Communications

25

10.3 UPS Intelligent Communications

The GXT2-6000RTL630 is equipped with two Intellislot® ports to provide advanced communication 

and monitoring options.
The Intellislot port closer to the corner of the UPS chassis is the serial card slot. This Intellislot port is 

used for the OCWEBCARD and the USBCARD. The other Intellislot port is used for 

RELAYCARD-INT or the MULTIPORT Card.

Liebert's MultiLink software continually monitors the UPS and can shut down your computer or 

server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card 

is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the 

network with other computers running MultiLink when you purchase a MultiLink License Kit. For 

more information about the Intellislot SNMP/Web Card and MultiLink license Kits, visit our Web site 

(www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the GXT2-6000RTL630. The Intel-

lislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the 

network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-

dinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom wired applications and deliv-

ers support for built-in shutdown for AS/400 systems. 

NOTE

The OCWEBCARD DB9 serial port cable should be used only for the initial card setup. Remove 

the cable after setup is complete.

When the DB9 OCWEBCARD serial port cable is removed, the OCWEBCARD DB9 connector 

needs to be covered. The DB9 cover is included with the UPS.

!

CAUTION

To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables 

should be segregated and run separate from all other power cables, where applicable.

DB9 (RS232) port 

covered

Liebert’s OCWEBCARD

Содержание GXT2-6000RTL630

Страница 1: ...AC Power For Business Critical Continuity Liebert GXT2 6000RTL630 User Manual 208 240 VAC...

Страница 2: ......

Страница 3: ...5 1 2 Rack Mount UPS Installation 12 5 1 3 Installing the Adjustable Rack Mount Kit Sold Separately 12 5 2 Install the Internal Batteries 14 5 3 Connect the Internal Batteries Using the External Conne...

Страница 4: ...TROUBLESHOOTING 31 12 0 1 Auto Learning Battery Run Times 35 13 0 SPECIFICATIONS 36 FIGURES Figure 1 GXT2 6000RTL630 front view 7 Figure 2 GXT2 6000RTL630 rear view 8 Figure 3 Internal battery pack wi...

Страница 5: ...sive substances This UPS contains no user serviceable parts except the internal battery pack The Off Bypass push button does not electrically isolate internal parts Under no circumstances attempt to g...

Страница 6: ...e is harmful to skin and eyes It is toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries...

Страница 7: ...ctions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC v...

Страница 8: ...nuously conditions and regu lates its output voltage whether utility power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best from...

Страница 9: ...e amount of distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the GXT2 6000RTL630 2 3 Inverter In nor...

Страница 10: ...external battery cabinets are available to extend battery run times 2 7 Dynamic Bypass The GXT2 6000RTL630 provides an alternate path for utility power to the connected load in the unlikely event of a...

Страница 11: ...eries to lighten the UPS for easier installation The internal batteries may be installed after the cabinet has been placed in its final floor or rack position The Power Distribution box is shipped sep...

Страница 12: ...OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH BREAKER 30A ON OFF OFF OFF UPS UTILITY COMMUNICATION PORT SEE MANUAL FOR CONNECTIONS OFF RE...

Страница 13: ...andard box for custom installations Figure 4 Optional power distribution PD L630 OUTPUT BREAKER 20A 240V T OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL...

Страница 14: ...and screws 2 each Support base 2 Mounting hardware Configuration program CD DB 9 port cover GXT2U Configuration Program www liebert com For use with Liebert GXT2U model UPS systems Version 1 6 For Win...

Страница 15: ...ermine the type of installation and follow the appropriate instructions in either 5 1 1 Tower UPS Installation or 5 1 2 Rack Mount UPS Installation 5 1 1 Tower UPS Installation When using the GXT2 600...

Страница 16: ...ing brackets Part RMKIT18 32 feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack To install the rack mount brackets 1 Unpack two 2 rack mou...

Страница 17: ...eck alignment of bracket assemblies and TIGHTEN ALL SCREWS FROM Steps 2 and 3 5 Prepare the UPS or battery cabinet the equipment for rack mounting by following instructions in the equipment s user man...

Страница 18: ...flange of the front members you can use the four 4 extra M5 screws provided in the kit to secure the equipment Otherwise the equipment should be secured to the front of the rack with four 4 customer s...

Страница 19: ...ed position using two screws The picture on the left shows the connector in the open position as shipped When the UPS is installed remove the two screws to release the connector Plug the connector int...

