Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct exceeds 

70°C (or 95°C for the fire damper with 95°C thermal fuse).

It is possible to close the damper by pressing the indicated button.

It is possible to remotely close the fire damper.

The manual command mechanism with magnet is equipped with 

an electromagnet which, in case power is interrupted (interuption 

magnet version) or when power is supplied (input magnet version), 

comands the closing of the damper.

Blade opening mode

The damper must be opened when the ventilation system if 

switched off.

In case of closed damper by pressing the closing button or remotely 

by electromagnet, it is possible to manually open the fire damper 

blade by rotating the lever antyclockwise.

In case of closed damper as a result of the action of the thermosen-

sitive element, it is possible to manually reopen the damper by rotat-

ing the lever counterclockwise once the element has been replaced.

Position indication microswitches

It is advisable to install the fire damper with position microswitches 

(S2 optional) which signal the position of the blade (open or closed). 

Refer to the section Electrical connections  for more details.

Closing by remote control

With power supply input or interruption magnet.

Temperature calibration of thermosensitive element for auto-

matic damper closing

70 °C±7 °C (Standard)

95 °C±9 °C (On request).

 

†

Belimo motorized version

1.   Manual closing switch

2.   Manual opening lever

3.   Position  indicator

4.   Blade locking lever

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct or in 

the room exceeds 72°C (or 95°C for the 95°C version).

To close the damper when the motor is connected, press the switch 

on the temperature sensor or cut off the power supply.

Blade opening mode

To open the damper with the electric motor driven actuator, provide 

power supply to the motor. Refer to the section Electrical connec-

tions  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate clockwise to the 90° indicator. To hold the damper in open 

position operate on the lever indicated in figure.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade’s position (open or closed). Refer to the section Elec-

trical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

 

†

Siemens motorized version

1.   Manual closing switch

2.   Manual opening lever

3.   Screwdriver

4.   Position  indicator

Blade closing mode

Automatic closing with thermal fuse.

The control mechanism has a thermosensitive element that auto-

matically closes the blade when the temperature in the duct or in 

the room exceeds 72°C (or 95°C for the 95°C version).

To close the damper when the motor is connected, press the switch 

on the temperature sensor or cut off the power supply.

Blade opening mode

To open the damper with the electric motor driven actuator, provide 

power supply to the motor. Refer to the section Electrical connec-

tions  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate counterclockwise to the 90 °C indicator. To hold the damp-

er in open position, rotate the screw anticlockwise as shown in the 

picture.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade’s position (open or closed). Refer to the section Elec-

trical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

ELEC TRICAL CONNEC TIONS

 

„

Electrical wiring

Electrical connections must be done by qualified and trained people.

Switch off the power supply before starting any work on the electric 

elements. Never switch on the power supply during electrical con-

nections.

Содержание RECTANGULAR Series

Страница 1: ...ts the aesthetic or dimensional features the technical data the equipment and acces sories indicated could be subject to variations Installation booklet Cert N 1812 CPR 1045 EN 15650 www mp3 italia it...

Страница 2: ...i o D B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 B x H min 100 x 200 max 800 x 600 EI 90 S Installation within vertical light wall gypsum blocks wall Wall minimum thickness 70...

Страница 3: ...Rock wool 140 kg m and endothermic varnish sealing ve i o W B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 B X H min 100 X 200 max 800 X 600 EI 120 S Installation within vertical...

Страница 4: ...00 EI 120 S Installation remote from the vertical light wall gypsum blocks wall with Fire Batt Weichschott sealing Wall minimum thickness 100 mm Wall minimum density 995 kg m Rock wool 140 kg m and en...

Страница 5: ...r 95 C for the fire damper with 95 C thermal fuse It is possible to close the damper by pressing the indicated button Blade opening mode The damper must be opened when the ventilation system if switch...

Страница 6: ...nnec tions for further information To manually open the damper use the handle supplied and carefully rotate clockwise to the 90 indicator To hold the damper in open position operate on the lever indic...

Страница 7: ...microswitches included 1 Microswitch contacts for blade position 2 Magnet power supply contacts 24V DC or 48V DC Keep to the polarity for input magnet MAG Magnet power supply FCU Closed blade contact...

Страница 8: ...SB Belimo BFL24T Opening 2 5 W In stand by 0 8 W Motor 230 V AC WK25DSB Belimo BFL230T Opening 3 5 W In stand by 1 1 W Motor 24 V AC DC WK25VSS Siemens GRA126 Opening 3 5 W In stand by 2 W Motor 230 V...

Страница 9: ...a for blade exposition values Fire damper and short extension ducts have to be connected to each other and fixed at the bottom and near the damper and suspended from the ceiling 1 Fire damper 2 Sealin...

Страница 10: ...in case of installation within floor with Fire Batt Weichschott sealing 1 Fire damper 2 Short extension duct 3 Flexible connector 4 C shaped profile 36 x 36 x 2 5 mm e g W rth or M pro or Hilti or eq...

Страница 11: ...ng 200 75 No Floor EI 180 S Installation within floor Mortar sealing 200 75 No EI 120 S Installation within floor Mortar sealing 200 75 No EI 90 S Installation within floor Mortar sealing 200 75 No Th...

Страница 12: ...tained as well as the correlation between wall floor used for the test and wall floor used for the actual installation The test results obtained on a type of wall floor are valid also for walls floor...

Страница 13: ...al walls Shaft wall The following indications are given for the installation walls U shaped horizontal metal frame minimum width 50 mm and C shaped vertical frame minimum width 49 mm made from sheet m...

Страница 14: ...and in the drawing Fire resistance classification Hole size D1 x D2 mm Damper protrusion from the wall E mm Wall minimum thickness S mm Sealing EI 120 S Installation within vertical rigid wall Wall mi...

Страница 15: ...opening must be provided in the wall as indicated in the table and in the drawing In case of paired installation refer to the section Fire dampers pairing for further information Damper positioning P...

Страница 16: ...B 90 x H 90 185 100 Mortar sealing EI 120 S Installation within floor Floor minimum density 650 kg m EI 120 S 500 Pa From B 70 x H 70 to B 90 x H 90 170 150 Mortar sealing EI 180 S Installation withi...

Страница 17: ...le height see table above E Damper protrusion from the wall see table above 1 Rock wool panel 50 mm thick with 140 kg m density 2 PROMASTOP E PASTE or HILTI CFS S ACR type sealant 3 PROMASTOP E PASTE...

Страница 18: ...aded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the wall and the damper using mortar suit able f...

Страница 19: ...shaped steel profiles 10x41x41x41x10 mm 2 M10 threaded rods 4 M10 nuts Position the threaded rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of th...

Страница 20: ...d rods 135 mm from the connection between fire damper and duct and at a distance of 50 mm from the side of the damper Filling Fill the space between the damper and the wall using Fire Batt Weichschott...

Страница 21: ...loor as indicated in the drawing The hanging structure is composed by 4 Angle connectors 105x105x90 mm Screws M8 x 40 mm Washers 15 x 9 mm Flush anchors M8 x 40 mm Filling Fill the space between the f...

Страница 22: ...rts characteristics for further information Comply with the minimum distances indicated on section Minimum distances Wall opening A opening must be provided in the wall as indicated in the table and i...

Страница 23: ...lasterboard infill panel thickness 20 mm 3 Mortar M 10 EN998 2 or plaster putty 4 Metal frame 5 Self drilling screw 3 5 X 70 mm D1 Hole base see table above D2 Hole height see table above E Damper pro...

Отзывы:

Похожие инструкции для RECTANGULAR Series