8
(13)
inDOMO HP
- Platform lift
FINAL TESTS
IM.TEC.028.EN_rev.10.2
- November 2015
All rights reserved
2.19 OVERRUN CONTACT AND HEADROOM SPACER
Check the efficiency of the overrun contact / headroom spacer:
i.
send the car to the upper floor;
ii. Control the ascent of the car from the control panel till the overtravel contact takes action (proceed little by little:
when the lift does not respond to an external call, it means the overtravel contact is in action);
iii. from the car, measure the distance between the outer surface of the ceiling and the lowest surface of the shaft in the
headroom:
minimum300 mm
.
2.20 LANDING DOOR LOCKS
Check the landing door locks.
i. when the car is not on the floor level, check that all the landing doors are locked correctly.
ii. standing inside the car (in case of a doorless car) and facing a closed landing door, verify that the lock lever cannot be
manually pulled up.
2.21 DISTANCES FROM THE ENTRANCE
Verify the maximum didtance between the shaft and the car entrances:
i.
measure the distance between the car entrance frame (doorstep, returns, main beam), the door and the shaft wall
in front of the entrance;
ii. CAR WITHOUT DOORS
the distance between the shaft and the entrances must be max 20 mm (valid for the full travel height).
ii. CAR WITH DOORS
the horizontal distance between the car and the landing doorsteps must be ≤ 35 mm
.
2.22 CAR LEVELLING DISTANCE
Make sure that the car is positioned within the door unblocking area:
i.
go to the upper floor;
ii. make several attempts: execute a short descent and release the button until the car reaches the minimum distance
from the stop, and the levelling starts; measure the gap (minimum 20 m
m
);
iii. make several attempts: execute a short descent, then release the button, until the car reaches the maximum distance
from the floor within the levelling zone; measure the gap (
maximum 20 mm
);
iv. repeat for each of the intermediate stops;
v. the levelling must function in an area b30 mm and -30 mm in relation to each landing level;
vi. the maximum acceptable gap after the levelling stop is equal to 20 mm above or under the landing level.
2.23 CAR LEVELLING
Make sure that the car levelling is efficient with doors open:
i.
go to the upper floor, with another persone operating from the machine room;
ii. keep the landing door open;
iii. go downwards, pressing the emergency descent button;
iv.
the levelling will be active with the door open
.