6.1
Indicator LEDs
6.2
List of electric cables
6.3
Setting up the electric system and connection to the mains supply
6
Connection cables
There is a row of 6 LEDs on the right hand side of the board, under the terminals.
These LEDs are lit when the corresponding signal is present.
For N.C. inputs
STOP
,
PHOTO1
and
PHOTO
, the corresponding LEDs
L7
,
L11
and
L12
are normally on.
For the N.O. inputs
OPEN
,
CLOSE
and
STEP
, the corresponding LEDs
L8
,
L9
and
L10
will be switched off. These LEDs therefore indicate any malfunction of
the connected devices.
• Use the power supply cable provided with the operator on
ly.
•
The power cable provided may not be extended or shortened
•
All wires must be unsheathed as little as possible (6mm at the most)
as close as possible
to the connection terminals, in order to prevent accidental contact
with live parts should the cables disconnect from the terminals.
• Do not pre-seal cables to be fastened to the terminals using screws.
• If it is possible that wires subject to voltage higher than 50
Volt RMS
and very low voltage safety wires may come into contact with one
another, wires with voltage higher than
50
volt RMS must be insulated
with a sheath; voltage safety wire must have an insulating sheath at
least 1mm thick.
• No external connection cables must be of the flat twin tinsel cord type.
ATTENTION: the cables used must be suited to the type of
installation. It is the Fitter ’s responsibility to choose
appropriate material.
The cables needed may vary depending on the installation and type
and quantity of devices installed.
The cables used in the installation must be IEC 60335 compliant.
Pos.
Type of cable
Connection
Electricity supply line
Internal button panel.
Sensitive strip (signal)
Power supply
Flashing light
Radio aerial
Tx Photo
Rx Photo
Selector
3x1,5 mm
2
cable
Cable supplied with Schuko socket
Screened RG58 50 Ω cable
4x1 mm
2
cable
2x1 mm
2
cable
2x1 mm
2
cable
3x1 mm
2
cable
3x1 mm
2
cable
2x1 mm
2
cable
This manual does not describe how the electrics system should be prepared for connection to the mains. It does, however, give the following warnings:
•
The electricity supply line must be installed and connected by an aut
horised electrician or professional fitt
er.
•
The electricity supply must be adequately protected against short circuits and static discharge.
•
T
he power supply network must contain an omnipolar circuit breaker with a contact opening distance equal to or greater than 3.5 mm that assures
the complete disconnection of the power supply.
Fitters must make the connections of the 50 Hz 230
Vac electricity supply, and the various automation devices.
Connections between the control unit, motor, encoder and transformer have already been performed by the Manufacturer.
•
Once the connections to the control unit have been made, the Fitter must use bands to
j
oin ad
j
acent wires into groups of 2,
3 or 4
in order to prevent
them coming away from the terminal board: bands must be attached as close as possible to the terminals, no more tha
n 10
mm away, taking care not
to damage wire insulation. No cable may remain unpaired.
•
The bands are only for unsheathed cables (sheathed cables are held in place by the sheath).
• Pay careful attention not to pair wires with voltages higher than 50
Volt RMS with lower voltage wires.
•
The wiring performed internally by the manufacturer is already equipped with clamping bands.
ATTENTION: the connections pre-wired by the manufacturer may not be altered under any circumstances.
L7
L8
L9
L10
L11
L12
Содержание RG1R DL S SUPRA MB 230 Vac
Страница 3: ...3 2 4 3 X2 X2 1 180 1 2 1 Dismantling of the barrier 2 Manual release ATTENTION ...
Страница 4: ...4 1 2 3 4 5 3 Fixing on the ground with base sole SUE 1 optional ...
Страница 7: ...7 mm 8 X4 A A B RIGHT LEFT 5 Assembly boom barrier 6 Mechanical stops adjustment ...
Страница 18: ...18 1 2 7 Ricambi ...