background image

28      Chapter 3  Operation And Display Panel 

Liebert ITA 16kVA/20kVA    User Manual 

Menu Item 

Explanation 

LCD contrast 

Adjust the LCD contrast 

Date format   

YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be 

selected. 

Date & time   

Set the date and time   

Comm1 baud rate 

Set the communication baud rate of the USB port   

Comm2 baud rate 

For internal communication only, can not be set   

Comm3 baud rate 

Set the communication baud rate of the SNMP card port 

UPS address 

This setting is suitable for RS485 communication 

Communication mode 

Set the communication mode   

Callback times 

If the communication mode of the SNMP card port is Modem, you can 

set alarm callback times here   

Phone No.1 

If the communication mode of the SNMP card port is Modem, you can 

set phone No.1 here   

Phone No.2 

If the communication mode of the SNMP card port is Modem, you can 

set phone No.2 here   

Phone No.3 

If the communication mode of the SNMP card port is Modem, you can 

set phone No.3 here   

Command password 

You can change the command password. Default: “123456” 

Battery capacity test 

Battery capacity 

Battery cell 

Set the battery cell. The setting options include: 30-cell, 32-cell, 

34-cell, 36-cell, 38-cell, 40-cell 

Battery boost charge   

Enabled or disenabled   

Temperature 

compensation   

Enabled or disabled   

Temperature sensor   

Set the position of the temperature sensor. “Remote” only   

Battery group sharing   

Set each single in parallel system to share the battery group or not   

Single/parallel Set 

the 

single/parallel 

 

Parallel number   

Set the parallel number   

Redundant number 

Set the redudant number   

ECO mode 

ECO function enabled 

Output frequency 

Set the output frequency   

Output voltage system 

Set the output voltage system   

LBS   

LBS function enabled 

Function settings 

3-in 3-out/3-in 3-out 

Set the output system: 3-in 3-out/3-in 3-out 

This setting can only be carried out after the EPO operation. After the 

setting, you must power off the system, and confirm that the system 

actual connection mode complies with the setting. Power on again, 

and the setting can come into force   

Battery maintenance 

test 

The battery maintenance test will lead to the battery being partly 

discharged, for rough assessment of the battery capacity. The load 

must range from 20% ~ 100%   

Battery capacity test 

The battery capacity test will lead to the battery being completely 

discharged, for accurate assessment of the battery capacity. The load 

must range from 20% ~ 100% 

System test 

For UPS self-test. The user actives this function, 5 seconds later, a 

pop window will appear to show the result of this test 

Stop testing 

Manually stop the test, including maintenance test, capacity test and 

system test 

Forcing charge 

Manually conduct the forcing boost charge for battery   

Test command (start, stop 

battery, system test or 

frocing boost charge)

 

Stop forcing charge 

Manually stop the forcing boost charge for battery 

Monitor Version 

Provide the monitor software version   

Rectifier Version 

Provide the rectifier software version 

System version 

Inverter Version 

Provide the inverter software version 

 

Keypad window 

The function of menu buttons (F1 ~ F4 and HELP) is shown in icon mode for the current display screen. 

Содержание ITA UPS 16kVA

Страница 1: ...the nearest Emerson local sales office or service center Copyright 2010 by Emerson Network Power Co Ltd All rights reserved The contents in this document are subject to change without notice Emerson N...

Страница 2: ...ranges from 3 5mA to 1000mA Transient and steady state earth leakage currents which may occur when starting the equipment should be taken into account when selecting instantaneous residual current cir...

Страница 3: ...l will exceed 400Vdc and physical contact would be fatal Battery manufacturers supply details of the necessary precautions to be observed when working on or in the vicinity of the battery strings Thes...

Страница 4: ......

Страница 5: ...6 2 2 1 Distribution Room 7 2 2 2 Battery Room 7 2 2 3 Storage 7 2 3 Installation tools 7 2 4 Mechanical Installation 8 2 4 1 Tower Installation 8 2 4 2 Rack Installation 9 2 5 External Protective Dev...

Страница 6: ...ary Screen 26 3 2 3 Default Screen 26 3 3 Detailed Description Of Menu Items 27 3 4 Prompt Window 29 3 5 UPS Alarm Message List 29 Chapter 4 UPS Operation Instructions 32 4 1 UPS Start up 32 4 1 1 Nor...

