24 Chapter 3 Operation And Display Panel
Liebert ITA 16kVA/20kVA User Manual
Chapter 3 Operation And Display Panel
This chapter introduces the functions and use of the components on the UPS operation and display panel, and
provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and
UPS alarm message list.
3.1 Introduction
The operation and display panel is located on the front door of the UPS. Through the operation and display panel,
you can conduct the UPS operation control and query all the UPS parameters, UPS and battery states, and alarm
message.
As shown in Figure 3-1, the operation and display panel provides LCD, menu buttons (F1 ~ F4
ǃ
HELP)
ǃ
LED
indicators (inverter indicator and fault indicator ), control buttons (FAULT CLEAR, ON, OFF, ALARM CLEAR, EPO).
LCD
Menu buttons
Control buttons
Inverter indicator
Fault indicator
Figure 3-1 Operation and display panel
3.1.1 LED Indicators
The LED indicators are composed of inverter indicator and fault indicator. Table 3-1 gives the indicators description.
Table 3-1 Description of LED indicators
LED Color State
Meaning
Steady green
Load power is supplied by the inverter
Flashing green
Inverter ON, starting up, synchronizing, or standing by (ECO mode)
Inverter indicator
Green
Off
Inverter not operating
Flashing red
General fault (such as no battery)
Steady red
Serious fault (such as inverter fault)
Fault indicator
Red
Off No
fault
3.1.2 Audible Alarm (Buzzer)
The UPS activity is accompanied with the following two different kinds of audible alarms shown in Table 3-2.
Table 3-2 Audible alarm description
Sound Meaning
One beep every second
UPS alarm, such as AC input failure
Continuous beep
UPS fault, such as fuse or hardware failure