Lifebreath 1500E-ECM Скачать руководство пользователя страница 23

23

It is necessary to have balanced air flows in an HRV. The volume of air 
brought in from the outside must equal the volume of air exhausted by 
the unit. If the air flows are not properly balanced, then;

The HRV may not operate at its maximum efficiency

A negative or positive air pressure may occur
in the building

The unit may not defrost properly

Failure to balance HRV properly may void warranty

Excessive

 

positive

 

pressure

  may  drive  moist  indoor  air  into  the 

external  walls  of  the  building  where  it  may  condense  (in  cold 
weather)  and  degrade  structural  components.  May  also  cause  key 
holes to freeze up.

Excessive

 

negative

 

pressure

  may  have  several  undesirable 

effects.  In  some  geographic  locations,  soil  gases  such  as  methane 
and  radon  gas  may  be  drawn  into  the  home  through 
basement/ground  contact  areas.  Excessive  negative  pressure  may 
also cause the backdrafting of vented combustion equipment.

Read

 

the

 

Application

 

Warning

 

on

 

the

 

front

 

of

 

this

 

manual!

Prior

 

to

 

balancing,

 

ensure

 

that:

1. All sealing of the ductwork system has been completed.
2. All of the HRV's components are in place and functioning properly.
3. Balancing dampers are fully open.
4. Unit is on HIGH speed.
5. Air flows  in branch lines to  specific  areas  of  the  house should be

adjusted  first  prior  to  balancing  the  unit.  A  smoke  pencil  used  at

the  grilles  is  a  good  indicator  of  each  branch  line's  relative  air

flow.

6. After  taking  readings  of  both  the  stale  air  to  the  HRV  duct  and

fresh  air  to  the  house  duct,  the  duct  with  the  lower  CFM ([L/

s] velocity) reading should be left alone, while the duct with the

higher reading  should  be  adjusted  back  to  match  the  lower  read-

ing. See 

Adjusting

 

the

 

Airflow

.

7. Return unit to appropriate fan speed for normal operation

BALANCING

 

PROCEDURE

The  following  is  a  method  of  field  balancing  an  HRV  using  a  Pitot 

tube, advantageous  in  situations  when  flow  stations  are  not  installed 

in  the ductwork. Procedure should be performed with the HRV on high 

speed.
The  first  step  is  to  operate 

all

  mechanical  systems  on  high  speed, 

which  have  an  influence  on  the  ventilation  system,  i.e.  the  HRV 

itself and  the  forced  air  furnace  or  air  handler  if  applicable.  This  will 

provide the  maximum  pressure  that  the  HRV  will  need  to  overcome, 

and allow for a more accurate balance of the unit.
Drill a small hole in the duct (about 3/16"), three feet 

downstream  of  any  elbows  or  bends,  and  one  foot 

upstream  of  any  elbows  or  bends.  These  are 

recommended  distances  but  the  actual  installation 

may limit the amount of straight duct.
The  Pitot  tube  should  be  connected  to  a  

manometer  capable  of  reading  3  digits  of 

resolution.  The  tube  coming  out  of  the  top  of 

the pitot  is  connected  to  the  high  pressure  side  of 

the gauge.  The  tube  coming  out  of  the  side  of  the 

pitot is  connected  to  the  low  pressure  or  reference 

side of the gauge.

I

nsert  the  Pitot  tube  into  the  duct;  pointing  the tip 

into the airflow.

For  general  balancing  it  is  sufficient  to  move  the  pitot  tube  around 
in the  duct  and  take  an  average  or  typical  reading.  Repeat  this 
procedure  in  the  other  (supply  or  return)  duct.  Determine  which 
duct has  the  highest  airflow  (highest  reading  on  the  manometer). 
Adjust  the  higher  airflow  by  reducing  the  fan  speed  (see 
“Adjusting  the  Airflow”).  The  flows  should  now  be  balanced. 
Actual  airflow  can  be  determined  from  the  gauge  reading.  The 
value  read  on  the  gauge  is called  the  velocity  pressure.  The  Pitot 
tube  comes  with  a  chart  that will  give  the  air  flow  velocity  based 
on  the  velocity  pressure  indicated  by  the  gauge.  This  velocity  will 
be  in  either  feet  per  minute  or  meters  per  second.  To  determine 
the  actual  airflow,  the  velocity  is  multiplied  by  the  cross  sectional 
area of the duct being measured.
This is an example for determining the airflow in a 6" duct.
The Pitot tube reading was 0.025 inches of water.
From the chart, this is 640 feet per minute.
The 6" duct has a cross sectional area of