Страница 7: ...r 5 Maintenance 36 5 1 Fan Maintenance 36 5 2 Battery Maintenance 36 5 3 Cleaning UPS 36 5 4 Checking UPS State 36 5 5 Checking UPS Functions 36 Appendix 1 Battery Module 38 Appendix 2 Optional Part L...

Страница 8: ......

Страница 9: ...id interference thus adaptable to areas with unstable mains supply z High power density z Full digital control technology based on digital signal processor DSP to achieve high system reliability with...

Страница 10: ...front panel provides the ventilation holes operation and display panel DIP switch and battery cold start button with protective cover The operation and display panel provides LCD menu buttons LED indi...

Страница 11: ...returns to normal state the UPS will automatically switch to Normal mode from Battery mode the mains power supplies DC power to the inverter through the rectifier PFC circuit and then the electronic t...

Страница 12: ...ECO mode is an energy saving operation mode For some power equipment that insensitive to power grid quality you can use the ECO mode for power supply through bypass to reduce the power loss Note 1 In...

Страница 13: ...20 default 15 Lower limit 10 20 30 or 40 default 20 Output Mains efficiency 93 up to 94 Type Sealed lead acid maintenance free battery Cell No 30 32 34 36 38 40 Rated voltage 360Vdc 480Vdc Battery Cha...

Страница 14: ...revent injury from accidental electric arcs z Remove rings watches and all metal objects z Use tools with insulated handles z Wear rubber gloves z If a battery leaks electrolyte or is otherwise physic...

Страница 15: ...is temperature will shorten the battery life and operation below this temperature will reduce the battery capacity If the battery average temperature in run rises from 20 C to 30 C the battery life wi...

Страница 16: ...llation you should prepare the battery rack and battery cabinet for installing the battery modules for rack installation the battery modules and the UPS can be installed in the same rack together 2 4...

Страница 17: ...UPS on the rack through brackets as shown in Figure 2 4 Rack Guide rail UPS Bracket Screw 4 pcs Figure 2 4 Installing the UPS Installation procedures for battery modules included The installation meth...

Страница 18: ...he thermomagnet circuit breaker of IEC60947 2 tripping curve C normal following the 125 of current value listed in Table 2 2 Bypass disconnection When the system uses bypass disconnection the protecti...

Страница 19: ...le 1 2 2 6 Connecting Power Cables I O cables and battery cables are needed to be connected Battery modules provide the battery cable options When designing the cables you should follow the instructio...

Страница 20: ...ss configuration In accordance with the four types of the two distribution methods this section will introduce the I O cables connection procedures respectively Note This product is compatible with 3...

Страница 21: ...C N line and PE line respectively to the user terminal block terminal mA mB mC and mN of the single POD and PE terminals 2 Connect the live line output phase A phase B and phase C N line and PE line r...

Страница 22: ...ut phase B phase C N line and PE line respectively to mB and mC terminals of the single POD user terminal block shorted copper bars 4 of mN and bN terminals and PE terminals 4 Connect the live line ou...

Страница 23: ...bar 5 of the single POD user terminal block shorted copper bars 4 of the two oN terminals and PE terminals 6 Remove all the shorted copper bars 3 from the UPS I O terminal block and connect the UPS te...

Страница 24: ...shorted copper bars 4 4 5 10 4 6 7 8 bC oN oA oB oC PE mN bN bB mA bA Figure 2 13 Shorted copper bar connection for the UPS I O terminal block 2 Connect the shorted copper bar 8 to one end of the sho...

Страница 25: ...tenance and then tick at the right side of the AC OUTPUT and BYPASS INPUT according to the actual conditions Figure 2 15 Label 2 6 3 Connecting Battery Cables Note If battery module is not selected th...

Страница 26: ...Dry contact port 4 Dry contact port 5 Figure 2 16 Pin distribution of dry contact ports Table 2 3 Description of the dry contact ports Silk screen Port name Pin NO Pin name Meaning 1 1 S_ALARM The sig...

Страница 27: ...nd USB port can be used together The pin distribution for each SNMP card port is shown in Figure 2 17 1 GND_SNMP 9_SNMP 9_TR SNMPSIG 14 PIN TXD232 RXD_SNMP TXD_SNMP RXD232 2 3 4 6 7 8 9 10 5 Figure 2...

Страница 28: ...llel POD if N 2 the self distribution will be required for the parallel system Installing parallel system includes z Mechanical installation z Setting parallel addresses z Connecting parallel cables z...

