background image

19

D1  Hole base: see table above

D2  Hole height: see table above

1.   Rock wool panel 50 mm thick with 140 kg/m³ density. 

2.   PROMASTOP E PASTE or HILTI CFS-S ACR type sealant

3.   PROMASTOP E PASTE or HILTI CFS-CT endothermic varnish

4.   Vertical  wall

5.   Self-drilling screw Ø 5 X 60 mm

6.   Self-drilling screw Ø 5 X 120 mm

7.   Washer 40 x 40 mm

8.   M10 threaded rod

9.   C-shaped steel profile 10x41x41x41x10 mm

10.   M10  nut

11.   Screw Ø 6 X 20 mm

12.   M6  nut

13.   Mortar M-10, EN998-2 or plaster putty

 

„

Installation remote from the vertical light wall (plasterboard)

Refer to the section Construction supports characteristics  for further 

information.

Comply with the minimum distances indicated on section Minimum 

distances .

 

†

Wall opening

A opening must be provided in the wall as indicated in the table and 

in the drawing

 

†

Damper positioning

Connect fire damper to the galvanized steel duct as indicated in the 

drawing.

Between fire damper and wall the maximum distance is 1000 mm.

The maximum length of the part of duct connected to the damper 

is 2100 mm

The fire damper has to be fixed and suspended from the ceiling as 

indicated in the drawing.

The hanging structure is composed by:

– 2 C-shaped steel profiles 10x41x41x41x10 mm

– 2 M10 threaded rods

– 4 M10 nuts

Position the threaded rods 135 mm from the connection between 

fire damper and duct and at a distance of 50 mm from the side of 

the damper.

 

†

Filling

Fill the space between the wall and the fire damper using rock wool 

which has density of 100 kg/m³.

Cover the rock wool by applying on both faces of the wall a layer of 

plasterboard, to a total minimum thickness of 12,5 mm per side, to 

make a frame 100 mm wide.

Cover the duct over its entire length  and fire damper with 2 rock 

wool panels 50 mm thick and with a density of 140 kg/m³.

The panels must be covered externally with endothermic varnish  

type PROSTOP E PASTE or HILTI CFS-CT (minimum thickness of 1 mm) 

and with an internal perimeter sealant type PROMOSTOP E PASTE or 

HILTI CFS-S ACR (minimum thickness of 1 mm).

Fix first layer of rock wool panel to the duct with screws Ø5 X 60 mm 

and washers 40 X 40 mm, and the second one with screws Ø5 X 120 

mm and washers 40 X 40 mm.

Fire resistance classification 

Hole size “D1 x D2”

[mm]

Wall minimum thickness “S”

[mm]

Sealing

Fle

xible w

all

Installation remote from the vertical light wall (plasterboard)

Wall rock wool minimum density 100 

kg/m³

EI 120 S

(300 Pa)

EI 90 S

(500 Pa)

From (B+75) x (H+75)

to (B+95) x (H+95)

100

Rock wool 100 kg/m³ or 

mortar or plaster putty with 

infill plasterboard (thickness 

12.5 mm)

Содержание RECTANGULAR Series

Страница 1: ...ts the aesthetic or dimensional features the technical data the equipment and acces sories indicated could be subject to variations Installation booklet Cert N 1812 CPR 1045 EN 15650 www mp3 italia it...

Страница 2: ...i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 90 S Installation within vertical light wall gypsum blocks wall Wall minimum thickness 70...

Страница 3: ...Rock wool 140 kg m and endothermic varnish sealing ve i o W B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 EI 120 S Installation within vertical...

Страница 4: ...00 EI 120 S Installation remote from the vertical light wall gypsum blocks wall with Fire Batt Weichschott sealing Wall minimum thickness 100 mm Wall minimum density 995 kg m Rock wool 140 kg m and en...

Страница 5: ...r 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade opening mode The damper must be opened when the ventilation system if switch...

Страница 6: ...nnec tions for further information To manually open the damper use the handle supplied and carefully rotate clockwise to the 90 indicator To hold the damper in open position operate on the lever indic...

Страница 7: ...microswitches included 1 Microswitch contacts for blade position 2 Magnet power supply contacts 24V DC or 48V DC Keep to the polarity for input magnet MAG Magnet power supply FCU Closed blade contact...

Страница 8: ...SB Belimo BFL24T Opening 2 5 W In stand by 0 8 W Motor 230 V AC WK25DSB Belimo BFL230T Opening 3 5 W In stand by 1 1 W Motor 24 V AC DC WK25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230 V...

Страница 9: ...a for blade exposition values Fire damper and short extension ducts have to be connected to each other and fixed at the bottom and near the damper and suspended from the ceiling 1 Fire damper 2 Sealin...

Страница 10: ...in case of installation within floor with Fire Batt Weichschott sealing 1 Fire damper 2 Short extension duct 3 Flexible connector 4 C shaped profile 36 x 36 x 2 5 mm e g W rth or M pro or Hilti or eq...

Страница 11: ...ng 200 75 No Floor EI 180 S Installation within floor Mortar sealing 200 75 No EI 120 S Installation within floor Mortar sealing 200 75 No EI 90 S Installation within floor Mortar sealing 200 75 No Th...

Страница 12: ...tained as well as the correlation between wall floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor...

Страница 13: ...al walls Shaft wall The following indications are given for the installation walls U shaped horizontal metal frame minimum width 50 mm and C shaped vertical frame minimum width 49 mm made from sheet m...

Страница 14: ...and in the drawing Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall minimum thickness S mm Sealing EI 120 S Installation within vertical rigid wall Wall mi...

Страница 15: ...opening must be provided in the wall as indicated in the table and in the drawing In case of paired installation refer to the section Fire dampers pairing for further information Damper positioning P...

Страница 16: ...B 90 x H 90 185 100 Mortar sealing EI 120 S Installation within floor Floor minimum density 650 kg m EI 120 S 500 Pa From B 70 x H 70 to B 90 x H 90 170 150 Mortar sealing EI 180 S Installation withi...

Страница 17: ...le height see table above E Damper protrusion from the wall see table above 1 Rock wool panel 50 mm thick with 140 kg m density 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PASTE...

Страница 18: ...aded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the wall and the damper using mortar suit able f...

Страница 19: ...shaped steel profiles 10x41x41x41x10 mm 2 M10 threaded rods 4 M10 nuts Position the threaded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of th...

Страница 20: ...d rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the damper and the wall using Fire Batt Weichschott...

Страница 21: ...loor as indicated in the drawing The hanging structure is composed by 4 Angle connectors 105x105x90 mm Screws M8 x 40 mm Washers 15 x 9 mm Flush anchors M8 x 40 mm Filling Fill the space between the f...

Страница 22: ...rts characteristics for further information Comply with the minimum distances indicated on section Minimum distances Wall opening A opening must be provided in the wall as indicated in the table and i...

Страница 23: ...lasterboard infill panel thickness 20 mm 3 Mortar M 10 EN998 2 or plaster putty 4 Metal frame 5 Self drilling screw 3 5 X 70 mm D1 Hole base see table above D2 Hole height see table above E Damper pro...

Отзывы: