background image

 

7

INSTALLATION

Grounding

The Extended Battery Cabinet must be installed
with a dedicated grounding electrode conductor
(GEC) to the site grounding system in accordance
with national and local wiring codes and regulations
as shown below. 

Communications

To enable communication between the Extended
Battery Cabinet and the 

Nfinity

, it is necessary to

install an Intellislot Battery Card (IBC) in the
Intellislot port of the UPS. See below. A second,
included IBC is installed in the Extended Battery
Cabinet. The provided serial cable is to be
connected between the two cards.

DC Power

DC connection with the UPS unit must be via the
factory-supplied battery cables, or if longer
connection cable is required, via the optional
Extended Battery Cable kits. See below.

After connections are made and verified, the
output circuit breaker must be closed to connect
the batteries inside the Extended Battery Cabinet
to the Nfinity UPS. To do this, move the handle of
the circuit breaker under the lower-most bezel to
the ON position

 (see illustration below for circuit

breaker location).

L1  L2

GEC
Connection

Communications

NOTE

Failure to turn on the circuit breaker 

may cause damage to the batteries in the 

Extended Battery Cabinet. Failure to 

follow this procedure may limit your 

warranty.

DC Power

Output Circuit Breaker

Содержание Nfinity Extended Battery Cabinet

Страница 1: ...POWER PROTECTION Extended Battery Cabinet for Nfinity USER MANUAL...

Страница 2: ......

Страница 3: ...N 4 INSPECTION 4 ENVIRONMENT 4 REQUIRED SETUP EQUIPMENT 4 SITE PREPARATION 4 UNLOADING 5 UNLOADING THE EXTENDED BATTERY CABINET 5 STATIONARY MOUNTING 6 OPTIONAL STATIONARY MOUNTING 6 INSTALLATION 7 GR...

Страница 4: ......

Страница 5: ...er must correct at his own expense Operating Environment Operate the Extended Battery Cabinet in an indoor environment only in an ambient temperature range of 32 F to 104 F 0 C to 40 C For optimum bat...

Страница 6: ...tput Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage OFF ON Standby...

Страница 7: ...m of 12 battery modules with the same level of monitoring and control as the battery modules fitted in the UPS Features Up to four Extended Battery Cabinets can be used with a single Nfinity UPS Up to...

Страница 8: ...weight and size of the unit Make sure that the structural integrity of the floor can withstand the weight Refer to the table below for size and fully populated weight considerations Check to make sure...

Страница 9: ...allet and cabinet Keep brackets and bolts for future transportation of cabinet or for additional sta bility once in place 3 Remove the metal ramp from the bottom of the battery cabinet rotating it Fit...

Страница 10: ...Additional stability can be added by bolting the mounting brackets used in shipping to the floor Optional Stationary Mounting For greater stability use a higher grade bolt Refer to the dimensions belo...

Страница 11: ...en the two cards DC Power DC connection with the UPS unit must be via the factory supplied battery cables or if longer connection cable is required via the optional Extended Battery Cable kits See bel...

Страница 12: ...f Extended Battery Cabi nets installed Press return arrow and then press to save your changes and exit The system is now configured Main Menu UPS Status UPS Configuration Display Date Time Event Log A...

Страница 13: ...environmentally responsible way that complies with local codes and regulations or return the module to Liebert for proper disposal CAUTION Battery modules are heavy 30 kg 66 lbs Make sure to use two...

Страница 14: ...lf way in slide the module sideways toward the center of the unit Continue pushing module until fully inserted 3 Press and turn fastener clockwise until locked 4 Wait about 15 seconds as the module pe...

Страница 15: ...3 73 149 221 293 7 000 4 900 8 16 23 30 36 43 50 57 78 161 245 329 6 500 4 550 9 17 24 32 40 47 55 62 84 174 258 342 6 000 4 200 11 19 24 36 43 51 60 68 92 190 286 382 5 500 3 850 12 21 23 39 47 56 66...

Страница 16: ...12...

Страница 17: ......

Страница 18: ...his literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2002 Liebert Corporation All...

Отзывы: