TFP Connected to Heat Recovery Ventilator
Location

The TFP should be located in the main trunk of the fresh air to

house line, after the Heat Recovery Ventilator (HRV) and before

any branch lines. (Fig. 3)

Mounting

1. Locate mounting bolts (4) on side of TFP cabinet for vertical

hanging (Fig. 3) and remove.

2. Measure distance between the bolts and mark it on the

floor/header joist where the TFP is to be hung.

3. Fasten hanging straps to floor joists using wide head nails or

screws with washers.

4. Insert hanging bolts through prepunched holes in straps and lift

TFP into position. Tighten and secure bolts.

Ducting

1. Install (2) 7” collars (provided) on TFP cabinet with (8)

8/32” X 3/8” sheet metal screws provided.

2. The ducting between the TFP and the HRV, and between the

TFP and the main supply trunk line to the house, should be

kept as straight as possible.

3. A relief opening or breathing T is required to prevent pressure

differences.

4. A short piece (1-2 foot) of flexible ducting should be used on

both sides of the TFP (Fig. 3). This will reduce vibration and

noise transfer if present.

NOTE: Please refer to the HRV installation manual for proper

ducting of that appliance.

Breathing T

The “Breathing T” is designed to assist in neutralizing pressure

differences which can occur between the HRV and the TFP when

joined together. The “Breathing T” should be situated in an area

with suitable indoor air quality (IAQ). Avoid mechanical rooms

and workshops. If required, an external connection should be made

from the “Breathing T” to an area with suitable IAQ (the air

should be free of fumes, vapors, odors, or large airborne particles

etc.).

The room in which the “breathing T” is open 
should be free of combustion equipment such as 
gas hot water tanks and furnaces.  If the “T” 
must be exposed in these areas, a pressure test  
(spillage or backdraft test) should be conducted 
on the combustion equipment after everything is 
installed.

CAUTION

TYPE 2 INSTALLATION

To a Fully Dedicated HRV System

Breather Tube

(Standard 

Galvanized

"Tee" Fitting)

Fresh Air 

to House

Fresh Air 

to House

Stale Air

from house

Air

Cleaner

HRV/ERV

Breather 

Tee

Outdoors

Figure 3

Содержание Lifebreath TFP3000

Страница 1: ... up 11 Medical prescription 11 Wiring Diagram 12 Table of Contents TFP 3000 0108 LEAVE MANUAL FOR HOMEOWNER NOTE Due to ongoing research and product development specifications ratings and dimensions are subject to change without notice Models TFP3000 TFPC3000 TFP3000HEPA TFPC3000HEPA Operation and Installation Manual Exhaust Air Supply Air Console Portable Models TFPC3000 and TFPC3000HEPA Whole Ho...

Страница 2: ...unting pads for TFPC to stand on Exhaust Air Supply Air Model TFPC3000HEPA HEPA Filter TFP Collector T Replace collector annually Replace collector every 3 years Due to the performance characteristics of the TFP collector the Hepa filter only needs to be replaced every 3 years CONSOLE MODEL 60 TFPC 3000 CAUTION ATTENTION BLUE BLACK BLACK BLACK G Neutral WHITE Line BLACK Ground GREEN HIGH SPEED OFF...

Страница 3: ...ust another filter Airia Energy Systems hold the patent for this TFP technology The TFP series are the only one of its kind How much maintenance is involved How often do the filters need to be replaced As tested under average household dust loading the TFP should be inspected annually Typically the primary collector should be replaced annually and the secondary collector should be replaced every 2...

Страница 4: ...ommended Case Twenty gauge prepainted galvanized steel G60 for superior corrosion resistance Weight 55 lbs 24 4 Kgs Electrical Codes Conforms to CSA and UL standards Mounting the Wholehouse TFP very flexible a Mount to the furnace return b Mount between the HRV and the furnace c Hang from a joist and duct to the furnace d Stand alone installation Warranty Units carry a five year warranty on all re...

Страница 5: ...ning and replacement Annual inspection recommended Case Twenty gauge prepainted galvanized steel G60 for superior corrosion resistance Weight 55 lbs 24 4 Kgs Electrical Codes Conforms to CSA and UL standards Mounting the Wholehouse TFP very flexible a Mount to the furnace return b Mount between the HRV and the furnace c Hang from a joist and duct to the furnace d Stand alone installation Warranty ...

Страница 6: ... 8 32 X 3 4 mounting screws provided through the brackets and into position Tighten and secure 7 TFP should now sit securely against the plenum with the foam in between 8 Cut 2 7 holes in the return air plenum Install ducting to join TFP to the return air plenum Fig 2 NOTE Do not support the weight of the TFP on the duct Duct must be open and not pinched NOTE Due to possible noise transfer through...

Страница 7: ...ith the TFP is acceptable Consult a certified electrician ATTENTION TYPE 1 INSTALLATION Option C Vertical Design Use Option B when Option A is not practical For cedAir Fur nace Return Air Supply Air Air Cleaner The furnace fan and or HRV must operate continuously for Type 1 and Type 2 installations If they do not operate continuously then interlocking them electrically with the TFP is acceptable C...

Страница 8: ...xible ducting should be used on both sides of the TFP Fig 3 This will reduce vibration and noise transfer if present NOTE Please refer to the HRV installation manual for proper ducting of that appliance Breathing T The Breathing T is designed to assist in neutralizing pressure differences which can occur between the HRV and the TFP when joined together The Breathing T should be situated in an area...

Страница 9: ...ler than the size of the port collars 7 on the TFP 4 Ductwork should be kept as short and straight as possible to allow for good air circulation Note For installations of more than one return or supply greater than 5 e s p it is often necessary to add an in line fan to the system as a booster TYPE 3 INSTALLATION Independent Duct System No HRV This installation configuration is recommended for home...

Страница 10: ...10 Épurateur d air Bureau ou salle de classe Espace climatisé Air Cleaner TYPE 3 INSTALLATION Alternative Applications Office or Classroom Application Work Table Application ...

Страница 11: ...replacing the collectors make sure the directional arrows are noted and the collectors are installed correctly Close the door and restart TFP furnace and HRV fan When your TFP is installed with a forced air heating system you are still required to use the recommended furnace filter This may be a good time to inspect this filter as well When new collectors are required call your dealer Model TFP300...

Страница 12: ...d GREEN HIGH SPEED OFF LOW SPEED DEFOND SWITCH 120 VAC 60 Hz FAN MOTOR 1 2 3 TRANSFORMER TERMINAL BLOCK BLACK WHITE BLUE WHITE BLUE BLACK BLACK BLUE RED WHITE RED G GREEN YELLOW 370V 50 60HZ CAPACITOR 10UF DOOR SWITCH RED RED BROWN CAUTION ATTENTION info lifebreath com 12 ...

Отзывы: