4.1.2. Remove bushings from both sides of cable connector. Place them on mains cable and
luminaire cable.
4.1.3. Connect wires according to cable connector's electrical scheme. Maximal tightening torque
- 0.5 Nm. Assemble cable connector in reverse order. Bushings tightening torque - 2.5 Nm.
4.2. Connections inside luminaire:
4.2.1. Remove luminare's cover by releasing screws.
4.2.2. Strip mains cable (max 2.5 mm2). Put the cable through cable gland and lock it. The cable
gland allows round cable with external diameter 6-10 mm. Connect power wires to terminals
block according to polarity shown. To use DALI control, the control wires should be connected to
terminals DA without polarity order.
4.2.3. Replace luminaire's cover back and tighten the screws. Maximal tightening torque - 6 Nm.
31