Страница 29: ...l cables connection is shown in Figure 2 19 UPS1 UPS2 UPS3 UPS4 Parallel port 1 Parallel port 2 Parallel port 1 Parallel port 2 Parallel port 1 Parallel port 2 Parallel port 1 Parallel port 2 Parallel...

Страница 30: ...e 1 Connection Power off the system completely and disconnect all the battery MCBs of the UPS single and then connect the terminal N and of the shared battery strings respectively to the terminal Bat...

Страница 31: ...cable UPS2 Bypass Rectifier input Bypass LBS STS Load connection UPS1 UPS2 UPS1 Rectifier input Parallel control cable Figure 2 20 Typical double bus system with the STS and LBS 2 10 2 External Protec...

Страница 32: ...ns FAULT CLEAR ON OFF ALARM CLEAR EPO LCD Menu buttons Control buttons Inverter indicator Fault indicator Figure 3 1 Operation and display panel 3 1 1 LED Indicators The LED indicators are composed of...

Страница 33: ...3 1 4 LCD And Menu Buttons The operation and display panel provides an LCD and five menu buttons F1 F2 F3 F4 HELP Table 3 4 gives the menu buttons function description Table 3 4 Menu key functions des...

Страница 34: ...w Menu window Keypad window F1 F2 F3 F4 HELP Figure 3 3 Primary screen The current icons on top of the F1 F4 and HELP menu buttons give the explanations of each key Under any menu in primary screen pr...

Страница 35: ...ut Power factor Power factor L N voltage V Phase voltage Frequency Hz Bypass frequency Bypass input L L voltage V Line voltage L N voltage V Phase voltage L N current A Phase current Frequency Hz Outp...

Страница 36: ...arallel Parallel number Set the parallel number Redundant number Set the redudant number ECO mode ECO function enabled Output frequency Set the output frequency Output voltage system Set the output vo...

Страница 37: ...pletely and then power on again after the wiring is changed according to the settings 3 5 UPS Alarm Message List The following list gives the UPS alarm message list based on the Current records and Hi...

Страница 38: ...beyond limits Load transfers to bypass Inverter overtemp The temperature of the inverter heat sink is too high to keep inverter running This alarm is triggered by the signal from a temperature monitor...

Страница 39: ...ss on or DC bus or rectifier not ready Alarm silence cancle Press FAULT CLEAR or ALARM CLEAR Bypass mode The UPS is in Bypass mode Normal mode The UPS is in Normal mode Battery mode The UPS is in Batt...

Страница 40: ...mal Module Start up Procedure This procedure is suitable for UPS start up when the UPS is in complete disconnection state Procedures are as follows 1 Close the output input switch outside the UPS on b...

Страница 41: ...tion 1 Press the OFF for 2 seconds The inverter indicators are off and the buzzer alarms The load switches to the static bypass and the inverter shuts down Note Press the ALARM CLEAR button can silenc...

Страница 42: ...ge and excessive switching may result in the UPS power off Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the LCD you can carry out th...

Страница 43: ...then press F5 Enter 4 Position the cursor on the row in which the date and time are displayed then press F5 Enter 5 Use F3 or F4 up or down arrows and enter the current time and date information 6 Pr...

Страница 44: ...d ambient temperature or two months at high ambient temperature Note 1 Never short circuit the battery terminals which will result in fire 2 Never open the battery as the electrolyte is harmful to hum...

Страница 45: ...ckup the load data before conducting the UPS functions check Procedures are as follows 1 Press the OFF button to check if the buzzer beeps indicators are on and the LCD display is normal 2 Press the A...

Страница 46: ...el after the battery module arrival The appearance of the battery module is shown in Figure 1 Fixing screw 6 pcs Protective panel Figure 1 Appearance of the battery module Rear panel Operation panel o...

Страница 47: ...cover of fuse box to prevent electric shock risk during the UPS operation as shown in Figure 3 Protective cover of fuse box Figure 3 Schematic diagram of replacing fuse Note 1 The battery loop and AC...

Страница 48: ...component Communication options UFMOD21Z1 MODBUS assembly used in UPS UFMOD21Z1 R5 UF POD3U20K10 3 in 3 out 3 in 3 in 1 out rack model 20kVA smart UPS single POD POD UF POD6U20K11 3 in 3 out 3 in 3 in...

Отзывы: