15 

Installation and Operation of Wireless 20/40/60 Minute Timer:  99-DET02

BC04 
Control

NOTE:

  Your  

control may look 
different than the 
one shown.

Press Simultaneously 
to Initiate Pairing Mode

Figure A 

Figure D 

NOTE

Th

e

  wireless  Timer

s and Repeaters

  must  be  matched  to 

the  main wall control of the HRV / ERV.  This process is 

called "Pairing".  Multiple Timers 

and Repeaters 

can be 

paired to a single wall control.

Figure B

1/8 in hole for 

screw and 

anchor 

1/8 in hole 

for screw and 

anchor 

Break off tab

Alternate Wall Mount

1/8 in hole for 

screw and anchor 

Figure C

Back Plate 

Face Plate 

1/8 in 

hole for 

screw and 

anchor

Break off tab

Figure F 

Figure E

Press Simultaneously 
to Initiate Pairing 
Mode

DXPL02 

Control

DET02 Timer

20/40/60 Minute 
Status Lights 

Select  Button  initiates 

high  speed  ventilation 

for 20, 40 or 60 min. 

Battery Indicator

Removable 

Backplate

The Timers may be installed onto a flush mounted electrical 

switch box or it may be surface mounted onto a wall. Multiple 

Timers may be installed in a ventilation system.  To increase 

the range of a wireless Timer, a RX02 Repeater should be used.

Pairing:

To pair additional DET02 Timers with the same wall control, or 

if  pairing  was  not  successful,  repeat  steps  1-6. 
When paired, the DET02 Timers can be moved and installed 

elsewhere.  Estimated range of the Timer is 40’ with no 

obstructions.  A RX02 Repeater may be installed to increase the 

range of the Timers.
Test if pairing was successful by pressing the Select Button and 

listen for the HRV / ERV to initiate HIGH fan speed Ventilation.

Un-pairing: 

1. Turn on the main wall control by pressing the ON/OFF

button     and remove the battery from Timer.

2.

DET02 with DXPL02 Controls:

   Press the left and right

buttons simultaneously on the main wall control

(    and RESET buttons).  The screen will go blank and the

wireless symbol     will appear flashing on the bottom right

of the display.  This indicates that the main control is now in

pairing mode.  (Figure D)

3.

DET02 with BC04 Control:

   Press the left and right

buttons simultaneously on the main wall control (    and

buttons).  The bottom row of 3 LED's will begin flashing.

This indicates that the main control is now in pairing mode.

(Figure E)

4. Keep the Timer within 16” of the main wall control when

pairing.

5. Install the battery in the DET02 Timer.  All four lights on

the Timer will immediately flash 5 times, then only the red

battery light will remain on for approximately 12 seconds

after which the "40" light flashes the rev code.  20, 40, 60

lights will flash until paired  or will stop if not paired within

12 seconds.  If pairing was not successful you now must

return to step 1 to restart the pairing process.

6. Press the     button on the main wall control to exit pairing

mode when Timers have been successfully paired.

1. Remove the battery from the back of the DET02 Timer
2. Press and hold the Select Button on the front of the Timer
3. While holding the Select Button, reinsert the battery in the

Timer.  Continue holding the select button until the LED

under "40" begins flashing.  The DET02 Timer will now be

unpaired with the main wall control.

Installation:

1. Separate the face plate from the back plate by firmly

pulling apart (Figure A).

2. For mounting the control without a Decora plate, break off top and bottom tabs and refer to Figure C for mounting.

3

.

Place the back plate of the control in the desired location on the wall and pencil mark the top and bottom screw    holes

(Figure B or C).  Drill two 1/8" holes.

4. Attach the back plate to the wall using the 2 supplied screws and anchors.

5. Attach the face plate to the back plate (Figure A).

Содержание Pure Performance 120ERV

Страница 1: ...511 McCormick Blvd London ON Canada N5W 4C8 General Info Tech Support 1 855 247 4200 Online www lifebreath com ERV SERIES INSTALLATION GUIDE 69 ERV INSTALL 072717...

Страница 2: ...r a mechanical room or an area close to the outside wall within close proximity to where the weatherhoods are mounted If a basement area is inconvenient or non existent install the unit in a utility r...

Страница 3: ...urther wiring have a licensed electrician make all of the electrical connections The recommended circuit is a separate 15 A 120 V circuit Attention Before installation careful consideration must be gi...

Страница 4: ...side Dampers for balancing air flows if not in collars of unit Spring Loaded Backdraft Damper Recommended There is a location for an optional Backdraft Damper with the leaf hinge vertical The damper i...

Страница 5: ...cing air flows if not in collars of unit Exhaust Air from different areas of the home bathrooms kitchen Spring Loaded Backdraft Damper Recommended There is a location for an optional Backdraft Damper...