Страница 20: ...L630 power distribution box OUTPUT BREAKER 20A 240V T OUTPUT BREAKER 20A 240V T ON ON INPPUT OUTPUT ONLY CB DOES NOT CONNECT BYPASS POWER TO MANUAL BYPASS SWITCH BREAKER 30A ON OFF OFF OFF UPS UTILITY...

Страница 21: ...cuit breaker on the rear fixed panel of the UPS disconnect all power between the main cabinet and the distribution box Models equipped with a manual bypass switch pass bypass power directly to the byp...

Страница 22: ...attery cabinet 5 Connect the supplied external battery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS 6 The UPS is now equipped with additional backup battery ru...

Страница 23: ...ker located on the distribution box The green AC Input indicator should illuminate on the UPS front panel 10 Press the On button for 1 second The BYPASS lamp will light for several seconds before the...

Страница 24: ...50 or 60 Hz Set the Low Battery Warning alarm time from 2 to 30 minutes Enable Disable the Auto Battery test Set the Auto Battery test to 7 14 21 or 28 days Specify the number of external battery cab...

Страница 25: ...LEDs illuminate allow the UPS to recharge the batteries for 24 hours After 24 hours retest the batteries After the batteries have been retested if only three of the five Battery LEDs illuminate conta...

Страница 26: ...MultiLink 3 x software and can remotely initiate the battery test 8 5 Fault Indicator LED Red The Fault indicator LED is illuminated if the UPS has detected a problem Also one or more of the battery l...

Страница 27: ...el indicator represents a 20 capac ity level As capacity decreases fewer indicators remain illumi nated Refer to 12 0 Troubleshooting For approximate battery run times refer to Table 5 These times are...

Страница 28: ...gnal will start a 2 minute shutdown timer The timer cannot be stopped After 2 minutes the UPS will shut down 4 If utility power returns during the 2 minute timer countdown the shutdown timer will cont...

Страница 29: ...license Kits visit our Web site www liebert com or contact your local dealer or Liebert representative Several option cards are available for use in the Intellislot port of the GXT2 6000RTL630 The Int...

Страница 30: ...ment to comply with national and local wiring codes and regulations REPO switch connection diagram CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables should be se...

Страница 31: ...length of time it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries Failure to recharge the batteries peri odically will result in...

Страница 32: ...way 8 Reconnect the electrical connections for each battery pack 9 Install the battery retaining brackets using the Phillips removed earlier 10 Install the battery access panel and tighten the captive...

Страница 33: ...t breaker on the rear of the UPS 7 Remove the distribution box from the UPS a Loosen all three captive screws until the box releases b Pull box away from the UPS and set the box aside on a padded surf...

Страница 34: ...ainst the UPS and tighten the captive screws Do not overtighten 6 If the utility branch circuit breaker and load is off turn the branch breaker on now 7 Turn on the output circuit breaker on the rear...

Страница 35: ...Please have the UPS model number and serial number available at the time of your inquiry Table 2 Indicator meanings LED status Diagnosis Audible alarm All LEDs On bypass due to output overload beep e...

Страница 36: ...ive or the Liebert Worldwide Support Group Fault and Bypass indicator LEDs and diagnostic LED B are illuminated UPS internal DC bus overvoltage UPS requires service Contact your local dealer Liebert r...

Страница 37: ...utility failure One short beep every 10 seconds more than 2 minutes of run time remaining Low Battery Two short beeps every 5 seconds less than 2 minutes of run time remaining Output Overload Bypass...

Страница 38: ...s 10 94 20 46 30 29 40 21 50 17 60 13 70 11 80 9 90 8 100 7 Internal Battery 1 External Battery Cabinet minutes 10 222 20 124 30 81 40 60 50 49 60 39 70 33 80 28 90 24 100 21 Internal Battery 2 Extern...

Страница 39: ...s The UPS will update the anticipated run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a battery...

Страница 40: ...Nominal Waveform Sinewave Main Mode Overload 200 for 96 milliseconds 131 199 for 2 seconds 112 129 for 10 seconds with transfer to bypass Bypass Protection Limits Disable Bypass operation If input vo...

Страница 41: ...W 28 12FT Electrical Characteristics Back up Time See Table 5 Battery run times Recharge Time 3 hrs to 90 capacity after full discharge into 100 load Table 8 Output distribution specifications Model N...

Страница 42: ...tery Parameters Type Valve regulated non spillable flame retardant lead acid Qty x V 20 x 12V Battery Manufacturer Part Yuasa REW 45 12 Backup Time See Table 5 Battery run times Environmental Operatin...

Страница 43: ......

Страница 44: ...bert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 monitoring emersonn...

Отзывы: