![Lifebreath CAF-D-L4A-36-P16 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/lifebreath/caf-d-l4a-36-p16/caf-d-l4a-36-p16_operation-sizing-and-installation-manual_1909141039.webp)
39
Top
Side
22.25"
(565 mm)
Supply Air
Ventilation
Supply Air
Inlet
Ventilation
Exhaust Air
Outlet
Return Air
Blower Section
(SERVICE CLEARANCE 1')
(SERVICE CLEARANCE 3')
Front
Latches
29.5"
(749 mm)
19"
(483 mm)
47.5"
(1207 mm)
6"
14"
(356 mm)
12"
(305 mm)
4”
(100 mm)
19”
(483 mm)
17.25”
(438 mm)
22”
(559 mm)
(150 mm)
6"
(150 mm)
29.5"
(749 mm)
OPTIONAL
99-186
Weatherhoods, Two - 6" (150 mm) c/w 1/4" (6 mm) mesh
screen
99-RSK6
6” (150 mm) back draft damper
99-DH-01 Lifestyle Dehumidistat
- Initiates high speed ventila-
tion for 20, 40, or 60 minutes (3 wire) 20 gauge wire (minimum)
100 ft. length
OPTIONAL TIMERS
99-DET01 Lifestyle 20/40/60 Minute Timer
- Initiates high speed
ventilation for 20, 40, 60 minutes. (3 wire) 20 gauge wire
(minimum) 100 ft. length
99- 20M01 Lifestyle 20 Minute Timer
- Initiates high speed
ventilation for 20 minutes. (3 wire) 20 gauge wire (minimum)
100 ft. length.
Core
Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).
Filters
Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.
Case
Pre-painted galvanized steel for superior corrosion resistance.
Dimensions & Clearances
Model
CAF-U-00-48-P16
Voltage
120 VAC 60 Hz
Hp
1/2
Amps (total)
10.6
*
Airflow (High)
.25 in wg
1888 CFM
.5 in. wg
1589 CFM
Ventilation
100 - 140 CFM
Airflow
Effectiveness
70%
(Aluminum Core)
Total Efficiency
50%
(Enthalpic Core)
Net Weight
132 lbs.
Shipping Weight
147 lbs.
* Airflow performance assumes an evaporator
coil static pressure loss of .25”WC.
Warranty
Units carry a lifetime warranty on the heat recovery (aluminum) core, a five year warranty on the energy recovery
(enthalpic) core and a five year replacement parts warranty on all other components.
Note: Ventilation ports and return plenum
opening available off either side of cabinet.
All units conform to CSA and UL Standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
Model CAF-U-00-48-P16
Static Pressure
Fan Speed (cfm)
Low
M Low
M High
High
0.5 “ WC
690
1033
1469
1589
0.25 “ WC
806
1134
1650
1888