Страница 6: ...as bedrooms livingroom recreation room etc Stale Air to Outside Fresh Air from Outside Dampers for balancing air flows if not in collars of unit Stale Air from various areas of the home bathrooms kitc...

Страница 7: ...nd right sides of the unit at the front and back 2 Using a flat pan head screwdriver bend out the four tabs to approximately 45o 3 Once the tabs have been all bent outwards insert the S hooks through...

Страница 8: ...and washers not included through the hanging strap grommets and fasten to the joists Figure A Step 4 Level the unit from right to left to right and front to back Adjust the unit up by pulling down ve...

Страница 9: ...he unit to balance the amount of stale air being exhausted with the amount of fresh air being brought into the house Refer to airflow balancing section The Lifebreath Kitchen Grille includes a removab...

Страница 10: ...have access to attach the retaining ring Available size 6 in Connect to ERV ducting Ceiling Fitting Retaining ring Flush mount the lip of the ceiling fitting to ceiling TechGrille Ceiling Quick Mount...

Страница 11: ...e to minimize air flow restrictions Twisting or folding the duct will severely restrict airflow Hard rigid ducting which has been sealed and insulated should be used for runs over 10 ft 3 3 m Refer to...

Страница 12: ...ntion Caution Dual Hood Part 99 190 With the Lifebreath Dual Hood only one 6 in hole is required in the exterior wall to complete two connections fresh air intake and stale air exhaust 13 Top View 8 2...

Страница 13: ...s Drill two 1 8 in holes for the screws and wall anchors Figure D E or F For DXPL02 control vent openings clear Figure D drill a 1 in hole in the center Figure D For BC04 control cut in a 3 4 in by 1...

Страница 14: ...lable on some models I Continuous Ventilation This mode of operation provides continuous ventilation within the home You may for example select Continuous Ventilation at low speed for normal operation...

Страница 15: ...the left and right buttons simultaneously on the main wall control and RESET buttons The screen will go blank and the wireless symbol will appear flashing on the bottom right of the display This indi...

Страница 16: ...epeater initially for pairing 4 Plug the RX02 Repeater into the power outlet The green light will flash after approximately 12 seconds indicating that the repeater is paired with the main wall control...

Страница 17: ...tandby off by adding a jumper on the terminal block between 2 ON and 3 RED Standby can also be achieved by setting the main control to the ON position and selecting speed 0 Timers and or additional co...

Страница 18: ...lect Button is pressed during lockout mode the Light will momentarily illuminate but no override will be initiated Status Lights Select Button initiates high speed ventilation for 20 40 0r 60 min Yell...

Страница 19: ...is recommended for servicing unit All ducts use 5 in 125 mm connections 16 1 2 in 419 mm Core Balancing Damper 9 1 4 in 235 mm 18 1 4 in 464 mm 17 1 4 in 438 mm 22 3 4 in 578 mm 14 in 356 mm Front Vie...

Страница 20: ...g unit All ducts use 6 in 152 mm round collars balancing dampers are located on two collars Recirculating Damper For 230ERVR Model Only Balancing Dampers Dimensional Drawing for 30ERV Model Front View...

Страница 21: ...t properly balanced the following issues may occur A positive or negative pressure in the house ERV not operate at its maximum efficiency The unit not defrost properly Airflow Measuring Gauge A digita...

Страница 22: ...d Rigid Ducting Insulated flexible ducting Installations where the ERV is ducted directly to the return of a furnace may require additional dampening on the fresh air to building duct This is due to t...

Страница 23: ...ube with the tip facing towards the air stream in the stale air from Building air stream Move the pitot tube around in the duct facing toward the airflow and take an average reading Record the reading...

Страница 24: ...peed of the ERV have contractor balance ERV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the o...

Страница 25: ...en tres r glage trop haut du d shumidistat VRE pas assez puissant pour un hot tub une piscine int rieure etc mode de vie des occupants humidit qui p n tre dans la maison en provenance d un espace sani...

Страница 26: ...pour r duire le d bit du conduit o la v locit est la plus haute R p tez les tapes 2 et 3 jusqu ce que vous obteniez des lectures identiques dans les deux conduits tape 4 b Une fois l quilibrage termin...

Страница 27: ...t dans la canalisation qui a le plus grand d bit d air pour qu il soit gal au plus faible d bit Consultez les m thodes d quilibrage des d bits d air qui sont propos es dans ce manuel Tous les autres a...

Страница 28: ...ube de Pitot le poste de mesure du d bit et la sonde de mesure du d bit La Figure B fait voir un manom tre num rique avec un tube de Pitot Cet ensemble permet de mesurer avec pr cision la pression due...

