www.lifebreath.com
19
13
A
DDITIONAL
C
ONTROLS
Setting
“Standby” When Using the Main Control
The HRV will be “fully
-
off” when selected on the main control. Timers and/or other controls will not function
when the HRV is in off position.
The “fully
-
off” feature can be modified to “standby
-
off” by adding a jumper
on the HRV terminal block
between 2 (ON) and 3 (RED) terminals. “Standby” can also be achieved by setting the main control to the on
position and selecting speed 0. Timers and/or additional controls will initiate high speed ventilation when
activated.
Adding Dry Contact Controls
A jumper must be placed between 2 (ON) and 3 (RED) terminals on the HRV terminal block to activate the
HRV for timers and/or dry contact controls, or if installing the unit without a main control. Jumpers can be
added between terminals on the HRV terminal block for additional controls, per the table below:
Setting
Terminals
Low Speed Ventilation
2 (ON)
1 (LOW)
High Speed Ventilation
2 (ON)
6 (HI)
Dehumidistat
2 (ON)
10 (BLK)
Caution
•
Building codes in some areas require “fully
-
off” functionality. Check with your local building authority before
modifying the unit to “standby
-
off”. Unintentional operation of the HRV by the end user may occur if the unit
is modified from “fully
-
off” to “s
tandby-
off”.