9
P
F
Connecting
Optional
Control
- Part #
99-DH01
The
Lifebreath Dehumidistat
may be installed onto a
flush mounted 2" x 4" electrical switch box or it may be
surface mounted onto a wall.
Only 1 master control should be installed to a ventilation
system (the Face Plate on this illustration may not be
exactly the same as yours).
1. Remove the Operating Instructions Card from the
top of the Control (Figure A).
2. Separate the Face Plate from the Back Plate by
firmly pulling apart (Figure B). Be careful not to
damage Face Plate Contact Pins.
3. Place the Back Plate of the control in the desired
location on the wall and pencil mark the wall in
the center of the Wire Opening, Top Screw Hole
and Bottom Screw Hole (Figure C).
4. Remove the Back Plate and drill a 3/8" opening in
the wall to allow for the Wire Opening and a 1/8"
hole for the Wall Anchors for the top and bottom
screw holes (Figure D).
5. Pull 3/20 wire through the opening in the wall
and the Wire Opening of the Back Plate (Figure C).
6. Connect Red, Green and Yellow to the Wiring
Terminals located on the Back Plate (Figure C).
7. Secure a single wire to the Wire Retainer located
on the Back Plate (Figure C).
8. Attach the Back Plate to the wall using the 2
supplied screws and anchors.
9. Attach the Face Plate to the Back Plate (Figure
B). Note: Be careful to correctly align the Face
Plate to avoid damaging the Face Plate Contact
Pins.
10. Insert the Operating Instructions Card into the
control (Figure A).
11. Connect the 3 wire 20 gauge (min.) 100 ft length
(max.) to the digital controls terminal strip located
on the Aircom circuit board (Figure E).
%
80
20
HIGH
ATTENTION
Pay special attention not to damage the Contact
Pins when attaching and detaching the Face Plate.
(Figure B)
Figure
A
- Face
Plate
Operating
Instructions Card
Back
Plate
Figure B
Face Plate
Contact
Pins
Face
Plate
Separate the
Face Plate from
the Back Plate.
Side View
Figure
C
Front View of Back Plate
Wire
Opening
Wiring
Terminals
Wire
Retainer
TOP
Top Screw
Hole
Bottom
Screw Hole
Drill a 1/8” hole
for the Top Screw
and Anchor
Figure D
Drill holes in
wall
Drill a 3/8” hole
for the Wire
opening
Drill a 1/8” hole
for the Bottom
Screw and
Anchor
Wall Face
Dehumidistat Sensor
Openings to room
air allow accurate
sensor readings.
Figure F
Correct Installation
of Back Plate
Back
Plate
Face Plate
Contact
Pins
Face
Plate
RED
GRN
YEL
DET
Digital
Contr
ols
Figure
E
Terminal strip on
Aircom circuit
board
•
Yellow to YEL
•
Red to RED
•
Green to GRN
•
Use 3/20 wire
Содержание 1500E-ECM
Страница 24: ...24 Wiring Diagram Neutral Neutre CHASSIS T44 Line Ligne C3 C2 C1 ...
Страница 26: ...26 ...
Страница 27: ...27 ...
Страница 28: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 1500 110116 ...