6.1   

Indicator LEDs

6.2  

List of electric cables

6.3

Setting up the electric system and connection to the mains supply

  

Connection cables

There is a row of 6 LEDs on the right hand side of the board, under the terminals.

These LEDs are lit when the corresponding signal is present.

For N.C. inputs 

STOP

,

PHOTO1

 and 

PHOTO

, the corresponding LEDs 

L7

,

 L11

and

L12

 are normally on.

For the N.O. inputs 

OPEN

,

CLOSE

 and 

STEP

, the corresponding LEDs 

L8

,

L9

and

L10

 will be switched off. These LEDs therefore indicate any malfunction of 

the connected devices.

•    Use the power supply cable provided with the operator on

ly.

•   

 The power cable provided may not be extended or shortened

•   

 All wires must be unsheathed as little as possible (6mm at the most)

     as close as possible 

     to the connection terminals, in order to prevent accidental contact 

     with live parts should the cables disconnect from the terminals.

•    Do not pre-seal cables to be fastened to the terminals using screws.

•    If it is possible that wires subject to voltage higher than 50

 Volt RMS 

     and very low voltage safety wires may come into contact with one 

     another, wires with voltage higher than

 50 

volt RMS must be insulated 

     with a sheath; voltage safety wire must have an insulating sheath at 

     least 1mm thick.

•    No external connection cables must be of the flat twin tinsel cord type.

ATTENTION: the cables used must be suited to the type of 

installation. It is the Fitter  ’s responsibility to choose 

appropriate material.

The cables needed may vary depending on the installation and type 

and quantity of devices installed.

The cables used in the installation must be IEC 60335 compliant.

Pos.

Type of cable

Connection

Electricity supply line

Internal button panel.

Sensitive strip (signal)

Power supply

Flashing light

Radio aerial

Tx Photo

Rx Photo

Selector

3x1,5 mm

2

cable

Cable supplied with Schuko socket

Screened RG58 50 Ω cable

4x1 mm

2

cable

2x1 mm

2

cable

2x1 mm

2

cable

3x1 mm

2

cable

3x1 mm

2

cable

2x1 mm

2

cable

This manual does not describe how the electrics system should be prepared for connection to the mains. It does, however, give the following warnings:

•  

 The electricity supply line must be installed and connected by an aut

horised electrician or professional fitt

er.

•  

 The electricity supply must be adequately protected against short circuits and static discharge. 

•  

 T

he power supply network must contain an omnipolar circuit breaker with a contact opening distance equal to or greater than 3.5 mm that assures

    the complete disconnection of the power supply. 

Fitters must make the connections of the 50 Hz 230 

Vac electricity supply, and the various automation devices. 

Connections between the control unit, motor, encoder and transformer have already been performed by the Manufacturer.

   Once the connections to the control unit have been made, the Fitter must use bands to 

j

oin ad

j

acent wires into groups of 2,

 3 or 4 

in order to prevent

    them coming away from the terminal board: bands must be attached as close as possible to the terminals, no more tha

n 10

mm away, taking care not

    to damage wire insulation. No cable may remain unpaired.  

•  

 The bands are only for unsheathed cables (sheathed cables are held in place by the sheath).

•   Pay careful attention not to pair wires with voltages higher than 50

 Volt RMS with lower voltage wires. 

•  

 The wiring performed internally by the manufacturer is already equipped with clamping bands.

ATTENTION: the connections pre-wired by the manufacturer may not be altered under any circumstances.

L7

L8

L9

L10

L11

L12

Содержание RG1R DL S SUPRA MB 230 Vac

Страница 1: ...Rev 01 10 2014 LG 1 SUPRA MB 230Vac RG1R DL S ROAD BARRIER 230 Vac INS TR UCTION AND ADVE R TIS ING FOR US E AND MAINTE NANC E ...

Страница 2: ... switch electromechanical Yes Encoder Yes Speed Rpm 3 5 Opening time Sec 5 Maximum Full Cycle time H 150 25 C Work cycle 40 25 C Nominal maximum work time Min 35 25 C Operating temperature C 20 70 Motor thermal protection C 140 Protection class IP 54 Motor insullation class F Dimensions Weight 25x15 H100 30 Kg Control unit RG1R DL S LIFE home integration reserves the right to make changes to techn...

Страница 3: ...3 2 4 3 X2 X2 1 180 1 2 1 Dismantling of the barrier 2 Manual release ATTENTION ...

Страница 4: ...4 1 2 3 4 5 3 Fixing on the ground with base sole SUE 1 optional ...

Страница 5: ...5 A A 45 B LEFT A B SUM 1 Boom 3 mt protective rubber 45 4 Closure to LE FT A B OPENING LIMIT SWITCH CLOSING LIMIT SWITCH GREEN BROWN WHITE GREEN Unlocked position boom SUM 2 Boom 4 mt protective rubber ...