= [3.14 x (6"÷12)

2

]÷4

= 0.2 square feet 

The airflow is then:
640 ft./min. X 0.2 square feet  = 128 cfm

For your convenience, the cross sectional area of some common round duct 
is listed below:

DUCT

 

DIAM.

 (inches)

5 (127 mm) 
6 (152 mm) 
7 (178 mm)

CROSS

 

SECTION

 

AREA

 (sq. ft.) 

0.14
0.20
0.27

The accuracy of the air flow reading will be affected by how close to 
any  elbows  or  bends  the  readings  are  taken.  Accuracy  can  be 
increased by taking an average of multiple readings as outlined in the 
literature supplied with the Pitot tube.

DUCT

AIR

FLOW

Pitot tube

Digital manometer

Pitot

 

tube

 

and

 

gauge

Place pitot tube  a minimum 

of 18"

 

from

 

blower or 

elbows

Note:

 

Duct

 

connections may vary,

depending on model.

Outdoors

Pitot

tube

Pitot

tube

Pitot

 

Tube

 

Air

 

Flow

 

Balancing

 

-

 

Commercial

Pitot

 

Tube

 

Air

 

Flow

Balancing

 

Kit

c/w digital manometer, 

Pitot tube, hose and tool 

bag.

PART NO. 99-BAL-KIT

Digital Manometer

Содержание 1500E-ECM

Страница 1: ...er operating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflows of the Heat Recovery Ventilator HRV by using the balancing procedure found in this manual It is always important to assess how the operation of any HRV may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install...

Страница 2: ...______________________________ Submitted by ____________________________________ DEFROST Factory set defrost time Supply motor is shut off while exhaust air defrosts core WEIGHT 460 lbs 210 kg SHIPPING WEIGHT 580 lbs 260 kg NOTE All specifications are subject to change without notice DIMENSIONS 1500I ECM in inches Specifications 1500I ECM TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Ini...

Страница 3: ...haust air defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 4...

Страница 4: ...ir defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 40 appro...

Страница 5: ...OUTSIDE 5 The 1500E ECM E is designed for outdoor installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are at the ends of the unit The 1500E ECM is designed for outdoor rooftop installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are located at the bottom of the unit A roof curb is required for this install...

Страница 6: ...ing the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After a few seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level is lower than the setting Re...

Страница 7: ... is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level ...

Страница 8: ...the middle of the screw holes Refer to Figure B or C for placement 5 Cut in a 3 4 in by 1 in oval hole in the wall to allow for the wire opening and drill two 1 8 in holes for the screws and wall anchors Figure B or C 6 Pull 3 wire 20 gauge min 100 ft length max through the opening in the wall 7 Connect red green and yellow to the Wiring Terminals located on the Back Plate Figure B or C 8 Attach t...

Страница 9: ...the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate to the Back Plate Figure B Note Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins 10 Insert the Operating Instructions Card into the control Figure A 11 Connect the 3 wire 20 gauge min 100 ft length max to the digital controls terminal...

Страница 10: ...essful repeat steps 1 6 When paired the DET02 Timers can be moved and installed elsewhere Estimated range of the Timer is 40 with no obstructions A RX02 Repeater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Turn on the main wall control by pressing the ON ...

Страница 11: ...ess Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan operation The corresponding Status Light will illuminate under the number on the Timer to indicate either 20 40 or 60 minutes of HIGH speed fan operation To cancel the call for HIGH speed fan operatio...

Страница 12: ... Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Status Light will illuminate and the unit will run on high speed ventilation for the selected time The High Speed Status Light will dim after 10 seconds of run time The High Speed Status Light will flash du...

