background image

 

SLI-23185QS6_Rev0_09-2012 

The Liebert

®

 GXT3

 UPS is ready to be powered.   

1.  Locate the plastic bezel from the shipping box and attach the bezel to the UPS taking care to align the fastening 

clips on both ends before inserting them into the holes. 

2.  If your application requires the use of external battery cabinets for longer back up time requirements, connect the 

first battery cabinet to the UPS with the cable provided with the battery cabinet.  

Note: Either connector is 

acceptable to connect the external battery cabinet

.  If more than one battery cabinet is used the additional 

cabinets then connect to the previously connected battery cabinet.   

3.  Ensure the maintenance bypass breaker is in the open position and that the guard is secured in place. 
4.  Ensure that the REPO connector on the rear of the unit has a jumper between pins 1-2 of the REPO connector or 

properly wired to an Emergency Power Off circuit (normally closed). 

5.  Install any optional Intellislot communication card into the Intellislot port on the rear of the unit. 
6.  Close the input breaker in the panelboard that provides input power to the UPS 
7.  Close the input breaker on the rear of the UPS unit.

 Note: The UPS will now have power and the AC Input 

indicator on the display will illuminate.  The UPS will begin to charge the internal batteries causing the battery 
capacity LEDs to illuminate.

 

8.  The Liebert GXT3 UPS has customizable settings that might be required depending on the application.  Please 

review the CD that ships with the UPS unit for the steps to use the configuration program and make any 
necessary changes.  Once that is complete, proceed to the next step. 

9.  Close all output breakers on the rear of the UPS 
10.  If external battery cabinets are used, close all breakers on the rear of each battery cabinet 
11. 

Press and hold for about 4 seconds, the “ON” button on the UPS display.  

Note: this will apply power to the output 

receptacles via the internal bypass. The bypass indicator will be illuminated along with an audible beep during this 
time

.   

12.  Over the next several seconds the UPS will perform the self checks and then automatically transfer the connected 

equipment to conditioned power.  Once that is complete, the bypass indicator will turn off and the inverter 
indicator will illuminate.   

 
The UPS is now running in normal operation mode providing protected, filtered power to the connected equipment. 

 
 

 

 

 
 
 

 

6000VA 

Отзывы: