AURORA SE POWER BEST PRACTICES
Power Requirements
• Aurora SE requires a maximum of 1.5 A @ 120 VAC
• NDB Power requirements vary for each installation
Power and Data considerations for installations
• Make sure that your installation’s lights will draw no more than 75% of the
NDB Power Supply’s rated output current.
• Power Top-Ups supply 5A at 12V
• Inject power every 100’ or 100 LED pixels—whichever comes first
• Inject power every 80’ or 80 LED pixels for Triklit-style lights—whichever
comes first.
• At 2.5 A a 10’ leader cable drop approximately 0.5V.
• Power Top-Ups must be used with Power Ts to isolate power in each
direction.
• Cable runs greater than 15’ must use a Smart Extender/Receiver to maintain
control signal integrity.
• Use a voltmeter to measure the voltage at the end of each light run (see
voltage thresholds below)
End of Line Voltage Thresholds
VEOL > 10 V
VEOL > 9 V
Globes
All other fixture
End of line Voltage Threshold
Fixture Type
Measure End of Line Thresholds
Measure the end-of-line voltage to ensure light fixtures are receiving adequate
power.
v
10.312