X 70 mm D1 Hole base see table above D2 Hole height see table above E Damper pro...