Страница 29: ...sser un d gagement de 25 po 635 mm l avant pour faciliter l entretien de l appareil Tous les conduits utilisent un collier de 6 po 152 mm Il y a un registre d quilibrage sur chacun des quatre colliers...

Страница 30: ...Air vici de l int rieur Turbine motoris e Noyau r cup rateur de chaleur amovible Registre de d givrage par recirculation pour seulement 130ERVR Filtres N B On conseille de laisser un d gagement de 25...

Страница 31: ...sse s allume momentan ment mais aucun changement prioritaire n est actionn Installation et utilisation de la minuterie pour 20 40 60 minutes 99 DET01 Voyant de haute vitesse Bouton s lecteur pour acti...

Страница 32: ...odifi et remplac par arr t en attente off en ajoutant un cavalier sur le bloc de connexions entre les bornes 2 ON marche et 3 RED rouge On peut aussi atteindre le mode en attente Standby en r glant la...

Страница 33: ...rayon de 16 po de la commande principale S il n y a pas de prise courant proximit utilisez une rallonge pour alimenter le r p teur pr s de la commande principale 4 Branchez le r p teur RX02 dans la pr...

Страница 34: ...e inf rieure des 3 t moins DEL commence clignoter Cela indique que la commande principale se trouve alors en mode de pairage figure E Lors du pairage gardez la minuterie dans un rayon de 16 po de la...

Страница 35: ...minutes de marche 40 minutes de recirculation Ce mode de fonctionnement donne 20 minutes de ventilation avec de l air neuf et 40 minutes d air recircul c est dire recycl Toutefois ce mode n est pas di...

Страница 36: ...rquez le trou pour le fil au centre entre les trous de vis Reportez vous la figure D E ou F pour les dimensions 6 Percez 2 trous de 1 8 po pour les vis et chevilles figure D E ou F Dans le cas d une c...

Страница 37: ...N 99 190 Avec le capuchon double Lifebreath il suffit de percer un seul trou de 6 pouces dans le mur ext rieur pour effectuer deux raccordements un pour l arriv e de l air neuf et l autre pour l vacu...

Страница 38: ...rieurs au VRE devrait tre bien tir e et aussi courte que possible Quand le conduit est tortill ou pli la circulation de l air est s rieusement limit e Pour les longueurs de plus de 10 pieds 3 3 m tres...

Страница 39: ...ntage rapide sur le montant TechGrille Rev tement de 1 2 po Raccord montage rapide Coude pour sommet de canalisation Pi ce N 99 WF6 Utilisez ce raccord avant la pose du rev tement mural int rieur Ce r...

Страница 40: ...ini re Des registres d quilibrage fournis sur place devraient tre pos s l ext rieur du ventilateur pour quilibrer l vacuation d air vici de la maison et l adduction d air neuf dans la maison Voyez la...

Страница 41: ...issez les quatre 4 vis m taux qui se trouvent sur la partie sup rieure de l appareil Attachez les crochets en S et r ins rez les vis m taux Figure B D TAIL Remarque Cette illustration de l appareil po...

Страница 42: ...c t s gauche et droit de l appareil l avant et l arri re 2 l aide d un tournevis plat inclinez les 4 languettes environ 45o vers l ext rieur 3 Une fois les languettes inclin es ins rez les crochets en...

Страница 43: ...e 6 Air vici provenant de diverses pi ces de la maison comme par exemple les salles de bains au besoin la cuisine au besoin Air neuf achemin vers les principales surfaces habit es chambres coucher sal...

Страница 44: ...l air vici vers l ext rieur 5 RACCORDEMENTS DIRECTS DU CIRCUIT DE DISTRIBUTION D AIR DU VRE ET DU CIRCUIT D AIR VACU LA REPRISE D AIR FROID DE LA FOURNAISE Air repris Air vici vers l ext rieur Retour...

Страница 45: ...reprise Registre antiretour avec charni re lamelle en position verticale recommand 4 Air repris RACCORDEMENTS DIRECTS DU CIRCUIT DE DISTRIBUTION D AIR DU VRE ET DU CIRCUIT D AIR VACU LA REPRISE D AIR...

Страница 46: ...comp tent le soin de faire toutes les connexions lectriques On recommande d employer un circuit distinct de 120 volts 15 amp res Attention Avant de proc der l installation il faut bien tenir compte d...

Страница 47: ...niques ou dans un endroit pr s du mur ext rieur sur lequel on posera les capuchons anti intemp ries Si la maison n a pas de sous sol ou s il ne convient pas ce genre d installation vous pouvez install...

Страница 48: ...511 boul McCormick London ON Canada N5W 4C8 Information g n rale support technique 1 855 247 4200 En ligne www lifebreath com S RIE VRC GUIDE D INSTALLATION 69 ERV INSTALL 072717...

Отзывы: