Controllers MCE06ADV – MCE12ADV 

 

 

- 11 - 

 

4.2.3 

Cabling cross sections and protections  

The  supply  circuit  must  be  protected  by  means  of fuses  or  a  circuit  breaker  sized  between  0,5  and  2A. 
Recommended fuses are gl type (IEC 269) or M type (IEC 127). A main circuit breaker must be provided 
in order to allow the disconnection of control circuits from supply (controller, relays, contactor coils, etc.) 

The main switch must be easily accessible. The cabling cross section must be minimum 1,5mm

2

 for the 

voltage  supply  and  for  the  relay  outputs  and  2,5mm

2

  for  the  cables  connecting  secondary  of  CT  to 

MCExxADV . For distances between CT and controler higher than 10m the cross section of the last must 
be increased at a rate of 1 extra mm

2

 every 10m. 

4.2.4 

Schematics 

MCE06ADV 

COM

0

1

2

3

4

5

6

A

B

S1

S2

C

D

RELAYS     C1..C6

SUPPLY AND MEASURE 

TERMINALS

V

P1

P2

 

Fig.  4.2.- Connection schematic for MCE06ADV  

 

Nº 

 

Terminals functions 

Current input S1 

Current input S2 

COM 

Relays common 

Relay Output 1 

Relay Output 2 

Relay Output 3 

Relay Output 4 

Relay Output 5 

Relay Output 6 

Supply/Measure Input  0V 

Supply/Measure Input(*) 

 

(*) Rated voltage depending on type.  See device label 

 

MCE12ADV 

COM

7

8

9

10

11 12

COM

0

1

2

3

4

5

6

A

B

S1

S2

C

D

RELAYS     C1..C6

RELAYS     C7..C12

SUPPLY AND MEASURE 

TERMINALS

V

P1

P2

 

Fig.  4.3.- Connection schematic for MCE12ADV

 

 

 

Nº 

 

Terminals description 

Current input S1 

Current input S2 

COM 

Relays common 

Relay Output 1 

Relay Output 2 

Relay Output 3 

Relay Output 4 

Relay Output 5 

Relay Output 6 

Relay Output 7 

Relay Output 8 

Relay Output 9 

10 

Relay Output 10 

11 

Relay Output 11 

12 

Relay Output 12 

Supply/Measure Input  0V 

Supply/Measure Input(*) 

(*) Rated voltage depending on type.  See device label 

 

WARNING!  For  MCE12ADV  devices  (12  relay  outputs)  the  connection  between  COM  terminals  in  the 

upper and lower terminal strips must be done externally. 

 

Содержание MCE06ADV

Страница 1: ...POWER FACTOR REGULATORS MCE06ADV MCE12ADV Instructions Manual...

Страница 2: ...Controllers MCE06ADV MCE12ADV 1...

Страница 3: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4...

Страница 4: ...terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be...

Страница 5: ...ch the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages...

Страница 6: ...cos sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the t...

Страница 7: ...panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP...

Страница 8: ...th the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes ar...

Страница 9: ...accept configuration changes Manual connection of capacitor stages If this key is pushed for more than 1s the regulator starts connecting new steps in a sequential mode respecting the adjusted connect...

Страница 10: ...n 1 5mm 2 Supply circuit protection By means of a 0 5 to 2A fuse gl type Current measurement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L...

Страница 11: ...side the equipment cabinet MCExxADV devices require current sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the...

Страница 12: ...V P1 P2 Fig 4 2 Connection schematic for MCE06ADV N Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Re...

Страница 13: ...smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according t...

Страница 14: ...ngs Taking as base the power of the smaller capacitor stage the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration...

Страница 15: ...tween 0 7 and 1 Table 5 3 Phase shift options in MCExxADV Screen V I phase shift at cos 1 V measured in phases CT placed in phase T1 30 L3 L2 L3 T2 270 L3 L2 L1 T3 150 L3 L2 L2 T4 210 L3 L2 L3 P1 P2 o...

Страница 16: ...C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes th...

Страница 17: ...equentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed dur...

Страница 18: ...gh the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay...

Отзывы: