Controllers MCE06ADV – MCE12ADV 

 

 

- 16 - 

RUN STATUS 

Once  the  device  has  been  configured  according  to  installation  needs  it  can  be  set  to  RUN  mode  to 
regulate  the  PF  of the  installation.  RUN mode is  the  default mode  after exiting the set-up menu or after 
the device start (supply connection followed by a short initialisation period).  When the device is in RUN 
mode it can reach one of the following status: 

a)  Normal  RUN  status  (Absence  of  alarm):  In  this  status  the  device  performs  the  automatic  PF 

regulation, connecting and disconnecting the capacitor stages according to installation needs. In 
this  status  the  user  can  access  to  the  measurement  of  different  parameters  and  can  also  force 
the manual connection or disconnection of capacitor stages as described in paragraph 7.1.  

b)  Alarm  status:  If  any  of  the  anomalous  situations  described  in  paragraph  3.2  occur,  the  device 

jumps to alarm status and displays the error code. Depending on the error type the regulator may 
perform the disconnection of all the stages or continue regulating the PF as in normal RUN. 

 

7.1 

Functions of the device in normal RUN mode. 

In the normal RUN mode the MCExxADV can perform the following functions: 

 

 long 

Manual connection of capacitor stages. Keep the key pushed during more than 1s 
and  the regulator will sequentially connect the different steps, following the normal 
program and respecting the delay time t

on

 set in the set-up procedure 

 long 

Manual disconnection of capacitor stages: Keep the key pushed during more than 
1s and  the regulator will sequentially disconnect the different steps, following the 
normal program and respecting the delay time t

off

 set in the set-up procedure. 

 

Displaying the number of connected steps: If both keys are simultaneously pushed 
the device displays the Nr of connected steps. (Remember the difference between step 
and stage described in paragraph 1.1) 

 short 

Parameters measurement:  Performing successive short pushing of this key (<1s), the 
user can travel along several display screens showing the values of the following 
parameters:  (cos) , cosinus 

ϕ

 of the installation ; (I) , mains current; (THD), THD of 

mains current; (V) , Mains voltage; (I, MAX), Maximum value of mains current since the 
last clear; (V MAX), Maximum value of mains voltage since the last clear. The 
displayed parameter is pointed by the cursor   

 short 

Parameters measurement:  Performing successive short pushing of this key (<1s), the 
user can travel through the readings of the same parameters described above but in 
reverse order.  

 long 

Start the SET-UP mode:  Performing a long push of this key (<1s), the device jumps 
to set-up mode. 

  

 MAX 

Clear MAX values: Performing a long push of this key (<1s) while the cursor   is 
pointing to MAX , the MCExxADV

 

 clears the maximum values of voltage and current 

recorded since the last clear. 

 

Содержание MCE06ADV

Страница 1: ...POWER FACTOR REGULATORS MCE06ADV MCE12ADV Instructions Manual...

Страница 2: ...Controllers MCE06ADV MCE12ADV 1...

Страница 3: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4...

Страница 4: ...terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be...

Страница 5: ...ch the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages...

Страница 6: ...cos sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the t...

Страница 7: ...panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP...

Страница 8: ...th the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes ar...

Страница 9: ...accept configuration changes Manual connection of capacitor stages If this key is pushed for more than 1s the regulator starts connecting new steps in a sequential mode respecting the adjusted connect...

Страница 10: ...n 1 5mm 2 Supply circuit protection By means of a 0 5 to 2A fuse gl type Current measurement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L...

Страница 11: ...side the equipment cabinet MCExxADV devices require current sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the...

Страница 12: ...V P1 P2 Fig 4 2 Connection schematic for MCE06ADV N Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Re...

Страница 13: ...smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according t...

Страница 14: ...ngs Taking as base the power of the smaller capacitor stage the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration...

Страница 15: ...tween 0 7 and 1 Table 5 3 Phase shift options in MCExxADV Screen V I phase shift at cos 1 V measured in phases CT placed in phase T1 30 L3 L2 L3 T2 270 L3 L2 L1 T3 150 L3 L2 L2 T4 210 L3 L2 L3 P1 P2 o...

Страница 16: ...C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes th...

Страница 17: ...equentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed dur...

Страница 18: ...gh the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay...

Отзывы: