Specifications
38
Table 9
External battery cabinet specifications
Model Number
GXT2-240VBATTUL
Used w/ UPS model
GXT2-6000RTL630
Dimensions, W x D x H, in. (mm)
Unit (with bezel)
6.9 x 20.6 x 16.9 (176 x 522 x 430)
Shipping
22.0 x 27.2 x 17.9 (560 x 690 x 455)
Weight, lb (kg)
Unit
145 (65)
Shipping
173.1 (78.5)
Battery Parameters
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V
20 x 12V
Battery Manufacturer, Part #
Yuasa / REW 45-12
Backup Time
See
Table 5 - Battery run times
Environmental
Operating Temp
32
°
F to 104
°
F (0
°
C to 40
°
C)
Storage Temp
5
°
F to 122
°
F (-15
°
C to 50
°
C)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 6600 ft. (2000m) at 104
°
F (40
°
C) without derating
Storage Elevation
50,000 ft. (15,000m) maximum
Agency
Safety
UL, C-UL Listed to UL1778
Transportation
ISTA Procedure 1B