Страница 13: ...ard SPEED High R W Medium R Y Low R G JUMPER 13 Optional 20 40 60 Minute Timer Part 99 DET01 Boost unit to Ventilation Mode for 20 40 60 minutes no speed change Connect up to 4 maximum Connect to Yellow Red Green HIGH OFF OFF OFF MED LOW Optional 3 Speed Control Part 99 500 Connect to R W Y and G on Thermostat T18 T5 T13 C4 T17 T19 T1 T2 T3 T4 T6 T14 T15 T16 C3 C2 C1 RELAY Fan Hi Fan Med Fan Low F...

Страница 14: ...um 115V 10 amp resistive load T30 T29 T28 T43 SPARE P2 P3 F2 MAX 2 amp R 24Vac Defrost Freeze K7 K1 K2 K8 T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 N C Contact 2 and 4 These relays initiate whenever the HRV fans are operating ...

Страница 15: ...oth sides 2 Remove first set of filters 3 Remove filter divider panels if only accessing from one side 4 Remove filters from behind filter divider panel 5 Replace all filters Ensure that filter divider panels are re inserted into unit Servicing Cores 1 Remove core service panel one or both sides 2 Slide cores out regular core maintenance 3 When placing the cores back into the unit ensure that ther...

Страница 16: ...16 Option 1 Unit can be suspended with U channels and Threaded Rod Option 2 Mounting the 1500 Unit can be placed on blocks sleepers ...

Страница 17: ...s under deck Securing the Frame To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of frame 2 Measure frame diagonally from one corner to the opposite corner Repeat with the remaining two corners These dimensions must be equal for the frame to be square 3 It is e...

Страница 18: ...LY TOP VIEW SIDE VIEW 14 356 mm 16 406 mm 19 483 mm 65 3 4 1670 mm 1 3 4 45 mm 1 3 4 45 mm 42 3 4 1086 mm 16 406 mm 19 483 mm 1 3 4 45 mm 1 3 4 45 mm STALE AIR RETURN FRESH AIR SUPPLY DUCT COLLAR SUPPORTS FACTORY INSTALLED PERIMETER WOODEN NAILER STRIP ...

Страница 19: ...to be built elsewhere and provided by the contractor NOTE It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air free from restriction Recommended no less than 10 ft 3 m apart from each other at least 18 in 46 cm above ground level away from sources of contaminants such as automobile exhaust fumes gas meters garbage containers c...

Страница 20: ...y isolated and separately grounded electrically from the air handler This will avoid a possible shock hazard to service people if a short to ground develops in one of the devices It may be necessary to install a separate fresh air supply ductwork system if the heating is other than forced air When installing an HRV the designer and installer should be aware of local codes that may require smoke de...

Страница 21: ...ed directly into the ceiling space but this should occur near the air handler s intake By operating the HRV ERV on a 24 hour 7 day battery backed timer the unit can be set to operate only when occupancy or indoor conditions require the air exchange In installations where it is satisfactory to provide general exhaust from the space the air to be exhausted may be taken directly from the return air p...

Страница 22: ...FWDEOH VSHHGV LJK PHGLXP DQG ORZ DFK RI WKHVH VSHHGV FDQ EH IXUWKHU DGMXVWHG WR REWDLQ WKH GHVLUHG DLUIORZ 7KLV LV GRQH RQ WKH 0 FLUFXLW ERDUG ORFDWHG ZLWKLQ WKH HOHFWULFDO ER RWK PRWRUV FRQWDLQ D VHSDUDWH 0 FLUFXLW ERDUG WR DOORZ IRU LQGHSHQGHQW DGMXVWPHQW RI WKH PRWRUV 7KH DGMXVW WDS ZLOO FKDQJH WKH DLUIORZV RQ DOO WKUHH RI WKH VSHHGV 3OHDVH QRWH WKDW WKLV XQLW KDV EHHQ IDFWRU VHW WR REWDLQ 0 DW...

Страница 23: ...e unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a manometer capable of reading 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pr...

Страница 24: ...24 Wiring Diagram Neutral Neutre CHASSIS T44 Line Ligne C3 C2 C1 ...

Страница 25: ...ndon Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a the customer may supply labor at their own expense or b if the product was purchased from a dealer then the dealer will supply labor at co...

Страница 26: ...26 ...

Страница 27: ...27 ...

Страница 28: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 1500 110116 ...

Отзывы: