background image

 

www.lifebreath.com

 

 

 

 26

 

17

 

S

ERVICE AND 

M

AINTENANCE

 

Filters 

Open front service door to access the filters located in both supply and exhaust air streams. Note to remove 

and install filters, it may be easier to first remove the core(s). Refer t

Core

. 

 

The filters are designed to stop large particles from entering in the core. The filters are fastened in place by a 

metal spring rod. To remove filters from core(s) simply pull the rod from one end, outward until free from core 

lip, and remove. 

 

Only use cold water with a mild detergent to wash the filters. Do not wring out or use harsh chemicals. The 

time between filter service will depend on the application the HRV has been installed in. It can be as often as 

one - two months or at the very least, cleaned every six months. 

 

Condensate Drains 

The condensate drain consists of one drain pan, which may collect water after the HRV initiates a defrost 
cycle, and a drain line to remove the condensate.  

 

Maintenance on this portion of the system should be done as often as possible and should not exceed six 

months. Note bacterial growth in standing water is a major concern to healthy indoor air quality, and should 

be avoided whenever possible. 

 

To clean these components, open the front service door and flush the pans with water. Ensure that the pans 

drain completely and in a reasonable amount of time. Note if the water does not drain right away, check for 

blockage in the drain line, also check that the drain line has a good slope to it. (1/8 - 

1/4” per foot)

 

The drain line itself should have a “P” trap in it below the HRV which is to be filled with water to prevent odors 

or gases from entering back into the unit. 

 

Duct Work 

It is a good idea to inspect ducting, outside weatherhoods (wall caps), and grilles for blockage and dirt 

buildup, at least every six months. 

 

Outside weatherhoods should be protected by a bird screen which can plug up with debris. Also, it is a good 

idea to visually confirm that the fresh air supply is free from any sources of contamination, such as other 

vented combustion equipment added after the fact. 

 

Damper Motor 

The damper motor, (if applicable) is a self-contained motor and does not require service. The damper door 

attached to the motor could use a little lithium grease on the shaft opposite the motor, where it enters its 

holder, once every two to three years. 

 

General Maintenance 

As a final step in a routine maintenance schedule, it is a good idea to confirm operation of the system, 

checking speed control functions and remote control operation, if applicable. Wipe the inside of the cabinet to 

remove dust and cobwebs as needed. It is a good idea to keep a service/maintenance log of the unit. 

 

 

 

 

Содержание 350 DGS

Страница 1: ...A 120 V circuit Caution Before installation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air...

Страница 2: ...the balancing procedure found in this manual Never install a ventilator in a situation where its normal operation lack of operation or partial failure may result in the back drafting or improper func...

Страница 3: ...7 Location Notes 10 8 The Duct Work System 11 9 The Integrated HVAC System 12 9 Stale Air Return and Fresh Air Supply System 14 10 Weatherhoods 15 11 Drain Connections 16 12 Main Control Installation...

Страница 4: ...or humidity during the cooler winter months of the year by exchanging the humid indoor air with the dryer air from outside Automatically cycles through its defrost mode when temperatures drop below fr...

Страница 5: ...ou can use this ventilation mode at low speed for low household activity levels or when the home is unoccupied 4 10 Minutes On 50 Minutes Standby This mode of operation provides 10 minutes of ventilat...

Страница 6: ...revert to its previous setting The Dehumidistat function should be set to off for all seasons except the heating season because a dehumidifying effect occurs only when the outdoor air is dryer than t...

Страница 7: ...required by a remote timer if installed 20 40 60 High Speed Button Press the 20 40 60 High Speed Button to temporarily initiate HIGH Fan Speed for 20 40 or 60 minutes Press one time for 20 minutes Pre...

Страница 8: ...GH Fan speed operation in Venitilation mode until the indoor humidity has been reduced below the set point Reset Button The RESET Button will clear the current Fan Timer Mode and Dehumidistat settings...

