In the “Modbus configuration” section of the screen you can set up the communication parameters of the
actuator.
• ”Address” is from the factory set to 247. Remember that each unit must have its own unique
address. Do not use 247 or 0 as an address. It is possible to avoid upload/download of the address value by
unchecking the “Include Address” box.
• “Baudrate”, “parity”, “stop bits” has to be set to specified, common values across the MODBUS
system. No-parity requires 2 stop bits.
• “Modbus response delay” is used in cases where the MODBUS master is unable to pickup too
fast responses from the slave. In case of communication problems you can increase this value.
In the “Actuator configuration” section of the screen you can set up some basic parameter values.
• “Ref pos 1 – 4” are used to define 4 different set points as you prefer. This could e.g. be a safe
position in case of storm, or maintenance position for cleaning etc.
• “Current limit” can be set in both directions. On the “Manual run” tab it is possible to see the
max current measured in running mode; then you can set the current limit according to the
measured max current.
• “Max speed” may be specified from 10 - 100%.