Страница 6: ...6 5 Closure to R IGHT A B OPENING LIMIT SWITCH CLOSING LIMIT SWITCH GREEN BROWN WHITE GREEN Unlocked position boom SUM 1 Boom 3 mt protective rubber SUM 2 Boom 4 mt protective rubber A B 45 A B RIGHT 45 ...

Страница 7: ...7 mm 8 X4 A A B RIGHT LEFT 5 Assembly boom barrier 6 Mechanical stops adjustment ...

Страница 8: ...ll or safety device is disengaged Leave jumpered if no device is envisaged 6 12 PHOTO NC input for photocells or safety devices Does not intervene during gate opening during closure causes reversal of gate motion until open Leave jumpered if no device is envisaged 19 17 FLASHING LIGHT 230 Vdc 25W max output for connecting a SPLENDOR SRL flashing light characterised by three flashing modes 1 slow d...

Страница 9: ...mA max 230 Vac 25W max 230 Vac 40W max COUTESY LYGHT FLASHING L7 L8 L9 L10 L11 L12 A B C D E 13 24 Vac RADIO TRANSMITER CH2 13 16 5 24 Vdc 3w max Relè CH2 1 2 Indicator Leds There is a row of 6 LEDs on the right hand side of the board under the terminals These LEDs are lit when the corresponding signal is present For the NC inputs stop sensitive edge and photo the corresponding LEDs L7 L11 and L12...

Страница 10: ...he barrier starts rolling if it and after start flashing The automation will perform in sequence a closure 1 an opening 2 a closure 3 an opening 4 Once programming is complete the two green LEDs will Flash and the red one will be fix Should the result obtained not be satisfactory repeat the whole process P H ASE 1 TOTAL RESET opens press again the start button to invert the movement The first limit...

Страница 11: ... ashing ve more seconds the the last two led s will transmitters have been deleted To exit wait 25 seconds or push the radio icon button once TOTAL OPENING a Press The left green led will light b Press P1 Button on the transmitter once the top 5 led s light the transmit ter has been coded a Press the radio icon button top left TWICE The left green led will light and the second L to R of the top 5 ...

Страница 12: ...ashing The button will de select the option led off Press 5 seconds then press in sequence to scroll through the options as shown by the five led s at the top The flashing of the led indicates the option selected The button is used to select the function indicated by the led staying lit The button will de select the option To exit continue to scroll through to option 5 NO FUNCTION IS ACTIVE Condom...

Страница 13: ...n greater or lesser rapidity in response to the obstacle 1 During the closing phase if the control unit identifies an obstacle the automation inverts motion and performs complete opening If the obstacle is detected 3 times consecutively the automation stops in a completely open position awaiting a command 2 During the opening phase if the control unit identifies an obstacle the automation performs a...

Страница 14: ...onnection Electricity supply line Internal button panel Sensitive strip signal Power supply Flashing light Radio aerial Tx Photo Rx Photo Selector 3x1 5 mm2 cable Cable supplied with Schuko socket Screened RG58 50 Ω cable 4x1 mm2 cable 2x1 mm2 cable 2x1 mm2 cable 3x1 mm2 cable 3x1 mm2 cable 2x1 mm2 cable This manual does not describe how the electrics system should be prepared for connection to th...

Страница 15: ...s adopted for eliminating or reducing risks manuals of the individual components list of the components used instructions for use and warnings concerning use by the owner system maintenance record declaration of the system s CE conformity b Fix a CE marking plate to the gate bearing at least the following information Name and address of the party responsible for installation and testing Type of au...

Страница 16: ...nce with the following law 46 90 directive 98 37 EC 73 23 EEC 89 336 EEC and subsequentamendments He she must also make constant reference to harmonised standards EN 12453 and EN 12445 The indications given in this manual must always be observed when installing connecting adjusting testing and setting the control unit The Manufacturer declines all responsibility for damage or injury caused by non ...

Страница 17: ... a person with a similar qualification in order to avoid risks Do not perform technical or programming modifications on the control unit Operations of this type may cause malfunctions and or risk of accidents The manufacturer declines all responsibility for damage caused by products that have been modified In the event of intervention of automatic or fuse switches before restoring function conditions...

Страница 18: ...18 1 2 7 Ricambi ...

Страница 19: ...e of motorised doors testing methods EN 12453 Industrial commercial and garage doors and gates Safety in the usage of motorised doors Requisites EN 60204 1 1997 Machinery safety Electric equipment of the machine Part 1 general rules EN 60950 Information technology equipment Safety Part 1 General requisites ETSI EN 301489 3 2001 Electromagnetic compatibility for radio equipment and appliances EN 30...

Страница 20: ...Address Via Sandro Pertini 3 5 31014 COLLE UMBERTO TV Italia Telephone 39 0438 388592 Telefax 39 0438 388593 http www homelife it e mail info homelife it 20 ...

Отзывы: