Adjusting the Orifices Plate Gap Setting (Split Head Design)
Figure 3: Gas Manifold
1
2
4
5
6
7
8
3
1. Primary Air Tube
2. Gas Manifold
4. 3 ea. Jam Screw / Washer
3. 3 ea. Gap Adjusting Screw
8. Adjustible Orifice Plate
7. 3 ea. Diffuser Fastening Screw
6. Diffuser Plate
5. 3 ea. Diffuser Spacer
Figure 4: Pilot Injector
Diffuser Face
1/ 8" (3mm)
Pilot Injector Disc
Pilot Injector Body
Set Screw
Pilot Gas Supply Line
To alter the orifice plate gap setting, the gas manifold (item 2) must first be removed from the burner. To do
this, follow the procedure outlined on the previous page. Once the gas manifold has been removed, the
diffuser (item 6) must be removed. Once removed, the service person has access to the adjustable orifice
plate (item 8).
Step 1: If the burner is equipped with a proven gas pilot (Lc21-310), the pilot injector disc must be removed.
Loosen set screw to allow for removal of the pilot injector disc assembly (figure 4).
Step 2: Remove 3 ea. Diffuser fastening screws (item 7) and diffuser stand off pillars (item5).
Step 3: Loosen 3 ea. Jam screw/washer (item 4) on the orifice plate.
Step 4: To DECREASE the gap setting, rotate the gap adjusting screw (item 3) clockwise as illustrated in
Figure 5 on the next page. To INCREASE the gap, rotate counter-clockwise. Using a measuring scale or gap
gauge, adjust all three screws so that the gap setting is equally maintained around the circumference of the
assembly. The orifice plate is free to slide along the primary air tube (item 1).
(Instructions continue on next page.)
Содержание LC Series
Страница 3: ...Section 1 Legal statements and Disclaimers Burner assembly area ...
Страница 7: ...Section 2 Burner Technical Data Gas flame firing at 12 300 000 btu hr ...
Страница 9: ...Section 3 Component Information General assembled burner ...
Страница 11: ...Section 4 Gas Manifold assembly Split gas head assembly ...
Страница 16: ...Section 5 Oil Gun assembly Oil nozzle and lance assembly ...
Страница 19: ...Section 6 Electrode settings Pilot injector and ignition setup ...
Страница 22: ...Section 7 Burner Installation Limpsfield LC9 dual fuel burners on Hurst boilers ...
Страница 24: ...Sample Typical fire tube installation ...
Страница 25: ...Typical water tube installation ...
Страница 29: ...Section 8 Typical Gas control Train 2 gas control train assembled ...
Страница 32: ...Section 9 Typical Oil Train Assembled oil pump with filter ...
Страница 36: ...Section 10 General start up procedure ...
Страница 43: ...Section 11 Service Recommendations ...
Страница 47: ...Section 12 General Burner Servicing Procedure ...
Страница 52: ...Section 13 Fault Finding ...