Troubleshooting

 

 
The following symptoms indicate the Liebert

®

 GXT3

 is malfunctioning: 

• 

The relative indicators illuminate, indicating the UPS has detected a problem. 

• 

An alarm buzzer sounds, alerting the user that the UPS requires attention. 

 
In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be 
illuminated to provide a diagnostic aid to the user, as shown below 
 

 

The descriptions are listed in the following table 

Indicator 

Diagnosis/Audible alarm 

A - E

 

On bypass from output overload (half-second beep every half-second)

 

A

 

On bypass due to over temperature condition (1-second beep every 4 seconds)

 

B

 

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

 

C

 

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds) 

D

 

PFC failure (1-second beep every 4 seconds) 

E

 

On bypass due to inverter failure (1-second beep every 4 seconds) 

A&B

 

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and 
battery charger failure) and continuous alarm

 

A&C

 

UPS failed battery test (2-second beep every 60 seconds)

 

A&D

 

Maintenance bypass switch on (continuous)

 

A&E

 

Bypass feedback (1-second beep every 4 seconds) 

B&C

 

REPO (one quarter-second beep at quarter-second intervals)

 

B&E

 

Short circuit on the output 

C&E

 

UPS shutdown by command from communication (USB or Liebert IntelliSlot

®

 port)  

(no audible alarm) 

AC Input Indicator 

LED flashing

 

L-N reverse 

Battery Indicator 

Flashing

 

Internal battery source not available (continuous audible alarm); check battery 
connection, power down and reboot UPS

 

Bypass Indicator 

Flashing

 

Utility power voltage or frequency is out of tolerance; bypass is unavailable

 

 
 

Single-Phase UPS & Server Cabinets Technical Support 

[email protected] 
800-222-5877 
Outside North America: +00800 1155 4499 

 
Emerson Network Power Worldwide Locations 

United States 

1050 Dearborn Drive 
P.O. Box 29186 
Columbus, OH 43229 
800-222-5877 
 

Europe 

Via Leonardo Da Vinci 8 
Zona Industriale Tognana 
35028 Piove Di Sacco (PD) Italy 
+39 049 9719 111 
Fax: +39 049 5841 257

 

Asia 

29/F, The Orient Square Building 
F. Ortigas Jr. Road, Ortigas Center 
Pasig City 1605 
Philippines 
+63 2 687 6615 
Fax: +63 2 730 9572

 

 

 

Отзывы: