Appendix 1 Battery Module 39
Liebert ITA 16kVA/20kVA User Manual
Replacing battery fuse
If the battery internal fuse is damaged, loosen the protective cover of fuse box on the battery module rear panel and
replace the damaged fuse with a new one, then tighten the fixing screws of the protective cover of fuse box to prevent
electric shock risk during the UPS operation, as shown in Figure 3.
⋎⋐᧼
䰽
Protective cover
of fuse box
Figure 3 Schematic diagram of replacing fuse
Note
1. The battery loop and AC input are not insulated, a hazardous voltage may exist between the battery ports and ground, so it is
prohibited to touch them for avoiding electric risk.
2. The length of the standard battery cable delivered with the battery module is 0.5m. If you need more length cable, please
consult the dealer.