Страница 9: ...ted When the battery in the timer needs to be replaced the red LED Battery Indicator will illuminate When paired to the digital wall control the wireless timer may be moved to a remote location in the...

Страница 10: ...RV is recommended to service the heat exchanger cores and the filters The HRV may be mounted on an equipment platform providing the drain hoses are clear and there is enough space to open the doors fo...

Страница 11: ...noise galvanized metal ducts properly sized are recommended Keep ducting as short as possible and use a minimum of elbows and tees Connecting sections and shorter runs may be flexible ducting one size...

Страница 12: ...oves stale room air eg from lunch room storage or copy area and returns to the space an equal amount of fresh outdoor air making the use of an economizer obsolete in conjunction with an HRV Warning At...

Страница 13: ...ctly from the return air plenum to the HRV as it is drawn back to the air handler Fresh air supplied by the HRV is then introduced directly into the return air plenum but at a location closer to the a...

Страница 14: ...he air handlers return system if the static pressure of the return in the air handler exceeds 0 1 to 0 15 in w g A damper located just prior to the HRV is required to balance the stale air exhausted w...

Страница 15: ...cient cross section with an integral single piece vapor barrier should be used to connect the ERV to the weatherhoods A minimum R value of insulation should be equal to 4 RSI 0 75 A good bead of high...

Страница 16: ...Hand tighten the nut 3 Construct a P trap using 1 2 in drain hose not included Ensure that the loop is large enough to avoid kinks Secure it with a zip tie 4 Pour a cup of water into the drain pan of...

Страница 17: ...hole for the wires in between the two screw holes figure B 5 Drill two holes for the screws and wall anchors and drill one hole for the wires in between the two screw holes figure B 6 Pull the 3 wire...

Страница 18: ...must be interlocked to the furnace air handler with a Simplified Installation Return Return Method The HRV should be interlocked to the furnace air handler with a Partially Dedicated System Installati...

Страница 19: ...tion when activated Adding Dry Contact Controls A jumper must be placed between 2 ON and 3 RED terminals on the HRV terminal block to activate the HRV for timers and or dry contact controls or if inst...

Страница 20: ...ical Timers 99 101 Installation The Mechanical Timer is a 2 wire dry contact timer Connect a jumper wire between the 2 ON and 3 RED terminals on the terminal block and connect the two timer wires to t...

Страница 21: ...tes HIGH fan speed ventilation pairing was successful If the HRV does not initiate HIGH fan speed ventilation pairing was not successful Un pair the timer and return to step 1 of the pairing procedure...

Страница 22: ...needs to be moved closer to the main wall control Pairing 1 Turn on the main control by pressing the ON OFF button 2 DXPL02 control Press the left and right buttons simultaneously on the main control...

Страница 23: ...more accurate balance of the unit 2 Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances...

Страница 24: ...ft2 128 cfm For your convenience the cross sectional areas of some common duct sizes are listed below DUCT DIAM inches CROSS SECTION AREA sq ft 5 127 mm 0 14 6 152 mm 0 20 7 178 mm 0 27 The accuracy o...

Страница 25: ...resistance when sliding out Avoid tilting the core as this will result in its edges catching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent an...

Страница 26: ...ce door and flush the pans with water Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also che...

Страница 27: ...ed to run continuously to distribute ventilation air comfortably Dehumidistat is not operating Outdoor temperature is above 15 C 59 F Improper low voltage connection External low voltage is shortened...

Страница 28: ...ed on cores before unit initiates defrost cycle functions Have HVAC contractor balance the HRV Ensure damper defrost is operating during self test Condensation or ice buildup in insulated duct to the...

Страница 29: ...www lifebreath com 29 19 WIRING DIAGRAM 350DCS...

Страница 30: ...e neglect improper care or other failure by the owner to provide reasonable and necessary maintenance of the product any attempt at repair by an unauthorized service representative or not in accordanc...

Отзывы: