Lifasa MCE06ADV Скачать руководство пользователя страница 18

                                                                                                                         

Controllers MCE06ADV – MCE12ADV 

 

 

- 17 - 

 

7.2 

MCExxADV behaviour in ALARM mode 

In case that the MCExxADV detects an error during normal operation (see paragraph 3.2) the screen 
displays an error code and the behaviour of the device is as described in table 7-.1. 
 

 Table 7-1: MCExxADV behaviour under ALARM conditions 

ERROR 

message 

Description 

Possible cause and MCExxADV

 

 behaviour 

 

Measured  current  below 
threshold (
0,1ª measured at 
the secondary side of CT)  

Posible causes:  Baja carga o TC no conectado. 
El  aparato  muestra  el  LED  de  RUN  y  la  pantalla  con  todo 
ceros parpadeando y no conecta ningún relé  

 

Over-compensation

The 

controller 

demands 

for 

stages  disconnection  and 
they are all disconnected. 

Possible causes:  C/K not properly adjusted 
None of the realys will connect. 

 

Sub-compensation

The 

controller 

demands 

for 

stages  connection  and  they 
are all connected. 

Possible causes:  C/K not properly adjusted 
All the relays will remain connected, except the alarm relay 
if exists (see paragraph 3.3) 

 

Overcurent.  The  measured 
current  is  20%  above  the 
rated current (primary of CT) 

Possible causes:  C/K not properly adjusted 
Alarm  relay,  if  exists,  disconnects  (see  paragraph  3.3) 
Although  the  regulation  may  be  wrong,  the  device  tries  to 
regulate the PF normally. 

 

Overvoltage.The  measured 
voltage  is  15%  above  rated 
voltage. 

Possible causes:  Connection to a wrong supply voltage. 
Alarm  relay,  if  exists,  disconnects  (see  paragraph  3.3) 
Although  the  regulation  may  be  wrong,  the  device  tries  to 
regulate the PF normally. 

 

MAINTENANCE  

The  MCExxADV  do  not  require  a  special  maintenance  program.  In  case  that  some  adjustments  or 
maintenance might be necessary it must be performed by dully qualified staff and respecting the required 
safety procedures. 

If  any  malfunction  of  the  PF  compensation  equipment  or  associated  protections  is  detected,  the 
equipment  should  be  disconnected    from  mains.  Before  performing  any  maintenance  repair  or  update 
operation  on  the  controller  or  associated  PF  compensation  equipment,  be  sure  to  disconnect  the  main 
switch and after disconnecting the switch, wait at least 5 minutes to ensure that the capacitors are totally 
discharged.  
 

TECHNICAL SERVICE 

In case of any doubt on the behaviour of the device or in case of malfunction which cannot be solved by 
the maintenance staff, contact INTERNATIONAL CAPACITORS, S.A. technical service: 

 

INTERNATIONAL CAPACITORS, S.A. 

c/ Vallés, 32 – Pol. Ind. Can Bernades 
08130 – Santa Perpetua de Mogoda (Barcelona) SPAIN  
Tel. (+34) 935 747 017 – Fax: (+34) 935 448 433 
E-mail : 

[email protected]

  

Web: 

www.lifasa.com

 

 

Содержание MCE06ADV

Страница 1: ...POWER FACTOR REGULATORS MCE06ADV MCE12ADV Instructions Manual...

Страница 2: ...Controllers MCE06ADV MCE12ADV 1...

Страница 3: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4...

Страница 4: ...terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be...

Страница 5: ...ch the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages...

Страница 6: ...cos sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the t...

Страница 7: ...panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP...

Страница 8: ...th the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes ar...

Страница 9: ...accept configuration changes Manual connection of capacitor stages If this key is pushed for more than 1s the regulator starts connecting new steps in a sequential mode respecting the adjusted connect...

Страница 10: ...n 1 5mm 2 Supply circuit protection By means of a 0 5 to 2A fuse gl type Current measurement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L...

Страница 11: ...side the equipment cabinet MCExxADV devices require current sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the...

Страница 12: ...V P1 P2 Fig 4 2 Connection schematic for MCE06ADV N Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Re...

Страница 13: ...smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according t...

Страница 14: ...ngs Taking as base the power of the smaller capacitor stage the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration...

Страница 15: ...tween 0 7 and 1 Table 5 3 Phase shift options in MCExxADV Screen V I phase shift at cos 1 V measured in phases CT placed in phase T1 30 L3 L2 L3 T2 270 L3 L2 L1 T3 150 L3 L2 L2 T4 210 L3 L2 L3 P1 P2 o...

Страница 16: ...C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes th...

Страница 17: ...equentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed dur...

Страница 18: ...gh the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay...

Отзывы: