INSTALLATION
SITING
The installer must ensure that all regulations are met and that there is an unobstructed
minimum distance of 400mm from the top of the flue to the ceiling, which must be of non-
combustible material.
The appliance should be installed on a level surface ensuring the unit is stable and firmly
located. It should be well lit, draught free and positioned to minimise the possibility of
accidental touching.
Any partitions, walls or kitchen furniture in close proximity must be of non-combustible
materials and not be closer than 100mm from the sides and rear. A minimum clear space
of 600mm to the front to allow for safe operation.
WATER SUPPLY AND CONNECTION
Install in accordance with BS EN 1717 and the National Water Regulations in Use.
Connection is at the rear of the unit via a 15mm compression fitting with check valve.
When making the connection to the appliance an isolating cock should be fitted into the
supply line close to the unit, for emergency shutdown or servicing purposes.
It is recommended that the overflow pipe at the rear of the unit be connected to a drain.
GAS SUPPLY AND CONNECTION
Connection is at the rear of the unit via a 1/2" G male thread.
Connection shall comply with local regulations. The gas supply hose or tubing should be
periodically examined and replaced as necessary.
When making the connection to the appliance an isolating cock should be fitted into the
supply line close to the unit, for emergency shutdown or servicing purposes.
1 OF 1
GAS 1/2" BSPT
WATER INLET
15mm COMPRESSION
OVERFLOW
PIPE - 15mm
Fig. 1